Ebmpapst CN1082 Manual

Operating and Maintenance Instructions
210-OMI12492_Iss3.doc
ORIGINAL INSTRUCTIONS Page 1 of
ebm-papst UK Ltd
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
e-mail [email protected]bmpapst.com
CN1082
Table of Contents
Introduction .............................................................................................................................................................. 2
Specification ............................................................................................................................................................ 2
Connection Details (see “Terminal Block Use” below”) ........................................................................................... 2
Fan Compatibility ..................................................................................................................................................... 2
Mechanical Outline .................................................................................................................................................. 3
Safety ...................................................................................................................................................................... 3
EMC Compliance..................................................................................................................................................... 3
ESD ......................................................................................................................................................................... 3
Installation ............................................................................................................................................................... 3
Operation ................................................................................................................................................................. 4
Fan Speed Control and LED’s: ........................................................................................................................... 4
Fan Monitor: ........................................................................................................................................................ 4
Duty Sharing (Alternate Fan Run) ....................................................................................................................... 5
Simultaneous Fan Run (Load Share) .................................................................................................................. 5
Single Fan operation ........................................................................................................................................... 5
Power-up Check.................................................................................................................................................. 5
Maintenance and Servicing ..................................................................................................................................... 5
Terminal Block Use ................................................................................................................................................. 5
PCB Component Location ....................................................................................................................................... 6
Declaration of Conformity ........................................................................................................................................
The most recent version of this document may be downloaded at: www.ebmpapst.co.uk/instructions
Part No
CN108
2
Description
Dual EC Fan Controller
Issue
Date
ug no
Comments
1
10 July 2012
1205
Signed CE front sheet & instructions clarified
2
28 Jan 2013
1205
Instructions clarified, identify Live & SELV circuits
3
12 May 201
2091
CE Certifica
te update

Operating and Maintenance Instructions
210-OMI12492_Iss3.doc
ORIGINAL INSTRUCTIONS Page 2 of
ebm-papst UK Ltd
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
e-mail [email protected]bmpapst.com
CN1082
Introduction
Commercial Dual Fan Controller, mains powered with enclosure, controls two fans Stop/Run and Low/High
speed. Speeds preset by on-board trimmers, selected by 230VAC and volt-free inputs. Optional alternate fan run
with selectable duty (changeover) period, or simultaneous (Load Share) and Single Fan operation.
With LED indicators and alarm output. Configurable options set by on-board DIP switches.
Specification
CN
108
2
Supply Voltage
V AC
20
–
253 V
AC
AC line Frequency
Hz
4
–
63 Hz
Supply Current
A
Controller
1
5
mA
, plus Fans if wired via PCB 13A max.
Alarm Relay
Contacts
1
00mA max, 60VDC max
Ope
rating Environment
-
3
0 to 60
°C
, IP66 Enclosure
Connection Details (see “Terminal Block Use” below”)
Mains Connector J1
Pin
Function
SL1
1
Switched Live 1,
Low/High fan speed
Select
i
nput
SL2
2
Switched Live 2,
Stop/Run control i
nput (shipped with lin
k to 230VAC Live to
Run
)
L
3
230VAC, Live (for
Stop/Run control
link)
L
4
230VAC, Live (
Supply
to Fan
1
)
L
5
230VAC, Live (Input)
L
6
230VAC, Live (
Supply
to Fan
2
)
N
230VAC, Neutral (spare)
N
8
230VAC, Neutral (
Supply
to Fan
1
)
N
9
230VAC, Neutra
l (Input)
N
10
230VAC, Neutral (
Supply
to Fan
2
)
E
11
Earth (
Supply
to Fan
1
)
E
12
Earth (Input)
E
13
Earth (
Supply
to Fan
2
)
E
14
Earth (spare)
Control Connector J2
Pin
Function
1
Alarm Relay, Contact A
(Contacts Closed = No Alarm)
2
Alarm Relay,
Contact B
3
Fan 1 Speed Control PWM
Output
Fan
1
4
Fan 1 Tachome
ter Open Collector / Relay Input
5
Fan 1 GND / 0V
6
Fan 2 Speed Control PWM
Output
Fan
2
7
Fan 2 Tachometer Open Collector / Rela
y Input
8
Fan 2 GND / 0V
9
BMS
Low/High fan speed
Select Input, Volt Free Contacts
10
0V for BMS
input
11
Stop/Run control i
nput
, Volt Free Contacts (shipped with link to 0V to
Run
)
12
0V for Stop/Run
input
13
Remote
Low/High fan speed
Select Input, Volt Free Contacts
14
0V for Remote Low/High
input
Note: all “0V” terminals on J2 are commoned.
Fan Compatibility
Fan Speed control outputs compatible with EC 0-10V or Open Collector PWM speed controlled fans, 2kHz PWM,
maximum of 12 EC Fans per 0-10V output.
Tachometer / Relay input compatible with Open Collector tachometer or Relay Alarm fans.

Operating and Maintenance Instructions
210-OMI12492_Iss3.doc
ORIGINAL INSTRUCTIONS Page 3 of
ebm-papst UK Ltd
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
e-mail [email protected]bmpapst.com
CN1082
Mechanical Outline
Enclosure 180(L) x 94(W) x 5 (H), transparent lid for LED visibility, fixing centres 165 x 9mm
PCB 15 mm x 1mm, Hole centres 146mm x 60mm. Height 31mm max.
LED Identification LED “Fan1” and “Fan2” Run and Alarm, indicated by PCB silk screen legend
LED “En” Run Enable and LED “B” High Speed, indicated by PCB silk screen legend
Trimmer Identification Trimmer indicated by PCB silk screen legend, R1, R2 and R3
IP Rating IP66 Enclosure
Cable Glands Not included. Enclosure has “knock-outs” to suit 16mm or 20mm glands.
Safety
•Installation must be by qualified personnel in accordance with local applicable standards.
•This equipment must be Earthed.
•Access is limited to service personnel only.
•Residual risk of contact with fan. Maintenance personnel should take due care and attention.
•Complies with Low Voltage Directive 3 /23/EEC as amended by 93/68/EEC
•Complies with EN60335-1 - Specification for safety of household and similar electrical appliances
•Connector J1 Terminals SL1 and SL2 may be live even with the controller supply disconnected
•EC Fans use Capacitors to store mains voltage. Contact with the mains wiring must be avoided for 5
minutes following supply disconnection.
EMC Compliance
BS EN61000-6-3:200 (Emissions), Radiated BS EN55022:2010 Class B, Conducted BS EN55022:2010 Class B
BS EN61000-6-2:2005 (Immunity) ESD EN61000-4-2:1995 +A1+A2, Radiated EN61000-4-3:2002 +A1+A2, Fast
Transients EN61000-4-4:2004 Surges EN61000-4-5:1995 +A1+A2, Conducted EN61000-4-6:200 , Voltage Dips
/ Interruptions EN61000-4-11:2004
ESD
Many modern electronic components are susceptible to damage from Electro Static Discharge (Static Electricity).
During commissioning, avoid unnecessary contact with electronic components on PCB’s.
PCB’s which are Static Sensitive should be stored in anti-static packaging until installed.
Installation
General:
See “Safety” information above.
For connections, see Connection Details table above. Route control wiring separately from AC mains wiring.
Remove enclosure knock-outs as required to fit cable glands, taking care not to damage the PCB. Cable entry at
enclosure end is recommended.
Tools:
A 2.5mm flat screwdriver is recommended for the screw terminal block clamps and Variable Resistor adjustment.
A voltmeter is required during commissioning.
230VAC Supply:
Controller connection to 230VAC supply must be fused to 13A maximum.
The supply for single phase fans up to 13A total load may be connected via this control PCB, connect Fans to
230VAC output and Earth output terminals. For higher currents or 3-phase fans route supply direct to fans.
Fans:
Connect fan supply, speed control and tachometer leads, see table above for connections. If fan has a 10V
output wire cut back & insulate. If fans are Alarm Relay type (not Tachometer), connect Fan N/C & COM between
tachometer Input and 0V. If fan monitoring is not required, then link tachometer Input to 0V to prevent alarms.
Select Inputs:
Connect Run/Stop and Speed/Set-point select inputs as required for the application, see Tables below.
PC Switches and Variable Resistors:
Set DIP Switches and Variable Resistors as required, see tables and procedures below.

Operating and Maintenance Instructions
210-OMI12492_Iss3.doc
ORIGINAL INSTRUCTIONS Page 4 of
ebm-papst UK Ltd
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
e-mail [email protected]bmpapst.com
CN1082
DIP Switch
Position
OFF
ON
1
Alternate Fan Run
Simultaneous Fan
Run
2
, 3
Alt
ernate Fan
Run
Changeover
P
eriod, see table
4
No
High
-
Speed
Start
Delay
High
-
Speed
Start Delay,
Three minutes
5
Two Fans
Single Fan
6
RESERVED, MUST BE [Off]
7
Fan 1
Speed Control
, Open Collector
Fan 1
Speed Control
, 0
-
10V
8
Fan 2
Speed Control
, Open
Collector
Fan 2
Speed Control
, 0
-
10V
DIP Switch
Alternate Fan
Run
Changeover Period
(Hours)
2
3
Off
Off
3
ON
Off
6
Off
ON
12
ON
ON
24
Potentiometers
RV1
Fan Low Speed, 20% to 100%
RV2
Fan High Speed, 20% to 100%
RV3
High Speed Run
-
on period,
0
-
50 minutes
Operation
Fan Speed Control and LED’s:
1) Stop/Run: Fans will not run unless both Run enable signals (Switched Live and Volt Free) are present.
LED “En” will be illuminated if Fan Run is enabled, and will flash mostly off if not. Unit is shipped with
both Run enables linked. “En” LED Off indicates either no 230VAC supply or a PCB fault.
2) High Speed: Fans will run at High speed if any High Speed signal (Switched Live or Volt Free) is active,
LED “B” illuminated. If the “High” potentiometer set speed is lower than the “Low” potentiometer set
speed the fan will continue at the “Low” set speed.
3) High Speed Delay Start: Enabled by DIP Switch. Fan Speed Outputs will remain at Low speed after the
High Speed Input becomes active, for this timer period. (exception - BMS input responds immediately) If
High Speed Delay timer is running LED “B” will flash, mostly Off.
4) High Speed Run-on: Fan Speed Outputs will remain at High speed after the “High Speed” input ceases
to be active, for a period set by R3. (exception - BMS input responds immediately) If Run-on timer is
running LED “B” will flash, mostly On.
Fan Monitor:
1) “FAN1” and “FAN2” LEDS, Green LED = Fan Running, Red LED = Fan Alarm
2) Alarm Relay output: Contacts closed = No Alarm, Contacts Open = Fan Alarm or Power Fail.

Operating and Maintenance Instructions
210-OMI12492_Iss3.doc
ORIGINAL INSTRUCTIONS Page 5 of
ebm-papst UK Ltd
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
e-mail [email protected]bmpapst.com
CN1082
Duty Sharing (Alternate Fan Run)
The controller will run each fan alternately.
Each fan will run for a period selected by the DIP Switch setting, see table.
In the event of a fan alarm (detected by controller monitoring the Fan Relay / Tachometer signal) the controller
will:
1) Automatically switch over to the alternate fan
2) Indicate the Fan Alarm by means of the Fan red LED and Alarm Relay
Note: at the end of each Duty Share period the controller will select the alternate fan. If the alternate fan is faulty
the controller will swap back.
Simultaneous Fan Run (Load Share)
In this mode, for settings above the equivalent of two fans on minimum speed, both fans will run and the load will
be shared. For speed settings below this the fans will run alternately to allow the maximum airflow range.
In the event of a Fan Alarm the remaining fan speed will be doubled (up to full speed) to compensate, or for low
speed setting the alternate fan will run.
Single Fan operation
For single fan operation connect the fan to Fan 1 controller terminals. Set the DIP switch for Single Fan operation
to suppress alarms from the unfitted fan.
Power-up Check
At power-up all LED’s will illuminate and Alarm Relay energise for a few seconds. If only one fan is running the
controller will run Fan 1 briefly to check it is operating correctly, then switch to Fan 2 to check that fan. Fan run
check inhibited if Enable not active.
Maintenance and Servicing
The PCB has no replaceable parts, if a fault develops return the PCB to the manufacturer.
Terminal lock Use
The terminal blocks fitted are operated as follows:
Insert a 2.5mm or 3mm flat blade screwdriver fully into the upper hole as shown, to open the terminal wire entry.
Insert the wire into the lower hole, then remove the screwdriver to leave the wire clamped in the terminal.
Alternatively, open the wire entry by inserting the screwdriver fully from the opposite side of the connector as
shown
Insert the wire into the lower hole, then remove the screwdriver to leave the wire clamped in the terminal.
Check wire clamp has moved clear
to
allow wire entry

Operating and Maintenance Instructions
210-OMI12492_Iss3.doc
ORIGINAL INSTRUCTIONS Page 6 of
ebm-papst UK Ltd
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
e-mail [email protected]bmpapst.com
CN1082
PC Component Location
Key PCB components are identified below
J1 Pin1 High Speed Run Enabled S1
LED “ ” LED “En”
Live Circuit SELV Circuit
R1 R3 Fan1 Run Fan2 Run
R2 LED LED
Fan1 Alarm Fan2 Aalrm J2 Pin1
LED LED

Operating and Maintenance Instructions
210-OMI12492_Iss3.doc
ORIGINAL INSTRUCTIONS Page of
ebm-papst UK Ltd
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
e-mail [email protected]bmpapst.com
CN1082
Declaration of Conformity
12/05/201 10:14:52
Table of contents
Other Ebmpapst Controllers manuals