Eldes ET08 User manual

COMMUNICATOR
ET08 / ET081

Copyright ©“ELDES UAB”, 2011. All rights reserved.
It is strictly forbidden to copy and distribute information in this document or pass to a third party without an advanced written authorization from
“ELDES UAB”. “ELDES UAB”reserves the right to update or modify this document and/or related products without a warning. Hereby, ELDES UAB
declares that this communicator ET08 / ET081 is in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC.
The declaration of conformity may be consulted at www.eldes.lt
User Manual v1.2
Safety instructions
Please read and follow these safety guidelines in order to maintain safety of operators and people around:
• GSM communicator ET08 / ET081 (further referenced as system or device) contains a radio transceiver operating in
GSM850/900/1800/1900 bands.
• DO NOT use the system where it can interfere with other devices and cause any potential danger.
• DO NOT use the system with medical devices if this is required in the manual of the medical device.
• DO NOT use the system in hazardous environment.
• DO NOT expose the system to high humidity, chemical environment or mechanical impacts.
• DO NOT attempt to personally repair the system.
• System labelling sticker is at the bottom of the device.
System ET08 / ET081 is a device mounted in limited access areas. Any system repairs must be done only by qualied, safety
aware personnel.
Mains power must be disconnected before any installation or tuning work starts. The system installation or maintenance
must not be done during stormy conditions.
The system must be powered by main 10-24V 300mA power supply which must be approved by LST EN 60950-1 stan-300mA power supply which must be approved by LST EN 60950-1 stan-
dard and be easily accessible.
Any additional devices linked to the system ET08 / ET081 (computer, sensors, relays etc.) must be approved by LST EN 60950-
1 standard.
External power supply can be connected to AC mains only inside ins-
tallation room with automatic 2-pole circuit breaker capable of discon-
necting circuit in the event of short circuit or over-current condition.
Open circuit breaker must have a gap between connections of more
than 3mm and the disconnection current is 5A.
Fuse F1 model - miniSMDC 500mA. Blown fuse cannot be replaced by the user and the replacement fuses have to be exactly
the same as indicated by the manufacturer.
The device is fully turned o by disconnecting 2-pole switch o device of the external power supply or any other linked
device that the system ET08 / ET081 is powered from.
The WEEE (Waste Electrical and Electronic Equipment) marking on this product (see left) or its documentation indicates that in the EU
the product must not be disposed of together with household waste.
Phase
AC 230V
50 Hz/DC 24V
USB cable
Null
ET08/
ET081
PE

Limited Liability
The buyer must agree that the system will redu-
ce the risk of re, theft, burglary or other dangers
but does not guarantee against such events. “EL-
DES UAB” will not take any responsibility regarding
personal, property or revenue loss while using the
system. “ELDES UAB” responsibility according to
local laws does not exceed value of the purchased
system. “ELDES UAB” is not aliated with GSM ope-
rators providing cellular services, therefore is not
responsible for network services, coverage or its
operation.
Manufacturer Warranty
The system carries a 24-month warranty by the
manufacturer “ELDES UAB”.
Warranty period starts from the day the system
has been purchased by the end user. The warranty
is valid only if the system has been used as inten-
ded, following all guidelines listed in the manual
and within specied operating conditions. Receipt
with purchase date must be kept as a proof.
The warranty is voided if the system has been
exposed to mechanical impacts, chemicals, high
humidity, uids, corrosive and hazardous environ-
ment or other force majeure factors.
Package Content
1. System ET08 / ET081...........................................1 pcs
2. ET08 / ET081 user manual ................................1 pcs
3. GSM antenna.........................................................1 pcs
4. Jumpers..................................................................4 pcs.
5. Fastening holders ...............................................4 pcs.
About User Manual
This document describes communicator ET08 /
ET081, its operation and installation. It is very im-
portant to read User Manual before start using the
system.
CONTENTS
1. General Information..................................................................... 4
1.1 Operation Description ...............................................................................4
2. Technical Specications .............................................................. 5
2.1 Electrical & Mechanical Specications .................................................5
2.2 Main Unit, Connector, Pin & LED Functionality.................................5
2.2.1 Main Unit Functionality..........................................................................6
2.2.2 Connector Functionality........................................................................6
2.2.3 Pin Functionality.......................................................................................6
2.2.4 LED Functionality .....................................................................................6
2.3 Connection Circuit ......................................................................................7
3. Installation.................................................................................... 8
4. Communication Modes................................................................ 9
4.1 Communication Mode 1. Data Transmission from Alarm
System to Monitoring Station via GSM Audio Channel ............9
4.2 Communication Mode 2. Data Transmission from Alarm
System to Preset User (-s) by SMS. ................................................... 10
4.3 Communication Mode 3. Data Transmission
from Alarm System to Monitoring Station via GSM
Audio Channel and SMS Messages to Preset User (-s)............. 11
4.4 Communication Mode 4. Data Transmission from
Alarm System to Monitoring Station via GPRS Network.........12
4.5 Communication Mode 5. Data Transmission
from Alarm System to Monitoring Station via PSTN
using GSM Audio Channel as Backup Connection .................... 13
4.6 Communication Mode 6. Data Transmission
from Alarm System to Monitoring Station via PSTN
using SMS Messages as Backup Connection ...............................14
4.7 Communication Mode 7. Data Transmission
from Alarm System to Monitoring Station via PSTN
using GSM Audio Channel as Backup Connection
and SMS Messages to Preset User (-s).............................................15
4.8 Communication Mode 8. Data Transmission
from Alarm System to Monitoring Station via PSTN
using GPRS Network as Backup Connection................................ 16
4.9 Communication Mode 9. Data Transmission from Alarm
System to Monitoring Station via PSTN through PBX
using GSM Audio Channel as Backup Connection .................... 17
4.10 Communication Mode 10. Data Transmission from Alarm
System to Monitoring Station via PSTN through PBX
using SMS Messages as Backup Connection ...............................18
4.11 Communication Mode 11. Data Transmission
from Alarm System to Monitoring Station via PSTN
through PBX using GSM Audio Channel as a Backup
Connection and SMS Messages to Preset User (-s)....................19
4.12 Communication Mode 12. Data Transmission from
Alarm System to Monitoring Station via PSTN through
PBX using GPRS Network as Backup Connection....................... 20
5. SMS Commands* ........................................................................22
6. Appendix ..................................................................................24
6.1 Restoring Default Parameters ............................................................ 24
6.2 Upgrading Firmware................................................................................24
6.3 ELDES Conguration Tool Software...................................................24
6.4 Technical Support.....................................................................................25

4
1. General Information
Communicator ET08 / ET081 is a device for transmitting data from alarm system to monitoring station via:
• GSM audio channel;
• GSM audio channel and/or to users via SMS message;
• Telehone landline (PSTN);
• GPRS network.
The system can be used in the following applications:
• Property security.
• GSM network backup for PSTN.
1.1 Operation Description
ET08 / ET081 communicator acts as a gateway between the alarm system and monitoring station providing a dial tone and fully
replacing the landline (PSTN). The communicator noties monitoring station (ET081 ONLY) and/or the preset user by SMS message
in case PSTN is unavailable, has been cut o or disconnected by PSTN provider. ET08 / ET081 supports only outgoing calls. DTMF
number dialing mode in alarm system must be enabled.
ET08 / ET081 can detect temporary service suspension by the service provider for technical or billing reasons even if a dial tone is
still present (optional feature).
ET08 / ET081 features several communication ways between alarm system and monitoring station via:
1. GSM audio channel;
2. PSTN using GSM audio channel as backup connection;
3. SMS messages to preset users;
4. PSTN using GSM audio channel as backup connection with data duplication to preset users via SMS;
5. GPRS network.
6. PSTN using GPRS network as backup connection.
Please, refer to chapter 4. Communication Modes for more details.
The system ET08 / ET081 has 1 digital input (normally open) for sensor connection. The open collector output allows to connect
and control 1 electronic appliance on receipt of the correct SMS text message from one of the preset phone numbers. This feature
provides control over heating, lighting, gates, blinds etc.
ELDES Conguration Tool software is used to congure the system to operate in one of its communication modes, providing data
transmission either via SMS text message or via GPRS. The device has to be connected to the computer using a USB cable. Please,
refer to software‘s HELP section for more details.

USER MANUAL ELDES ET08 / ET081 V1.2 5
2. Technical Specications
2.1 Electrical & Mechanical Specications
Power Supply 10-24V 300mA max
Current Used in Standby Mode 120mA max
GSM Modem Frequency 850/900/1800/1900 MHz
Supported Protocols Contact ID, 4+2**
Maximum Number of Users to whom SMS Messages are De-
livered
5
Number of “Low” Level (Negative) Digital Inputs* 1
Allowable Input Values* Voltage: 0... 1.45V; current: 0.8... 0.6mA
Input Type NO (normally open)
Number of Outputs* 1
Output Circuit* Open collector output. Output is pulled to COM when turned
on.
Maximum Allowed Output Values* Voltage: 30V ; current: 50 mA
Dimensions 130 x 73 mm
Operating temperature range -20...+55oC
Generated Phone Line Voltage 18 V
Generated Phone Line Current 25 mA
Generated Phone Line Impedance 600
Dial Tone Frequency of Generated Phone line 350 Hz
* only in ET081
** 4+2 protocol operates in communication mode 1, 5 and 9 ONLY (via GSM audio channel).
2.2 Main Unit, Connector, Pin & LED Functionality
GSM
MODEM
INFO
STATUS
GSM
USB
DEFAULT
F1
L1 L2 L3 L4 RING TIP C1 N.C.DC+ COM Z1 N.C.
MODE
SET
B1 B2
For congurations
PROG
SIM CARD
ANT
Fig. No 1

6
2.2.1 Main Unit Functionality
GSM MODEM GSM network 850/900/1800/1900 MHz modem
SIM CARD SIM card slot / holder
ANT GSM antenna SMA type connector
F1 Fuse model – miniSMDC 500mA
USB Mini USB port
2.2.2 Connector Functionality
Labelling Description
L1 - L4 Landline or PBX contacts (according to backup mode)
RING RING contact
TIP TIP contact
C1 Output
DC+ Positive power supply contact
COM Negative power supply contact / Common contact
Z1 Input
N.C. Not connected
2.2.3 Pin Functionality
Labelling Description
DEFAULT For restoring factory default settings
SET For enabling communication modes
MODE For enabling communication modes
B1, B2 For communication backup connection
PROG Not used
2.2.4 LED Functionality
Labelling Description
INFO Working mode indicator
STATUS Device activity indicator
GSM GSM network quality indicator
GSM Signal Strength Indication
GSM signal strength is indicated by GSM LED. To ensure the best quality of the network adjust the position of GSM antenna and
nd the strongest possible signal by observing the GSM LED indications.
GSM LED Indication GSM Signal Strength
O No connection
Flashing every 3 seconds The connection is not reliable
Flashing every 1 second Satisfactory
Flashing several times per second Good
On Excellent
It is recommended to install the GSM antenna away from the alarm system to ensure better quality of the audio signal. It is not
recommend to install the antenna inside the metal enclosure.

USER MANUAL ELDES ET08 / ET081 V1.2 7
There are also a few other indicators - device activity indicator STATUS and working mode indicator INFO.
Device Activity Indication
STATUS LED Indication Meaning
O No power supply or some fault is present
Flashing several times per second SIM card is not inserted / insterted improperly
On Device is operating and ready for use
Working Mode Indication
INFO LED Indication Meaning
O Device is in standby mode
Flashing several times
per second
Device retransmits the data sent from alarm system to the monitoring station (this
indication is possible when device is operating in communication mode 1)
On Device is decoding Contact ID data to user-understandable text format.
2.3 Connection Circuit
COM connectors of ET08 / ET081 and alarm system unit must be connected.
ET081 Input Z1 is connected to PGM output of alarm system unit if PGM output is im-
plemented as open collector circuit or any other circuit and if it commutes with COM.
It is also possible to connect motion sensor or any other sensor to ET081 Z1 input.
ET081 C1 output can be connected to input of electronic appliance and if it commute
with COM. This connection allows to control heating, lighting, gates, blinds, water
pump etc.
Fig. No 2
* - only in ET081
ET08 / ET081
Alarm system
or other appliance
+12V
PGM
C1*
DC+ COM
Z1*

8
3. Installation
NOTE: Due to GSM network characteristics it is recommended that ET08/ET081 be equipped with a SIM card from the same
GSM operator who provided the SIM cards used by users who will receive messages from the system. Thus you will ensure the
quickest SMS message delivery and receipt.
NOTE: To ensure maximum system operation reliability we recommend not to use pay-as-you-go SIM cards. If the balance is
insucient the system will not be able to inform users by SMS or send Contact ID messages.
IMPORTANT: Power supply at alarm system must be disconnected before any installation or tuning work.
The system can be installed in a metal or non-ammable plastic enclosure together with alarm control panel. When the metal
enclosure is also used it is necessary to ground the enclosure using yellow/green colour cable. For the connection use 0.50 mm2
1 thread cable.
Device Installation and Pre-operation:
1. Fasten the system in the enclosure using fastening holders.
2. Place SIM card into the SIM card slot and x it with holder after making sure that SIM card PIN code is disabled. PIN code
can be disabled by inserting the SIM card into mobile phone and following proper menus. SIM card should not have any
remaining SMS messages.
3. Connect the GSM antenna to SMA connector. It is not recommended to turn on the device without GSM antenna connec-
ted.
4. Connect the circuit according to desired communication mode (see chapter 4. Communication Modes)
5. The system should start in less than a minute. GSM LED indicator should be blinking or be ON indicating successful con-
nection to GSM network.

USER MANUAL ELDES ET08 / ET081 V1.2 9
4. Communication Modes
ATTENTION: DTMF phone number dialing mode must be enabled on alarm system, activated Contact ID or 4+2 data
transmission protocol and monitoring station phone number set with international code, i.e. For UK London 20xxxxxxxx or
004420xxxxxxxx. The <plus> character is not allowed.
4.1 Communication Mode 1. Data Transmission from Alarm System
to Monitoring Station via GSM Audio Channel
In this mode the communicator retransmits Contact ID or 4+2 data sent from alarm system to monitoring station via GSM audio
channel. There is NO backup connection for this mode.
NOTE: No additional communicator conguration is required for this mode.
1. Connect the circuit as indicated in Fig. No. 3 – connect telephone contacts of the alarm system RING/TIP to RING/TIP con-
tacts of the communicator.
2. Connect power supply to DC+/COM contacts. Power supply is usually used as AUX- and AUX+ output of alarm system.
3. No jumpers have to be set on any pins. See Fig. No. 4 for correct jumper position.
L1 L2 L3 L4 RING TIP C1 DC+ COM Z1 N.C. N.C.
AUX+ AUX-
ALARM SYSTEM
RING/TIP
Fig. No 3
Fig. No 4

10
4.2 Communication Mode 2. Data Transmission
from Alarm System to Preset User (-s) by SMS.
In this mode the communicator retransmits Contact ID data sent from alarm system and decodes it to user-understandable text
format which is sent to preset user (-s) by SMS message. There is NO backup connection for this mode.
NOTE: User phone number (-s) must be set for the communicator using ELDES Conguration Tool. Please, refer to software's
HELP section for more details.
ATTENTION: It is also necessary to set monitoring station phone number on alarm system in this mode. In such case you can
use any number (one digit is enough).
1. Connect the circuit as indicated in Fig. No. 5 – connect telephone contacts of the alarm system RING/TIP to RING/TIP con-
tacts of the communicator.
2. Connect power supply to DC+/COM contacts. Power supply is usually used as AUX- and AUX+ output of alarm system.
3. Set the jumper on MODE pins. See Fig. No. 6 for correct jumper position.
L1 L2 L3 L4 RING TIP C1 DC+ COM Z1 N.C. N.C.
AUX+ AUX-
ALARM SYSTEM
RING/TIP
Fig. No 5
Fig. No 6

USER MANUAL ELDES ET08 / ET081 V1.2 11
4.3 Communication Mode 3. Data Transmission from Alarm System to
Monitoring Station via GSM Audio Channel and SMS Messages to Preset User (-s)
In this mode the communicator retransmits Contact ID data sent from alarm system to monitoring station via GSM audio channel.
In addition, the data is duplicated and decoded data to user-understandable text format and sent to preset user (-s) by SMS mes-
sage. There is NO backup connection for this mode.
NOTE: User phone number (-s) must be set for the communicator using ELDES Conguration Tool. Please, refer to software's
HELP section for more details.
1. Connect the circuit as indicated in Fig. No. 7 – connect telephone contacts of the alarm system RING/TIP to RING/TIP con-
tacts of the communicator.
2. Connect power supply to DC+/COM contacts. Power supply is usually used as AUX- and AUX+ output of alarm system.
3. Set the jumper on SET pins. See Fig. No. 8 for correct jumper position.
L1 L2 L3 L4 RING TIP C1 DC+ COM Z1 N.C. N.C.
AUX+ AUX-
ALARM SYSTEM
RING/TIP
Fig. No 7
Fig. No 8

12
4.4 Communication Mode 4. Data Transmission from Alarm System
to Monitoring Station via GPRS Network
NOTE: EGR100 software is required for this communication mode. The software is freeware and can be downloaded from
ELDES website at www.eldes.lt
In this mode the communicator retransmits Contact ID data via GPRS network sent from alarm system to monitoring station. There
is NO backup connection for this mode.
I. The following communicator GPRS settings must be set up using ELDES Conguration Tool software:
• CID over GPRS Enabled – enables Contact ID data transmission via GPRS network.
• APN – access-point-name provided by GSM operator.
• User Name – user name provided by GSM operator.
• Password – password provided by GSM operator.
• Server IP – external IP address of the computer (router) running EGR100 software.
•Server Port – forwarded UDP port for the computer running EGR100 software.
Please, refer to ELDES Conguration Tool software's HELP section for more details.
II. The following settings must be set up in EGR100 software:
• TCP/UDP Server Port - forwarded port for communication with the device via GPRS.
Please, refer to EGR100 software's user guide for more details.
NOTE: UDP port must be set the same both on the communicator using ELDES Conguration Tool and in EGR100 software.
1. Connect the circuit as indicated in Fig. No. 9 – connect telephone contacts of the alarm system RING/TIP to RING/TIP con-
tacts of the communicator.
2. Connect power supply to DC+/COM contacts. Power supply is usually used as AUX- and AUX+ output of alarm system.
3. Set the jumpers on SET and MODE pins. See Fig. No. 10 for correct jumper position.
L1 L2 L3 L4 RING TIP C1 DC+ COM Z1 N.C. N.C.
AUX+ AUX-
ALARM SYSTEM
RING/TIP
Fig. No 9
Fig. No 10

USER MANUAL ELDES ET08 / ET081 V1.2 13
4.5 Communication Mode 5. Data Transmission from Alarm System to Monitoring
Station via PSTN using GSM Audio Channel as Backup Connection
In this mode the communicator retransmits Contact ID and 4+2 data via landline (PSTN) sent from alarm system to monitoring sta-
tion. The communicator also monitors the voltage (dial tone monitoring optional) on the PSTN and in case the PSTN is unavailable,
disconnected or cut o (voltage drops below 4V), the system:
• switches to backup connection – GSM audio channel,
•noties monitoring station about PSTN failure,
• continues transmitting data to monitoring station via GSM audio channel until the PSTN is restored.
NOTE: Notication about PSTN loss/restore (if required) has to be enabled for the communicator using ELDES Conguration
Tool. Please, refer to software‘s HELP section for more details.
1. Connect the circuit as indicated in Fig. No. 11 – connect telephone contacts of the alarm system RING/TIP to RING/TIP
contacts of communicator.
2. Connect L3/L4 contacts to landline (PSTN).
3. Connect power supply to DC+/COM contacts. Power supply is usually used as AUX- and AUX+ output of alarm system.
4. Set the jumpers on B1 and B2 pins. See Fig. No. 12 for correct jumper position.
ALARM SYSTEM
L1 L2 L3 L4 RING
To landline
(PSTN)
TIP DC+ COM Z1 N.C. N.C.C1
AUX+ AUX-
RING/TIP
Fig. No 11
Fig. No 12

14
4.6 Communication Mode 6. Data Transmission from Alarm System to Monitoring
Station via PSTN using SMS Messages as Backup Connection
In this mode the communicator retransmits Contact ID data via landline (PSTN) sent from alarm system to monitoring station. The
communicator also monitors the voltage (dial tone monitoring optional) on the PSTN and in case the PSTN is unavailable, discon-
nected or cut o (voltage drops below 4V), the system:
• sends an SMS report to the preset user (-s) on PSTN failure,
• decodes data to user-understandable text format and continues transmitting it to preset user (-s) by SMS message until the
PSTN is restored.
NOTE: User phone number (-s) must be set for the communicator using ELDES Conguration Tool. Please, refer to software's
HELP section for more details.
1. Connect the circuit as indicated in Fig. No. 13 – connect telephone contacts of the alarm system RING/TIP to RING/TIP
contacts of communicator.
2. Connect L3/L4 contacts to landline (PSTN).
3 Connect power supply to DC+/COM contacts. Power supply is usually used as AUX- and AUX+ output of alarm system.
4. Set the jumpers on B1, B2 and MODE pins. See Fig. No. 14 for correct jumper position.
ALARM SYSTEM
L1 L2 L3 L4 RING
To landline
(PSTN)
TIP DC+ COM Z1 N.C. N.C.C1
AUX+ AUX-
RING/TIP
Fig. No 13
Fig. No 14

USER MANUAL ELDES ET08 / ET081 V1.2 15
4.7 Communication Mode 7. Data Transmission from Alarm System
to Monitoring Station via PSTN using GSM Audio Channel as
Backup Connection and SMS Messages to Preset User (-s)
In this mode the communicator retransmits Contact ID data via landline (PSTN) sent from alarm system to monitoring station. The
communicator also monitors the voltage (dial tone monitoring optional) on the PSTN and in case the PSTN is unavailable, discon-
nected or cut o (voltage drops below 4V), the system:
• switches to backup connection – GSM audio channel,
•noties monitoring station about PSTN failure,
• sends an SMS report to the preset user (-s) on PSTN failure,
• continues transmitting data to monitoring station via GSM audio channel until the PSTN is restored,
• duplicates and decodes data to user-understandable text format and sends it to preset user (-s) by SMS message until the
PSTN is restored.
NOTE: User phone number (-s) must be set and notication about PSTN loss/restore (if required) has to be enabled for the
communicator using ELDES Conguration Tool. Please, refer to software‘s HELP section for more details. for more details.
1. Connect the circuit as indicated in Fig. No. 15 – connect telephone contacts of the alarm system RING/TIP to RING/TIP
contacts of communicator.
2. Connect L3/L4 contacts to landline (PSTN).
3. Connect power supply to DC+/COM contacts. Power supply is usually used as AUX- and AUX+ output of alarm system.
4. Set the jumpers on B1, B2 and SET pins. See Fig. No. 16 for correct jumper position.
ALARM SYSTEM
L1 L2 L3 L4 RING
To landline
(PSTN)
TIP DC+ COM Z1 N.C. N.C.C1
AUX+ AUX-
RING/TIP
Fig. No 15
Fig. No 16

16
4.8 Communication Mode 8. Data Transmission from Alarm System to
Monitoring Station via PSTN using GPRS Network as Backup Connection
In this mode the communicator retransmits Contact ID data via landline (PSTN) sent from alarm system to monitoring station. The
communicator also monitors the voltage (dial tone monitoring optional) on the PSTN and in case the PSTN is unavailable, discon-
nected or cut o (voltage drops below 4V), the system:
• switches to backup connection – GPRS network,
•noties monitoring station about PSTN failure,
• continues transmitting data to monitoring station via GPRS network until the PSTN is restored.
NOTE: Notication about PSTN loss/restore (if required) has to be enabled for the communicator using
Please, refer to software‘s HELP section for more details.
I. The following communicator GPRS settings must be set up using ELDES Conguration Tool software:
•CID over GPRS Enabled – enables Contact ID data transmission via GPRS network.
• APN – access-point-name provided by GSM operator.
• User Name – user name provided by GSM operator.
• Password – password provided by GSM operator.
• Server IP – external IP address of the computer (router) running EGR100 software.
• Server Port – forwarded UDP port for the computer running EGR100 software.
Please, refer to ELDES Conguration Tool software's HELP section for more details.
II. The following settings must be set up in EGR100 software:
• TCP/UDP Server Port - forwarded port for communication with the device via GPRS.
Please, refer to EGR100 software's user guide for more details.
NOTE: UDP port must be set the same both on the communicator using ELDES Conguration Tool and in EGR100 software.
1. Connect the circuit as indicated in Fig. No. 17 – connect telephone contacts of the alarm system RING/TIP to RING/TIP
contacts of communicator.
2. Connect L3/L4 contacts to landline (PSTN).
3. Connect power supply to DC+/COM contacts. Power supply is usually used as AUX- and AUX+ output of alarm system.
4. Set the jumpers on B1, B2, SET and MODE pins. See Fig. No. 18 for correct jumper position.
ALARM SYSTEM
L1 L2 L3 L4 RING
To landline
(PSTN)
TIP DC+ COM Z1 N.C. N.C.C1
AUX+ AUX-
RING/TIP
Fig. No 17
Fig. No 18

USER MANUAL ELDES ET08 / ET081 V1.2 17
4.9 Communication Mode 9. Data Transmission from Alarm System to Monitoring
Station via PSTN through PBX using GSM Audio Channel as Backup Connection
In this mode the communicator retransmits alarm system Contact ID or 4+2 data to monitoring station via landline (PSTN) through
private branch exchange station (PBX). The communicator also monitors the voltage (dial tone monitoring optional) on the exter-
nal PSTN. In case the external PSTN is unavailable, disconnected or cut o (voltage drops below 4V), the system:
• switches to backup connection – GSM audio channel,
•noties monitoring station about PSTN failure,
• continues transmitting data to monitoring station via GSM audio channel until the external PSTN is restored.
NOTE: Notication about PSTN loss/restore (if required) has to be enabled for the communicator using ELDES Conguration
Tool. Please, refer to software‘s HELP section for more details.
1. Connect the circuit as indicated in Fig. No. 19 – connect telephone contacts of the alarm system RING/TIP to RING/TIP
contacts of communicator.
2. Connect L1/L2 contacts to external landline (PSTN).
3. Connect L3/L4 contacts to internal landline (PSTN) of PBX.
4. Connect power supply to DC+/COM contacts. Power supply is usually used as AUX- and AUX+ output of alarm system.
5. No jumpers have to be set on any pins. See Fig. 20 for correct jumper position.
ALARM SYSTEM
L1 L2 L3 L4
RING
To external
landline (PSTN)
Internal
landline (PSTN)
TIP
RING TIP DC+ COM Z1 N.C.C1 N.C.
AUX+ AUX-
PBX
Fig. No 19
Fig. No 20
FOR ADVANCED USERS ONLY!

18
4.10 Communication Mode 10. Data Transmission from Alarm System to Monitoring
Station via PSTN through PBX using SMS Messages as Backup Connection
In this mode the communicator retransmits alarm system Contact ID data to monitoring station via landline (PSTN) through pri-
vate branch exchange station (PBX). The communicator also monitors the voltage (dial tone monitoring optional) on the external
PSTN. In case the external PSTN is unavailable, disconnected or cut o (voltage drops below 4V), the system:
• sends an SMS report to the preset user (-s) on PSTN failure,
• decodes data to user-understandable text format and continues transmitting it to preset user (-s) by SMS message until the
external PSTN is restored.
NOTE: User phone number (-s) must be set and notication about PSTN loss/restore (if required) has to be enabled for the
communicator using ELDES Conguration Tool. Please, refer to software‘s HELP section for more details.
1. Connect the circuit as indicated in Fig. No. 21 – connect telephone contacts of the alarm system RING/TIP to RING/TIP
contacts of communicator.
2. Connect L1/L2 contacts to external landline (PSTN).
3. Connect L3/L4 contacts to internal landline (PSTN) of PBX.
4. Connect power supply to DC+/COM contacts. Power supply is usually used as AUX- and AUX+ output of alarm system.
5. Set the jumper on MODE pins. See Fig. No. 22 for correct jumper position.
FOR ADVANCED USERS ONLY!
ALARM SYSTEM
L1 L2 L3 L4
RING
To external
landline (PSTN)
Internal
landline (PSTN)
TIP
RING TIP DC+ COM Z1 N.C.C1 N.C.
AUX+ AUX-
PBX
Fig. No 21
Fig. No 22

USER MANUAL ELDES ET08 / ET081 V1.2 19
4.11 Communication Mode 11. Data Transmission from Alarm System to
Monitoring Station via PSTN through PBX using GSM Audio Channel
as Backup Connection and SMS Messages to Preset User (-s)
In this mode the communicator retransmits alarm system Contact ID data to monitoring station via landline (PSTN) through pri-
vate branch exchange station (PBX). The communicator also monitors the voltage (dial tone monitoring optional) on the external
PSTN. In case the external PSTN is unavailable, disconnected or cut o (voltage drops below 4V), the system:
• switches to backup connection – GSM audio channel,
•noties monitoring station about PSTN failure,
• sends an SMS report to the preset user (-s) on PSTN failure,
• continues transmitting data to monitoring station via GSM audio channel until the external PSTN is restored,
• duplicates and decodes data to user-understandable text format and sends it to preset user (-s) by SMS message until the
external PSTN is restored.
NOTE: User phone number (-s) must be set and notication about PSTN loss/restore (if required) has to be enabled for the
communicator using ELDES Conguration Tool. Please, refer to software‘s HELP section for more details.
1. Connect the circuit as indicated in Fig. No. 23 – connect telephone contacts of the alarm system RING/TIP to RING/TIP
contacts of communicator.
2. Connect L1/L2 contacts to external landline (PSTN).
3. Connect L3/L4 contacts to internal landline (PSTN) of PBX.
4. Connect power supply to DC+/COM contacts. Power supply is usually used as AUX- and AUX+ output of alarm system.
5. Set the jumper on SET pins. See Fig. No. 24 for correct jumper position.
FOR ADVANCED USERS ONLY!
ALARM SYSTEM
L1 L2 L3 L4
RING
To external
landline (PSTN)
Internal
landline (PSTN)
TIP
RING TIP DC+ COM Z1 N.C.C1 N.C.
AUX+ AUX-
PBX
Fig. No 23
Fig. No 24

20
FOR ADVANCED USERS ONLY!
4.12 Communication Mode 12. Data Transmission from Alarm System to Monitoring
Station via PSTN through PBX using GPRS Network as Backup Connection
In this mode the communicator retransmits alarm system Contact ID data to monitoring station via landline (PSTN) through pri-
vate branch exchange station (PBX). The communicator also monitors the voltage (dial tone monitoring optional) on the external
PSTN. In case the external PSTN is unavailable, disconnected or cut o (voltage drops below 4V), the system:
• switches to backup connection – GPRS network,
•noties monitoring station about PSTN failure,
• continues transmitting data to monitoring station via GPRS network until the external PSTN is restored.
NOTE: Notication about PSTN loss/restore (if required) has to be enabled for the communicator using ELDES Conguration
Tool. Please, refer to software‘s HELP section for more details.
I. The following communicator GPRS settings must be set up using ELDES Conguration Tool software:
• CID over GPRS Enabled – enables Contact ID data transmission via GPRS network.
• APN – access-point-name provided by GSM operator.
• User Name – user name provided by GSM operator.
• Password – password provided by GSM operator.
• Server IP – external IP address of the computer running EGR100 software.
• Server Port – forwarded UDP port for the computer running EGR100 software.
Please, refer to ELDES Conguration Tool software's HELP section for more details.
II. The following settings must be set up in EGR100 software:
• TCP/UDP Server Port - forwarded port for communication with the device via GPRS.
Please, refer to EGR100 software's user guide for more details.
NOTE: UDP port must be set the same both on the communicator using ELDES Conguration Tool and in EGR100 software.
ALARM SYSTEM
L1 L2 L3 L4
RING
To external
landline (PSTN)
Internal
landline (PSTN)
TIP
RING TIP DC+ COM Z1 N.C.C1 N.C.
AUX+ AUX-
PBX
Fig. No 25
This manual suits for next models
1
Table of contents
Other Eldes Cell Phone manuals