
Technical Manual MSR Universal Stage Controller Page 11
Start Up Examples
MSR as Compressor Compound Controller
Requirement:
4 single compressors, stage 1 configured for
emergency operation, automatic base-load
change.
Control setpoint 2 bar, neutral zone 0,5 bar.
pressure transmitter 4-20 mA, range 0-10 bar.
Night operation (2nd setpoint) within 19:00 and
7:00, 0,5 bar higher. Forward/Backrun delay 10
sec. The user want to see the actual pressure
valueonaremotedisplaywith 0-10V-input.While
a peak load limitation via OK 1, 2 stages remain
for control purposes.
Please always note the Security
Informations on page 2 !
Select Operation Mode
•Switch OFF power supply
•Push and hold key 'P', switch ON power
•Hold key 'P' until '_ _ _' appears
•Let go key 'P'
•Select '1 _ _' by key 'ñ'
(compressor compound mode)
•Push key 'P' once
•'def' appears, default values are loaded
•Actual values appear, ready for start up.
Basic Configuration
Enter Code Number '70' at P48
•P16=1 (single compressor at relay K1)
•P17=1 (single compressor at relay K2)
•P18=1 (single compressor at relay K3)
•P19=1 (single compressor at relay K4)
•P23=1 (relay K1 inverted, load at N/C)
•P25=1 (base load change ON)
•P28=4 (transmitter with 4-20 mA signal)
Enter Code Number '88' at P48
Adjustments
•P31=10.0(press. value transmitter at 20mA)
•P32=0.0 (press. value transmitter at 4 mA)
•P04=2.0 (control setpoint)
•P10=0.5 (neutral zone / hysteresis)
•P20=10 (forward delay in sec.)
•P21=10 (backrun delay in sec.)
•P24=2 (2 stages remain after peak load lim.)
•P26=2 (OK 1 configured for peak load lim.)
•P35=2.5 (2nd control setpoint)
•P36=19 (2nd setpoint ON 'hours')
•P37=00 (2nd setpoint ON 'minutes')
•P38=07 (2nd setpoint OFF 'hours')
•P39=00 (2nd setpoint OFF 'minutes')
•P42=10
(analog output delivers 10VDC at 10bar)
•P43=0
(analog output delivers 0V at 0 bar)
•P44=1 (analog output works proportional)
•P45=--(clock time 'hours')
•P46=--(clock time 'minutes')
•P47=--(clock time 'seconds')
Display correction
TheactualpressuredisplayP01canbecalibrated
by using P29.
MSR as Condenser Fan Controller
Requirement:
3 single fans, no emergency mode, automatic
base-load change.
Control at 15, 16, 17 bar, neutral zone 0,5 bar
each. Pressure transmitter 4-20 mA, range 0-25
bar. Night operation (2nd setpoint) within 20:00
and6:30,2barhigher.Forward/Backrundelay30
sec.
Please always note the Security
Informations on page 2 !
Select Operation Mode
•Switch OFF power supply
•Push and hold key 'P', switch ON power
•Hold key 'P' until '_ _ _' appears
•Let go key 'P'
•Select '2 _ _' by key 'ñ'
(condenser fan mode)
•Push key 'P' once
•'def' appears, default values are loaded
•Actual values appear, ready for start up.
Basic Configuration
Enter Code Number '70' at P48
•P16=1 (single fan at relay K1)
•P17=1 (single fan at relay K2)
•P18=1 (single fan at relay K3)
•P25=1 (base load change ON)
•P28=4 (transmitter with 4-20 mA signal)
Enter Code Number '88' at P48
Adjustments
•P31=25.0(press. value transmitter at 20mA)
•P32=0.0 (press. value transmitter at 4 mA)
•P04=15.0 (control setpoint stage 1)
•P05=1.0
(setpoint stage 2 in a distance to P04)
•P06=1.0
(setpoint stage 3 in a distance to P05)
•P10=0.5 (neutral zone / hysteresis)
•P20=20 (forward delay in sec.)
•P21=20 (backrun delay in sec.)
•P23=0 (no emergency mode)
•P35=17.0 (2nd control setpoint 1)
•P36=20 (2nd setpoint ON 'hours')
•P37=00 (2nd setpoint ON 'minutes')
•P38=06 (2nd setpoint OFF 'hours')
•P39=30 (2nd setpoint OFF 'minutes')
•P45=--(clock time 'hours')
•P46=--(clock time 'minutes')
•P47=--(clock time 'seconds')
Display correction
TheactualpressuredisplayP01canbecalibrated
by using P29.
MSR as Brine-Chiller Controller
Requirement:
2 dual-stage compressors, no emergency mode,
automatic base load change.
Control at 4, 6, 8, 10 °C, hysteresis 0,5 K each.
Temperature sensor TF 501, night operation
(2nd setpoint) within 20:30 and 6:00, 2 K higher.
Forward/Backrun delay 25 sec.
Please always note the Security
Informations on page 2 !
Select Operation Mode
•Switch OFF power supply
•Push and hold key 'P', switch ON power
•Hold key 'P' until '_ _ _' appears
•Let go key 'P'
•Select '3 _ _' by key 'ñ'
(Brine-Chillers)
•Push key 'P' once
•'def' appears, default values are loaded
•Actual values appear, ready for start up.
Basic Configuration
Enter Code Number '70' at P48
•P16=2 (compressor 1 ON, relay K1)
(compr. 1 power stage ON, relay K2)
•P17=2 (compressor 2 ON, relay K3)
(compr. 2 power stage ON, relay K4)
•P25=1 (base load change ON)
•P28=2 (temperature sensor TF 501)
Enter Code Number '88' at P48
Adjustments
•P04=4.0 (control setpoint stage 1)
•P05=2.0
(setpoint stage 2 in a distance to P04)
•P06=2.0
(setpoint stage 3 in a distance to P05)
•P07=2.0
(setpoint stage 4 in a distance to P06)
•P10=0.5 (neutral zone / hysteresis)
•P20=25 (forward delay in sec.)
•P21=25 (backrun delay in sec.)
•P23=0 (no emergency mode)
•P35=6.0 (2nd control setpoint 1)
•P36=20 (2nd setpoint ON 'hours')
•P37=30 (2nd setpoint ON 'minutes')
•P38=06 (2nd setpoint OFF 'hours')
•P39=00 (2nd setpoint OFF 'minutes')
•P45=--(clock time 'hours')
•P46=--(clock time 'minutes')
•P47=--(clock time 'seconds')
Display correction
The 2 actual temperature displays can be
calibrated by P29 ( P01, inlet temperature) and
P30 (P02, outlet temperature).