manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. elsner elektronik
  6. •
  7. Measuring Instrument
  8. •
  9. elsner elektronik KNX PY User manual

elsner elektronik KNX PY User manual

Pyranometer KNX PY 1
Pyranometer KNX PY • Version: 31.01.2023 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
EN
KNX PY
Pyranometer
Technical specifications and installation instructions
Item number 70157
1. Description
The Pyranometer KNX PY measures global irradiance, which is perceived as heat.
The measured current irradiance (watts per squaremetre) allows for drawing con-
clusions on the energy input to an area during a defined period of time (kilowatt
hours per squaremetre). Both values can be read out by the KNX PY. Four swit-
ching outputs with adjustable threshold values as well as additional AND and OR lo-
gic gates are available.The sensor system, the evaluation electronics and the elec-
tronics of the bus connection are mounted in a compact housing.
Functions:
•Measurement of global irradiance: The current irradiance is measured
(W/m²). The energy input to an area during a defined period of time can be
read out (kWh/m²)
•4 threshold values can be adjusted per parameter or via communication
objects
•2 AND and 2 OR logic gates with each 4 inputs. Every switching incident
as well as 8 logic inputs (in the form of communication objects) may be used
as inputs for the logic gates. The output of each gate may optionally be
configured as 1 bit or 2 x 8 bits
Configuration is made using the KNX software ETS. The product file can be dow-
nloaded from the Elsner Elektronik website on www.elsner-elektronik.de in the
“Service” menu.
1.1. Scope of delivery
• Pyranometer with combined wall/pole mounting
• 2x stainless steel installation band for pole installation
1.2. Technical specifications
The product conforms with the provisions of EU directives.
2. Installation and commissioning
Installation, testing, operational start-up and troubleshooting should
only be performed by an authorised electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
• Inspect the device for damage before installation. Only put undamaged
devices into operation.
• Comply with the locally applicable directives, regulations and provisions for
electrical installation.
• Immediately take the device or system out of service and secure it against
unintentional switch-on if risk-free operation is no longer guaranteed.
Use the device exclusively for building automation and observe the operating inst-
ructions. Improper use, modifications to the device or failure to observe the opera-
ting instructions will invalidate any warranty or guarantee claims.
Operate the device only as a fixed-site installation, i.e. only in assembled condition
and after conclusion of all installation and operational start-up tasks, and only in the
surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may
occur after publication of these operating instructions.
2.1. Location
Select an assembly location at the building where sun may be collected by the sen-
sors unobstructedly. The sensor may not be shaded by the building or for example
by trees.
At least 60 cm of clearance must be left all round the device. Concurrently, the pre-
vents spray (raindrops hitting the device) or snow (snow penetration) from impai-
ring the measurement. It also does not allow birds to bite it.
2.2. Mounting the sensor
2.2.1. Attaching the mount
The sensor comes with a combination wall/pole mount. The mount comes adhered
by adhesive strips to the rear side of the housing. Fasten the mount vertically onto
the wall or pole.
Housing Plastic material
Colour White / Transparent
Mounting On-wall
Degree of protection IP 44
Dimensions approx. 96 × 77 × 118 (W × H × D, mm)
Weight approx. 145 g
Ambient temperature Operation -25…+85°C, storage -30…+85°C
Voltage KNX bus voltage
Bus current max. 7 mA,
max. 10 mA when programming LED is active
Data output KNX +/- bus terminal plug
Group addresses max. 200
Allocations max. 200
Communication
objects
52
Measurement range 0…2500 W/m²
0…2196 kWh/m²
Fig. 1
There must be at least 60 cm of space
below, to the sides and in front of the
sensor left from other elements (struc-
tures, construction parts, etc.).
60 cm
Fig. 2
The sensor must be mounted onto a
vertical wall (or pole).
Wall
or
pole
Fig. 3
The sensor must be mounted horizon-
tally in the lateral direction.
horizontal
Fig. 4
For installation in the northern hemis-
phere, the sensor must be aligned to
face south.
For installation in the southern hemis-
phere, the sensor must be aligned to
face north.
Nord
Süd
Fig. 5
After installation, remove the "distan-
ce" sticker on the top of the cover.
Fig. 6
When wall mounting: flat side on wall,
crescent-shaped collar upward.
Collar
Fig. 7
When pole mounting: curved side on po-
le, collar downward.
Collar
Pyranometer KNX PY 2
Pyranometer KNX PY • Version: 31.01.2023 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
2.2.2. View of rear side and drill hole plan
2.2.3. Preparing the sensor
The sensor cover snaps in on the left and right along the bottom edge (see Fig.).
Remove the cover.
Push the connection cable through the rubber seal on the bottom of the device and
connect voltage and data cable to the provided clamps.
2.2.4. PCB layout
2.2.5. Mounting the sensor
Close the housing by putting the cover back over the bottom part. The cover must
snap in on the left and right with a definite “click”.
To remove it, the sensor can be simply pulled upwards out of the mount, against the
resistance of the fastening.
2.3. Notes on mounting and commissioning
Do not open the device if water (rain) might ingress: even some drops might dama-
ge the electronic system.
After the bus voltage has been applied, the device will enter an initialisation phase
lasting a few seconds. During this phase no information can be received or sent via
the bus.
3. Addressing of the device at the bus
The device is supplied with the bus address 15.15.250. You can program another ad-
dress into the ETS by overwriting the 15.15.250 address or by teaching via the pro-
gramming key on the circuit board inside the housing.
4. Maintenance
WARNING!
Risk of injury caused by components moved automatically!
The automatic control can start system components and place people in
danger.
• Always isolate the device from the mains for servicing and cleaning.
The device must regularly be checked for dirt twice a year and cleaned if necessary.
In case of severe dirt, the sensor may not work properly anymore.
ATTENTION
The device can be damaged if water penetrates the housing.
• Do not clean with high pressure cleaners or steam jets.
5. Disposal
After use, the device must be disposed of in accordance with the legal regulations.
Do not dispose of it with the household waste!
Fig. 8
Different mounting arms are available
from Elsner Elektronik as additional, op-
tional accessories for flexible installation
of the weather station on a wall, pole or
beam (pictures of sensors exemplary).
Example of the use of a mounting arm:
Due to flexible ball joints, the sensor can
be brought into ideal position.
Fig. 9
Example use of the hinge arm mounting:
With the hinge arm mounting, the weat-
her station projects from beneath the
roof overhang. Sun, wind and precipita-
tion can act upon the sensors without
hindrance.
Fig. 10
Example use of the hinge arm mounting:
Fitting to a pole with worm drive hose
clips
Langloch 7,5 x 5 mm
Fig. 11 a+b
Drill hole plan
Dimensions of rear side of housing with bra-
cket. Subject to change for technical enhan-
cement.
Fig. 12
1 Cover snaps
2 Bottom part of housing
1
2
Unsnap cover
and remove upwards
Fig. 13
1 KNX clamp +/-
2 Programming LED
3 Programming pushbutton
for the teach-in of the de-
vice
1
2
3
Fig. 14
Make sure the cover and bottom part
are properly snapped together! This
picture is looking at the closed sensor
from underneath.
Fastening
Fig. 15
Push the housing from above into the
fastened mount. The bumps on the
mount must snap into the rails in the
housing.

Other manuals for KNX PY

1

This manual suits for next models

1

Other elsner elektronik Measuring Instrument manuals

elsner elektronik KNX RW Series User manual

elsner elektronik

elsner elektronik KNX RW Series User manual

elsner elektronik KNX TH-UP basic Guide

elsner elektronik

elsner elektronik KNX TH-UP basic Guide

elsner elektronik KNX LW sl 70164 Guide

elsner elektronik

elsner elektronik KNX LW sl 70164 Guide

elsner elektronik KNX I4-ERD Guide

elsner elektronik

elsner elektronik KNX I4-ERD Guide

elsner elektronik TH PF Series User manual

elsner elektronik

elsner elektronik TH PF Series User manual

elsner elektronik KNX eTR M1 User manual

elsner elektronik

elsner elektronik KNX eTR M1 User manual

elsner elektronik KNX TH-UP basic Guide

elsner elektronik

elsner elektronik KNX TH-UP basic Guide

elsner elektronik KNX SO250 Guide

elsner elektronik

elsner elektronik KNX SO250 Guide

elsner elektronik KNX PY User manual

elsner elektronik

elsner elektronik KNX PY User manual

Popular Measuring Instrument manuals by other brands

LOVATO ELECTRIC DMED320 instruction manual

LOVATO ELECTRIC

LOVATO ELECTRIC DMED320 instruction manual

AG ZR-HM3-50-RC Installation and instruction manual

AG

AG ZR-HM3-50-RC Installation and instruction manual

MONARCH INSTRUMENT ACT-3X User manual and reference guide

MONARCH INSTRUMENT

MONARCH INSTRUMENT ACT-3X User manual and reference guide

Quicklynks BA1000 user manual

Quicklynks

Quicklynks BA1000 user manual

Motion Pro 08-0684 instructions

Motion Pro

Motion Pro 08-0684 instructions

Ripley ODM VIS 500 quick start guide

Ripley

Ripley ODM VIS 500 quick start guide

FLIR E75 user manual

FLIR

FLIR E75 user manual

Kane KANE251 manual

Kane

Kane KANE251 manual

Geotech EcoSense pH100A user manual

Geotech

Geotech EcoSense pH100A user manual

Bosch GMS 120 Professional Original instructions

Bosch

Bosch GMS 120 Professional Original instructions

Ankom A2000 Service Procedure

Ankom

Ankom A2000 Service Procedure

Niigata seiki WCDI-10D instruction manual

Niigata seiki

Niigata seiki WCDI-10D instruction manual

Sensor Electronics AirDistSys 5000 Operator's manual

Sensor Electronics

Sensor Electronics AirDistSys 5000 Operator's manual

KROHNE WATERFLUX 3000 Handbook

KROHNE

KROHNE WATERFLUX 3000 Handbook

Measurlogic DTS 307 install guide

Measurlogic

Measurlogic DTS 307 install guide

Keithley 6517B user manual

Keithley

Keithley 6517B user manual

Audison APM owner's manual

Audison

Audison APM owner's manual

Samoa 415000 Technical service guide

Samoa

Samoa 415000 Technical service guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.