manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Emerson
  6. •
  7. Controllers
  8. •
  9. Emerson Dixell XR10CX Wiring diagram

Emerson Dixell XR10CX Wiring diagram

1592020010 XR10CX GB m&M r1.1 27.03.2015 XR10CX 1/4
Digital controller with cooling or heating action
XR10CX
CONTENTS
1. GENERAL WARNING ___________________________________________________ 1
2. GENERAL DESCRIPTION _______________________________________________1
3. CONTROLLING LOADS _________________________________________________1
4. FRONT PANEL COMMANDS _____________________________________________ 1
5. MAX & MIN TEMPERATURE MEMORIZATION_______________________________ 1
6. MAIN FUNCTIONS _____________________________________________________2
7. PARAMETERS ________________________________________________________2
8. DIGITAL INPUT (ENABLED WITH P3P = N) _________________________________3
9. TTL SERIAL LINE –FOR MONITORING SYSTEMS ___________________________ 3
10. X-REP OUTPUT –OPTIONAL ____________________________________________ 3
11. INSTALLATION AND MOUNTING _________________________________________3
12. ELECTRICAL CONNECTIONS ____________________________________________ 3
13. HOW TO USE THE HOT KEY_____________________________________________3
14. ALARM SIGNALS ______________________________________________________3
15. TECHNICAL DATA _____________________________________________________3
16. CONNECTIONS _______________________________________________________ 4
17. DEFAULT SETTING VALUES_____________________________________________4
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and
quick reference.
The instrument shall not be used for purposes different from those described hereunder.
It cannot be used as a safety device.
Check the application limits before proceeding.
Dixell Srl reserves the right to change the composition of its products, even without
notice, ensuring the same and unchanged functionality.
1.2 SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits
avoiding sudden temperature changes with high atmospheric humidity to prevent
formation of condensation
Warning: disconnect all electrical connections before any kind of maintenance.
Fit the probe where it is not accessible by the End User. The instrument must not be
opened.
In case of failure or faulty operation send the instrument back to the distributor or to
“Dixell S.r.l.” (see address) with a detailed description of the fault.
Consider the maximum current which can be applied to each relay (see Technical Data).
Ensure that the wires for probes, loads and the power supply are separated and far
enough from each other, without crossing or intertwining.
In case of applications in industrial environments, the use of mains filters (our mod. FT1)
in parallel with inductive loads could be useful.
2. GENERAL DESCRIPTION
Model XR10C, format 32 x 74 mm format is a single stage temperature controller suitable for
applications in the field of refrigeration or heating. It provides a relay output to drive the
compressor. It is also provided with 2 NTC or PTC probe inputs, the first one for temperature
control, the second one, optional, to connect to the HOT KEY terminals to signal the
condenser temperature alarm or to display a temperature. The digital input can operate as
third temperature probe.
The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX,
to a network line ModBUS-RTU compatible such as the Dixell monitoring units of X-WEB
family. It allows to program the controller by means the HOT KEY programming keyboard.
The instrument is fully configurable through special parameters that can be easily
programmed through the keyboard.
3. CONTROLLING LOADS
3.1 THE REGULATION OUTPUT
The regulation is performed according to the temperature measured by the probe.
The instruments are provided with the CH programmable parameter which enables the user to
set the regulation both for heating or cooling applications:
· CH = CL: cooling applications
· CH = Ht: heating applications
3.2 CH = CL: COOLING APPLICATIONS.
The Hy value is automatically set above the Set Point. If the temperature increases and
reaches set point plus differential the compressor is started and then turned off when the
temperature reaches the set point value again.
Time
Temper.
Compr.
SET
ON
3.3 CH = HT: HEATING APPLICATION.
The Hy value is automatically set under the Set Point. If the temperature decreases and
reaches set point minus differential the regulation output is activated and then turned off when
the temperature reaches the set point value again.
Time
Temper.
Heating
ON
SET
SET- HY
Time
4. FRONT PANEL COMMANDS
: To display target set point; in programming mode it selects a parameter or confirm
an operation.
(DEF) Not enabled
(UP): To see the max. stored temperature; in programming mode it browses the
parameter codes or increases the displayed value.
(DOWN) To see the min stored temperature; in programming mode it browses the
parameter codes or decreases the displayed value.
To switch the instrument off, if onF = oFF.
Not enabled
KEY COMBINATIONS:
+  To lock & unlock the keyboard.
+To enter in programming mode.
+To return to the room temperature display.
4.1 USE OF LEDS
Each LED function is described in the following table.
LED
MODE
FUNCTION
ON
Compressor enabled
Flashing
Anti-short cycle delay enabled
ON
An alarm is occurring
ON
Energy saving enabled
°C/°F
ON
Measurement unit
°C/°F
Flashing
Programming phase
5. MAX & MIN TEMPERATURE MEMORIZATION
5.1 HOW TO SEE THE MIN TEMPERATURE
1. Press and release the nkey.
2. The “Lo” message will be displayed followed by the minimum temperature recorded.
3. By pressing the nkey again or by waiting 5s the normal display will be restored.
5.2 HOW TO SEE THE MAX TEMPERATURE
1. Press and release the okey.
2. The “Hi” message will be displayed followed by the maximum temperature recorded.
3. By pressing the okey again or by waiting 5s the normal display will be restored.
5.3 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED
1. Hold press the SET key for more than 3s, while the max. or min temperature is
displayed. (rSt message will be displayed)
2. To confirm the operation the “rSt” message starts blinking and the normal temperature
will be displayed.
1592020010 XR10CX GB m&M r1.1 27.03.2015 XR10CX 2/4
6. MAIN FUNCTIONS
6.1 HOW TO SEE THE SETPOINT
1. Push and immediately release the SET key: the display will show
the Set point value;
2. Push and immediately release the SET key or wait for 5 seconds to
display the probe value again.
6.2 HOW TO CHANGE THE SETPOINT
1. Push the SET key for more than 2 seconds to change the Set point value;
2. The value of the set point will be displayed and the “°C” or “°F” LED starts blinking;
3. To change the Set value push the o or narrows within 10s.
4. To memorise the new set point value push the SET key again or wait 10s.
6.3 HOW TO CHANGE A PARAMETER VALUE
To change the parameter’s value operate as follows:
1. Enter the Programming mode by pressing the Set + nkeys for 3s (the “°C” or “°F” LED
starts blinking).
2. Select the required parameter. Press the “SET” key to display its value
3. Use “UP” or “DOWN” to change its value.
4. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 15s without pressing a key.
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to
expire.
6.4 THE HIDDEN MENU
The hidden menu Includes all the parameters of the instrument.
6.4.1 HOW TO ENTER THE HIDDEN MENU
1. Enter the Programming mode by pressing the Set + nkeys for 3s (the “°C” or “°F” LED
starts blinking).
2. Released the keys, then push again the Set+nkeys for more than 7s. The Pr2 label will
be displayed immediately followed from the HY parameter.
NOW YOU ARE IN THE HIDDEN MENU.
3. Select the required parameter.
4. Press the “SET” key to display its value
5. Use o or nto change its value.
6. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET + o or wait 15s without pressing a key.
NOTE1: if none parameter is present in Pr1, after 3s the “noP” message is displayed. Keep
the keys pushed till the Pr2 message is displayed.
NOTE2: the set value is stored even when the procedure is exited by waiting the time-out to
expire.
6.4.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO
THE FIRST LEVEL AND VICEVERSA.
Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST
LEVEL” (user level) by pressing “SET + n”.
In HIDDEN MENU when a parameter is present in First Level the decimal point is on.
6.5 HOW TO LOCK THE KEYBOARD
1. Keep pressed for more than 3 s the UP + DOWN keys.
2. The “POF” message will be displayed and the keyboard will be locked. At this point it will
be possible only to see the set point or the MAX o Min temperature stored
3. If a key is pressed more than 3s the “POF” message will be displayed.
6.6 TO UNLOCK THE KEYBOARD
Keep pressed together for more than 3s the o and nkeys, till the “Pon” message will be
displayed.
6.7 THE ON/OFF FUNCTION
With “onF = oFF”, pushing the ON/OFF key, the instrument is switched off. The
“OFF” message is displayed. In this configuration, the regulation is disabled.
To switch the instrument on, push again the ON/OFF key.
WARNING: Loads connected to the normally closed contacts of the relays are always
supplied and under voltage, even if the instrument is in stand by mode.
7. PARAMETERS
REGULATION
Hy Differential: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point. Compressor
Cut IN is Set Point + differential (Hy). Compressor Cut OUT is when the temperature
reaches the set point.
LS Minimum set point: (- 50°C÷SET/-58°F÷SET): Sets the minimum value for the set point.
US Maximum set point: (SET÷110°C/ SET÷230°F). Set the maximum value for set point.
Ot Thermostat probe calibration: (-12.0÷12.0°C; -120÷120°F) allows to adjust possible
offset of the thermostat probe.
P3P Third probe presence (P3): n= not present:, the terminal operates as digital input.; y=
present:, the terminal operates as third probe.
O3 Third probe calibration (P3): (-12.0÷12.0°C; -120÷120°F). allows to adjust possible
offset of the third probe.
P4P Fourth probe presence: (n = Not present; y = present).
o4 Fourth probe calibration: (-12.012.0°C) allows to adjust possible offset of the fourth
probe.
OdS Outputs activation delay at start up: (0÷255min) This function is enabled at the initial
start up of the instrument and inhibits any output activation for the period of time set in
the parameter.
AC Anti-short cycle delay: (0÷50 min) minimum interval between the compressor stop and
the following restart.
COn Compressor ON time with faulty probe: (0÷255 min) time during which the
compressor is active in case of faulty thermostat probe. With COn=0 compressor is always
OFF.
COF Compressor OFF time with faulty probe: (0÷255 min) time during which the
compressor is OFF in case of faulty thermostat probe. With COF=0 compressor is always
active.
CH Type of action: CL = cooling; Ht = heating.
DISPLAY
CF Temperature measurement unit: °C=Celsius; °F=Fahrenheit. WARNING: When the
measurement unit is changed the SET point and the values of the parameters Hy, LS,
US, Ot, ALU and ALL have to be checked and modified if necessary).
rES Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display.
dLy Display delay: (0 ÷20.0m; risul. 10s) when the temperature increases, the display is
updated of 1 °C/1°F after this time.
ALARMS
ALC Temperature alarms configuration: (Ab; rE)
Ab= absolute temperature: alarm temperature is given by the ALL or ALU values. rE =
temperature alarms are referred to the set point. Temperature alarm is enabled when the
temperature exceeds the “SET+ALU” or “SET-ALL” values.
ALU MAXIMUM temperature alarm: (SET÷110°C; SET÷230°F) when this temperature is
reached the alarm is enabled, after the “ALd” delay time.
ALL Minimum temperature alarm: (-50.0 ÷ SET°C; -58÷230°F when this temperature is
reached the alarm is enabled, after the “ALd” delay time.
AFH Differential for temperature alarm recovery: (0,1÷25,5°C; 1÷45°F) Intervention
differential for recovery of temperature alarm.
ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm
condition and alarm signalling.
dAO Exclusion of temperature alarm at startup: (from 0.0 min to 23.5h) time interval
between the detection of the temperature alarm condition after instrument power on and
alarm signalling.
CONDENSER TEMPERATURE ALARM (detected by the fourth probe)
AP2 Probe selection for temperature alarm of condenser: nP = no probe; P1 =thermostat
probe; P2 = evaporator probe; P3 =configurable probe; P4 = Probe on Hot Key plug.
AL2 Low temperature alarm of condenser:(-55÷150°C) when this temperature is reached
the LA2 alarm is signalled, possibly after the Ad2 delay.
Au2 High temperature alarm of condenser:(-55÷150°C) when this temperature is reached
the HA2 alarm is signalled, possibly after the Ad2 delay.
AH2 Differential for temperature condenser alarm recovery:(0,1÷25,5°C; 1÷45°F)
Ad2 Condenser temperature alarm delay: (0÷255 min) time interval between the detection
of the condenser alarm condition and alarm signalling.
dA2 Condenser temperature alarm exclusion at start up: (from 0.0 min to 23.5h, res.
10min)
bLL Compressor off with low temperature alarm of condenser:n = no: compressor
keeps on working; Y = yes, compressor is switched off till the alarm is present, in any
case regulation restarts after AC time at minimum.
AC2 Compressor off with high temperature alarm of condenser:n = no: compressor
keeps on working; Y = yes, compressor is switched off till the alarm is present, in any
case regulation restarts after AC time at minimum.
DIGITAL INPUT
i1P Digital input polarity: oP: the digital input is activated by opening the contact; CL: the
digital input is activated by closing the contact.
i1F Digital input configuration: EAL = external alarm: “EA” message is displayed; bAL =
serious alarm “CA” message is displayed. PAL = pressure switch alarm, “CA” message
is displayed; dor = door switch function; dEF = not enabled; AUS = not enabled; Htr =
kind of action inversion (cooling –heating); FAn = do not set it; ES = Energy saving.
did:(0255 min) with i1F= EAL or i1F = bAL digital input alarm delay: delay between the
detection of the external alarm condition and its signalling.
with i1F= dor: door open signalling delay
with i1F = PAL: time for pressure switch function: time interval to calculate the
number of the pressure switch activation.
nPS Pressure switch number: (0

15) Number of activation of the pressure switch, during
the “did” interval, before signalling the alarm event (I2F= PAL).
If the nPS activation in the did time is reached, switch off and on the instrument to
restart normal regulation.
odc Compressor status when open door: no;Fan = normal; CPr; F_C = Compressor
OFF.
rrd Outputs restart after doA alarm: no = outputs not affected by the doA alarm; yES =
outputs restart with the doA alarm;
HES Temperature increase during the Energy Saving cycle : (-30,0°C

30,0°C/-22÷86°F)
it sets the increasing value of the set point during the Energy Saving cycle.
OTHER
Adr Serial address (1÷244): Identifies the instrument address when connected to a
ModBUS compatible monitoring system.
PbC Type of probe: it allows to set the kind of probe used by the instrument: PbC = PBC
probe, ntc = NTC probe.
onF on/off key enabling: nu = disabled; oFF = enabled; ES = not set it.
dP1 Thermostat probe display
dP3 Third probe display- optional.
dP4 Fourth probe display.
1592020010 XR10CX GB m&M r1.1 27.03.2015 XR10CX 3/4
rSE Real set point: (readable only), it shows the set point used during the energy saving
cycle or during the continuous cycle.
rEL Software release for internal use.
Ptb Parameter table code: readable only.
8. DIGITAL INPUT (ENABLED WITH P3P = N)
The free voltage digital input is programmable in different configurations by the “i1F”
parameter.
8.1 DOOR SWITCH INPUT (i1F = dor)
It signals the door status and the corresponding relay output status through the “odc”
parameter: no,Fan = normal (any change); CPr, F_C = Compressor OFF.
Since the door is opened, after the delay time set through parameter “did”, the door alarm is
enabled, the display shows the message “dA” and the regulation restarts is rtr = yES. The
alarm stops as soon as the external digital input is disabled again. With the door open, the
high and low temperature alarms are disabled.
8.2 GENERIC ALARM (i1F = EAL)
As soon as the digital input is activated the unit will wait for “did” time delay before signalling
the “EAL” alarm message. The outputs status don’t change. The alarm stops just after the
digital input is de-activated.
8.3 SERIOUS ALARM MODE (i1F = bAL)
When the digital input is activated, the unit will wait for “did” delay before signalling the “CA”
alarm message. The relay outputs are switched OFF. The alarm will stop as soon as the
digital input is de-activated.
8.4 PRESSURE SWITCH (i1F = PAL)
If during the interval time set by “did” parameter, the pressure switch has reached the number
of activation of the “nPS” parameter, the “CA” pressure alarm message will be displayed. The
compressor and the regulation are stopped. When the digital input is ON the compressor is
always OFF.
If the nPS activation in the did time is reached, switch off and on the instrument to
restart normal regulation.
8.5 INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i1F = Htr)
This function allows to invert the regulation of the controller: from cooling to heating and
viceversa.
8.6 ENERGY SAVING (i1F = ES)
The Energy Saving function allows to change the set point value as the result of the SET+
HES (parameter) sum. This function is enabled until the digital input is activated.
8.7 DIGITAL INPUTS POLARITY
The digital input polarity depends on the “i1P” parameter.
i1P=CL: the input is activated by closing the contact.
i1P=OP: the input is activated by opening the contact
9. TTL SERIAL LINE –FOR MONITORING SYSTEMS
The TTL serial line, available through the HOT KEY connector, allows by means of the
external TTL/RS485 converter, XJ485-CX, to connect the instrument to a monitoring system
ModBUS-RTU compatible such as the X-WEB500/3000/300.
10. X-REP OUTPUT –OPTIONAL
As optional, an X-REP can be connected to the instrument, trough the HOY
KEY connector. The X-REP output EXCLUDES the serial connection.
To connect the X-REP to the
instrument the following
connectors must be used CAB-
51F(1m), CAB-52F(2m), CAB-
55F(5m),
11. INSTALLATION AND MOUNTING
Instrument XR10CX shall be mounted on vertical panel, in a
29x71 mm hole, and fixed using the special bracket supplied.
The temperature range allowed for correct operation is 060
°C. Avoid places subject to strong vibrations, corrosive
gases, excessive dirt or humidity. The same
recommendations apply to probes. Let air circulate by the
cooling holes.
12. ELECTRICAL CONNECTIONS
The instrument is provided with screw terminal block to connect cables with a cross section up
to 2,5 mm2. Before connecting cables make sure the power supply complies with the
instrument’s requirements. Separate the probe cables from the power supply cables, from the
outputs and the power connections. Do not exceed the maximum current allowed on each
relay, in case of heavier loads use a suitable external relay.
12.1 PROBE CONNECTION
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid
infiltration. It is recommended to place the thermostat probe away from air streams to correctly
measure the average room temperature. Place the defrost termination probe among the
evaporator fins in the coldest place, where most ice is formed, far from heaters or from the
warmest place during defrost, to prevent premature defrost termination.
13. HOW TO USE THE HOT KEY
13.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1. Program one controller with the front keypad.
2. When the controller is ON, insert the “Hot key” and push okey; the "uPL" message
appears followed a by flashing “End”
3. Push “SET” key and the End will stop flashing.
4. Turn OFF the instrument remove the “Hot Key”, then turn it ON again.
NOTE: the “Err” message is displayed for failed programming. In this case push again okey
if you want to restart the upload again or remove the “Hot key” to abort the operation.
13.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY
(DOWNLOAD)
1. Turn OFF the instrument.
2. Insert a programmed “Hot Key” into the 5 PIN receptacle and then turn the
Controller ON.
3. Automatically the parameter list of the “Hot Key” is downloaded into the Controller
memory, the “doL” message is blinking followed a by flashing “End”.
4. After 10 seconds the instrument will restart working with the new parameters.
5. Remove the “Hot Key”..
NOTE the message “Err” is displayed for failed programming. In this case turn the unit off and
then on if you want to restart the download again or remove the “Hot key” to abort the
operation.
14. ALARM SIGNALS
Message
Cause
Outputs
“P1”
Room probe failure
Compressor output acc. to par. “Con” and
“COF”
“P3”
Third probe failure
Outputs unchanged
“P4”
Fourth probe failure
Outputs unchanged
“HA”
Maximum temperature alarm
Outputs unchanged.
“LA”
Minimum temperature alarm
Outputs unchanged.
"HA2"
Condenser high temperature
It depends on the “Ac2” parameter
"LA2"
Condenser low temperature
It depends on the “bLL” parameter
“dA”
Door open
Compressor according to rrd
“EA”
External alarm
Output unchanged.
“CA”
Serious external alarm
(i1F=bAL)
All outputs OFF.
“CA”
Pressure switch alarm
(i1F=PAL)
All outputs OFF
14.1 ALARM RECOVERY
Probe alarms P1”, “P3” and “P4” start some seconds after the fault in the related probe; they
automatically stop some seconds after the probe restarts normal operation. Check
connections before replacing the probe.
Temperature alarms “HA”, “LA” “HA2” and “LA2” automatically stop as soon as the
temperature returns to normal values.
Alarms “EA” and “CA” (with i1F=bAL) recover as soon as the digital input is disabled.
Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument.
14.2 OTHER MESSAGES
Pon
Keyboard unlocked.
PoF
Keyboard locked
noP
In programming mode: none parameter is present in Pr1
On the display or in dP2, dP3, dP4: the selected probe is nor enabled
noA
None alarm is recorded.
15. TECHNICAL DATA
Housing: self extinguishing ABS.
Case: XR10CX frontal 32x74 mm; depth 60mm;
Mounting: XR10CX panel mounting in a 71x29mm panel cut-out
Protection: IP20; Frontal protection: XR10CX IP65
Connections: Screw terminal block 2,5 mm2wiring.
Power supply: according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%; 230Vac 10%,
50/60Hz, 110Vac 10%, 50/60Hz
Power absorption: 3VA max
Display: 3 digits, red LED, 14,2 mm high; Inputs: Up to 3 NTC or PTC probes.
Digital input: free voltage contact
Relay outputs: compressor SPST 8(3) A, 250Vac; or 20(8)A 250Vac
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B; Pollution grade: 2;Software class: A.;
Rated impulsive voltage: 2500V; Overvoltage Category: II
Operating temperature: 0÷60 °C;Storage temperature: -30÷85 °C.
Relative humidity: 2085% (no condensing)
Measuring and regulation range: NTC probe: -40÷110°C (-40÷230°F);
PTC probe: -50÷150°C (-58÷302°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable); Accuracy (ambient temp. 25°C): ±1 °C ±1
digit
1592020010 XR10CX GB m&M r1.1 27.03.2015 XR10CX 4/4
16. CONNECTIONS
The X-REP output excludes the TTL output.. It’s present in the following codes:
XR10CX- xx2xx, XR10CX –xx3xx;
16.1 XR10CX –8A COMPRESSOR
N.C.
1 2 3 67
910 11 12
Comp
Room
8
Hot Key/IV Probe
TTL or X-REP output
8(3)A250V
Line
9-40Vdc supply: connect to the terminals 7 and 8.
12Vac/dc supply: connect to the terminals 7 and 8.
24Vac/dc supply: connect to the terminals 7 and 8.
120Vac supply: connect to the terminals 7 and 8.
16.2 XR10CX –20A COMPRESSOR
4 5 67
910 11 12
Comp
Room
8
Hot Key/IV Probe
TTL or X-REP output
20(8)A250V
Line
9-40Vdc supply: connect to the terminals 7 and 8.
12Vac/dc supply: connect to the terminals 7 and 8.
24Vac/dc supply: connect to the terminals 7 and 8.
120Vac supply: connect to the terminals 7 and 8.
17. DEFAULT SETTING VALUES
Label
Name
Range
°C/°F
Set
Set point
LS÷US
5.0
- - -
Hy
Differential
0,125.5°C/ 1255°F
2.0
Pr1
LS
Minimum set point
-50°CSET/-58°FSET
-50.0
Pr2
US
Maximum set point
SET110°C/ SET 230°F
110
Pr2
Ot
Thermostat probe calibration
-1212°C /-120120°F
0.0
Pr1
P3P
Third probe presence
n=not present; Y=pres.
n
Pr2
O3
Third probe calibration
-1212°C /-120120°F
0
Pr2
P4P
Fourth probe presence
n=not present; Y=pres.
n
Pr2
O4
Fourth probe calibration
-1212°C /-120120°F
0
Pr2
OdS
Outputs delay at start up
0÷255 min
0
Pr2
AC
Anti-short cycle delay
0 50 min
1
Pr1
COn
Compressor ON time with faulty probe
0 255 min
15
Pr2
COF
Compressor OFF time with faulty
probe
0 255 min
30
Pr2
CH
Kind of action
CL=cooling; Ht= heating
cL
Pr1
CF
Temperature measurement unit
°C °F
°C
Pr2
rES
Resolution
in=integer; dE= dec.point
dE
Pr1
dLy
Display temperature delay
0 ÷ 20.0 min (10 sec.)
0
Pr2
ALc
Temperat. alarms configuration
rE= related to set;
Ab = absolute
Ab
Pr2
ALU
MAXIMUM temperature alarm
Set110.0°C; Set÷230°F
110
Pr1
ALL
Minimum temperature alarm
-50.0°CSet/ -58°FSet
-50.0
Pr1
AFH
Differential for temperat. alarm
recovery
(0,1°C÷25,5°C) (1°F÷45°F)
1
Pr2
ALd
Temperature alarm delay
0 255 min
15
Pr2
dAo
Delay of temperature alarm at start up
0 23h e 50’
1.0
Pr2
AP2
Probe for temperat. alarm of
condenser
nP; P1; P2; P3; P4
P4
Pr2
AL2
Condenser for low temperat. alarm
(-55 ÷ 150°C) (-67÷ 302°F)
-40
Pr2
AU2
Condenser for high temperat. alarm
(-55 ÷ 150°C) (-67÷ 302°F)
110
Pr2
AH2
Differ. for condenser temp. alar.
recovery
[0,1°C ÷ 25,5°C] [1°F ÷
45°F]
5
Pr2
Ad2
Condenser temperature alarm delay
0 ÷ 254 (min.) , 255=nU
15
Pr2
dA2
Delay of cond. temper. alarm at start
up
0.0 ÷ 23h 50’
1,0
Pr2
bLL
Compr. off for condenser low
temperature alarm
n(0) - Y(1)
n
Pr2
AC2
Compr. off for condenser high
temperature alarm
n(0) - Y(1)
n
Pr2
i1P
Digital input polarity
oP=opening;CL=closing
cL
Pr1
i1F
Digital input configuration
EAL, bAL, PAL, dor; dEF; Htr,
AUS
EAL
Pr1
did
Digital input alarm delay
0÷255min
5
Pr1
nPS
Number of activation of pressure
switch
0 ÷15
15
Pr2
odc
Compress status when open door
no; Fan; CPr; F_C
no
Pr2
rrd
Regulation restart with door open
alarm
n –Y
y
Pr2
HES
Differential for Energy Saving
(-30°C÷30°C) (-54°F÷54°F)
0
Pr2
Adr
Serial address
0÷247
1
Pr2
PbC
Kind of probe
Ptc; ntc
ntc
Pr1
onF
on/off key enabling
nu, oFF; ES
nu
Pr2
dP1
Room probe display
--
--
Pr1
dP3
Third probe display
--
--
Pr1
dP4
Fourth probe display
--
--
Pr2
rSE
Real set point value
actual set
--
Pr2
rEL
Software release
--
--
Pr2
Ptb
Map code
--
--
Pr2

Other Emerson Controllers manuals

Emerson MR105 User manual

Emerson

Emerson MR105 User manual

Emerson Control Link User manual

Emerson

Emerson Control Link User manual

Emerson Fisher 4194HA User manual

Emerson

Emerson Fisher 4194HA User manual

Emerson Fincor 2330MKII Series Technical Document

Emerson

Emerson Fincor 2330MKII Series Technical Document

Emerson KEYSTONE FIGURE 738 Manual

Emerson

Emerson KEYSTONE FIGURE 738 Manual

Emerson Bettis XTE3000 User manual

Emerson

Emerson Bettis XTE3000 User manual

Emerson Dixell XC15CX Wiring diagram

Emerson

Emerson Dixell XC15CX Wiring diagram

Emerson Hytork XL Series Installation and operating manual

Emerson

Emerson Hytork XL Series Installation and operating manual

Emerson FRANSEL REGAL 3 User manual

Emerson

Emerson FRANSEL REGAL 3 User manual

Emerson 350 series User manual

Emerson

Emerson 350 series User manual

Emerson DIXELL XR77CHC User manual

Emerson

Emerson DIXELL XR77CHC User manual

Emerson Fisher 630 Series User manual

Emerson

Emerson Fisher 630 Series User manual

Emerson Dixell XWi70K Wiring diagram

Emerson

Emerson Dixell XWi70K Wiring diagram

Emerson Topworx D Series User manual

Emerson

Emerson Topworx D Series User manual

Emerson PNC001-A Series User manual

Emerson

Emerson PNC001-A Series User manual

Emerson FISHER 627F User manual

Emerson

Emerson FISHER 627F User manual

Emerson Tescom 44-2300 Series User manual

Emerson

Emerson Tescom 44-2300 Series User manual

Emerson EC2-742 User manual

Emerson

Emerson EC2-742 User manual

Emerson ROC809 User manual

Emerson

Emerson ROC809 User manual

Emerson Dixell iPro Master IPM500D Wiring diagram

Emerson

Emerson Dixell iPro Master IPM500D Wiring diagram

Emerson Powerdrive F300 User manual

Emerson

Emerson Powerdrive F300 User manual

Emerson EC1-233 User manual

Emerson

Emerson EC1-233 User manual

Emerson Dixell XR60C Wiring diagram

Emerson

Emerson Dixell XR60C Wiring diagram

Emerson E2 User manual

Emerson

Emerson E2 User manual

Popular Controllers manuals by other brands

ISVT IMC1300 instruction manual

ISVT

ISVT IMC1300 instruction manual

Agilent Technologies TV70 Navigator Series user manual

Agilent Technologies

Agilent Technologies TV70 Navigator Series user manual

Honeywell CIPer 50 Installation & commissioning instructions

Honeywell

Honeywell CIPer 50 Installation & commissioning instructions

Linak TR-EM-273 quick guide

Linak

Linak TR-EM-273 quick guide

Emotron MSF 2.0 instruction manual

Emotron

Emotron MSF 2.0 instruction manual

HEIDENHAIN ND 280 - 8-2010 operating instructions

HEIDENHAIN

HEIDENHAIN ND 280 - 8-2010 operating instructions

Horizont turbomax AN800 instruction manual

Horizont

Horizont turbomax AN800 instruction manual

MYPV AC-THOR Operation manual

MYPV

MYPV AC-THOR Operation manual

ESBE CRC110 series Technical description

ESBE

ESBE CRC110 series Technical description

Bodine FPM Series Instructions for installation and operation

Bodine

Bodine FPM Series Instructions for installation and operation

TQ TQMxE40C1 user manual

TQ

TQ TQMxE40C1 user manual

Danfoss ADAP-KOOL AK-HP 780 Design guide

Danfoss

Danfoss ADAP-KOOL AK-HP 780 Design guide

Russound ACP-1DU instruction manual

Russound

Russound ACP-1DU instruction manual

AUMA MEC 03.1 Operation instructions

AUMA

AUMA MEC 03.1 Operation instructions

SUPMEA SUP-DC2000 user manual

SUPMEA

SUPMEA SUP-DC2000 user manual

Lenze C520 Commissioning

Lenze

Lenze C520 Commissioning

Bernina BSR manual

Bernina

Bernina BSR manual

Linear Technology LTC4260 datasheet

Linear Technology

Linear Technology LTC4260 datasheet

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.