Emerson Fisher Y692 User manual

Type Y692
Installation Guide
D102031X014
November 2016
Introduction
This installation guide provides instructions for installation, startup and
adjustment. To receive a copy of the instruction manual, contact your
local Fisher Sales O󰀩ce or Sales Representative or view a copy at
www.sher.com. For further information, refer to Type Y692 Instruction
Manual, form 5347, D102031X012.
PED Categories
This product may be used as a safety accessory with pressure
equipment in the following Pressure Equipment Directive
97/23/EC categories. It may also be used outside of the Pressure
Equipment Directive using Sound Engineering Practice (SEP)
per table below. For information on the current PED revision,
see Bulletin: D103053X012.
PRODUCT SIZE CATEGORIES FLUID TYPE
DN 40 and 50 / 1-1/2 and 2 in. I 1
Specications
Maximum Inlet and Outlet Pressures(1)
10.4 bar / 150 psig and 1.0 bar / 15 psig
Proof Test Pressure
All Pressure Retaining Components have been proof tested per
Directive 97/23/EC - Annex 1, Section 7.4
Outlet Pressure Ranges(1)
Light Spring Assembly: 2 to 7 bar / 1 to 3 in. w.c., 7 to 26 mbar /
3 to 11 in. w.c., 16 to 86 mbar / 6.5 in. w.c. to 1.2 psig, 0.05 to
0.1 bar / 0.7 to 2 psig and 0.07 to 0.2 bar / 1 to 3.2 psig
Heavy Spring Assembly: 0.1 to 0.4 bar / 2 to 5.5 psig and
0.3 to 0.5 bar / 4 to 7 psig
Maximum Operating Outlet Pressure to Avoid Internal
Part Damage(1)
0.21 bar / 3 psig above outlet pressure setting
Temperature Capabilities(1)
Nitrile (NBR): -29 to 82°C / -20 to 180°F
Fluoroelastomer (FKM): 5 to 149°C / 40 to 300°F
Installation
▲ WARNING
Only qualied personnel should install or service a
regulator. Regulators should be installed, operated
and maintained in accordance with international
and applicable codes and regulations, and
Fisher™ instructions.
If the regulator vents uid or a leak develops in the
system, it indicates that service is required. Failure
to take the regulator out of service immediately may
create a hazardous condition.
Personal injury, equipment damage or leakage due
to escaping uid or bursting of pressure-containing
parts may result if this regulator is overpressured
or is installed where service conditions could
exceed the limits given in the Specications section
or where conditions exceed any ratings of the
adjacent piping or piping connections.
To avoid such injury or damage, provide pressure-
relieving or pressure-limiting devices (as required
by the appropriate code, regulation or standard) to
prevent service conditions from exceeding limits.
Additionally, physical damage to the regulator could
result in personal injury and property damage due
to escaping uid. To avoid such injury and damage,
install the regulator in a safe location.
Clean out all pipelines before installation of the regulator and check to
be sure the regulator has not been damaged or has collected foreign
material during shipping. For NPT bodies, apply pipe compound to
the male pipe threads. For anged bodies, use suitable line gaskets
and approved piping and bolting practices. Install the regulator in any
position desired, unless otherwise specied, but be sure ow through
the body is in the direction indicated by the arrow on the body.
For proper operation, the regulator must be installed with the spring
case barrel pointed down.
Note
It is important that the regulator be installed so that
the vent hole in the spring case is unobstructed at
all times. For outdoor installations, the regulator
should be located away from vehicular tra󰀩c and
positioned so that water, ice, and other foreign
materials cannot enter the spring case through the
vent. Avoid placing the regulator beneath eaves or
downspouts, and be sure it is above the probable
snow level.
Overpressure Protection
The recommended pressure limitations are stamped on the regulator
nameplate. Some type of overpressure protection is needed if the
actual inlet pressure exceeds the maximum operating outlet pressure
rating. Overpressure protection should also be provided if the
regulator inlet pressure is greater than the safe working pressure of
the downstream equipment.
Regulator operation below the maximum pressure limitations does
not preclude the possibility of damage from external sources or debris
in the line. The regulator should be inspected for damage after any
overpressure condition.
Startup
The regulator is factory set at approximately the midpoint of the spring
range or the pressure requested, so an initial adjustment may be
required to give the desired results. With proper installation completed
and relief valves properly adjusted, slowly open the upstream and
downstream shuto󰀨 valves.
Adjustment
To change the outlet pressure, remove the closing cap or loosen the
locknut and turn the adjusting screw clockwise to increase outlet pressure
or counterclockwise to decrease pressure. Monitor the outlet pressure with
a test gauge during the adjustment. Replace the closing cap or tighten the
locknut to maintain the desired setting.
1. The pressure/temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded.
3
4
2
1
4
5
35
23
93
30
5
4
44
35
23
30
1
2
3
47
74
44
23
30
35
21
22
20
13
11
19
17
16
14
28
25
27
46
6
7
1
2
3
4
5
8
9
34B4832-B
34B4869-A
Type Y692
Facebook.com/EmersonAutomationSolutions
LinkedIn.com/company/emerson-automation-solutions
Twitter.com/emr_automation
[email protected]
Emerson Automation Solutions
Fisher.com
D102031X014 © 2001, 2021 Emerson Process Management Regulator
Technologies, Inc. All rights reserved. 10/21.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
All other marks are the property of their prospective owners.
Fisher™ is a mark owned by Fisher Controls International LLC, a business
of Emerson Automation Solutions.
The contents of this publication are presented for informational purposes
only, and while every e󰀨ort has been made to ensure their accuracy,
they are not to be construed as warranties or guarantees, express or
implied,regarding the products or services described herein or their use
or applicability. All sales are governed by our terms and conditions, which
are available upon request. We reserve the right to modify or improve the
designs or specications of such products at any time without notice.
Emerson Process Management Regulator Technologies, Inc does not
assume responsibility for the selection, use or maintenance of any product.
Responsibility for proper selection, use and maintenance of any Emerson
Process Management Regulator Technologies, Inc. product remains solely
with the purchaser.
For further information on the current
PED revision see Bulletin: D103053X012
or scan the QR code.
Taking Out of Service (Shutdown)
▲ WARNING
To avoid personal injury resulting from sudden
release of pressure, isolate the regulator from all
pressure before attempting disassembly.
Parts List
Key Description
1 Control Spring
2 Adjusting Screw
3 Closing Cap
4 Control Spring Seat
5 Diaphragm and Plate Assy
6 Lower Diaphragm Plate
7 Diaphragm Plate Gasket
8 Pusher Post
9 Lever Assembly
11 Machine Screw
13 Stem
14 Cotter Pin
16 Body Gasket
17 Split Ring
19 Union Nut
20 Lower Casing
21 Diaphragm Case Cap Screw
Key Description
23 Spring Case
25 Disk Assembly
27 Orice
28 Body
29 Pipe Plug
30 Diaphragm Cap Screw
35 Closing Cap Gasket
44 Upper Spring Seat
46 Valve Disk Washer
47 Machine Screw
50 Nameplate
51 Drive Screws (4 required)
56 Vent Assembly
71 Bushing
74 Pitot Tube
93 Hex Nut
Figure 1. Type Y692 with a Heavy Control Spring Assembly
Figure 2. Type Y692 with a Light Control Spring Assembly Figure 3. Type Y692 Regulator
Americas
McKinney, Texas 75070 USA
T +1 800 558 5853
+1 972 548 3574
Europe
Bologna 40013, Italy
T +39 051 419 0611
Asia Pacic
Singapore 128461, Singapore
T +65 6777 8211
Middle East and Africa
Dubai, United Arab Emirates
T +971 4 811 8100

Other manuals for Fisher Y692

2

Other Emerson Controllers manuals

Emerson EC3-X33 User manual

Emerson

Emerson EC3-X33 User manual

Emerson EIM HQ Series User manual

Emerson

Emerson EIM HQ Series User manual

Emerson PCM-22 User manual

Emerson

Emerson PCM-22 User manual

Emerson dixell WING XW260L Wiring diagram

Emerson

Emerson dixell WING XW260L Wiring diagram

Emerson Fisher HSR Assembly instructions

Emerson

Emerson Fisher HSR Assembly instructions

Emerson Unidrive M700 User manual

Emerson

Emerson Unidrive M700 User manual

Emerson PACSystems RSTi-EP EPSCPE100 User manual

Emerson

Emerson PACSystems RSTi-EP EPSCPE100 User manual

Emerson Bettis XTE3000 User manual

Emerson

Emerson Bettis XTE3000 User manual

Emerson Control Link User manual

Emerson

Emerson Control Link User manual

Emerson Fisher HSR Series User manual

Emerson

Emerson Fisher HSR Series User manual

Emerson Dixell XW20LS Wiring diagram

Emerson

Emerson Dixell XW20LS Wiring diagram

Emerson Bettis XTE3000 Operating and maintenance instructions

Emerson

Emerson Bettis XTE3000 Operating and maintenance instructions

Emerson Fisher EZR Relief User manual

Emerson

Emerson Fisher EZR Relief User manual

Emerson Dixell IEV12D Wiring diagram

Emerson

Emerson Dixell IEV12D Wiring diagram

Emerson Fisher 2503 User manual

Emerson

Emerson Fisher 2503 User manual

Emerson Fisher 2052 User manual

Emerson

Emerson Fisher 2052 User manual

Emerson FISHER 657 User manual

Emerson

Emerson FISHER 657 User manual

Emerson Fisher 667 User manual

Emerson

Emerson Fisher 667 User manual

Emerson Hytork XL26 Instruction manual

Emerson

Emerson Hytork XL26 Instruction manual

Emerson Dixell WING XW264K Wiring diagram

Emerson

Emerson Dixell WING XW264K Wiring diagram

Emerson Yarway 20-55 Quick guide

Emerson

Emerson Yarway 20-55 Quick guide

Emerson ROC809 User manual

Emerson

Emerson ROC809 User manual

Emerson Aventics Sentronic PLUS 614 User manual

Emerson

Emerson Aventics Sentronic PLUS 614 User manual

Emerson Fisher 1052 User guide

Emerson

Emerson Fisher 1052 User guide

Popular Controllers manuals by other brands

Carel UltraCella Assembly and installation

Carel

Carel UltraCella Assembly and installation

Isel CSD 405-IMC Wiring and operation manual

Isel

Isel CSD 405-IMC Wiring and operation manual

Aaeon AEC-6915 manual

Aaeon

Aaeon AEC-6915 manual

Penny&Giles Solo Series Operation and installation

Penny&Giles

Penny&Giles Solo Series Operation and installation

QUANT QUANT-5,5 Operation manual

QUANT

QUANT QUANT-5,5 Operation manual

Duco L0001723VD quick start

Duco

Duco L0001723VD quick start

Intellitec 00-00606-100 Service manual

Intellitec

Intellitec 00-00606-100 Service manual

jbc SKR instruction manual

jbc

jbc SKR instruction manual

Dometic SmartStart SMRTSTACRV Installation and operating manual

Dometic

Dometic SmartStart SMRTSTACRV Installation and operating manual

Milton Roy LMI Liquitron DP5000 Series instruction sheet

Milton Roy

Milton Roy LMI Liquitron DP5000 Series instruction sheet

Pixsys DRR244 user manual

Pixsys

Pixsys DRR244 user manual

Phanteks PH-PWHUB manual

Phanteks

Phanteks PH-PWHUB manual

14POINT7 Edge AFR manual

14POINT7

14POINT7 Edge AFR manual

AlfaRadio AlfaSpid MD-01 manual

AlfaRadio

AlfaRadio AlfaSpid MD-01 manual

HAI OMNI LT Installation

HAI

HAI OMNI LT Installation

Novus N480D instruction manual

Novus

Novus N480D instruction manual

Penn P66AAB-1 installation instructions

Penn

Penn P66AAB-1 installation instructions

HAB Home Intelligence iBlinds user guide

HAB Home Intelligence

HAB Home Intelligence iBlinds user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.