WARNING
Personal injury or system damage may result if 
this controller is installed, without appropriate 
overpressure protection, where service 
conditions could exceed the limits given by the 
nameplates of either the regulator or controller 
or exceed the limits indicated in the regulator 
or controller instruction manuals.
All vents should be kept open to permit 
free ow of gas to the atmosphere. Protect 
openings against entrance of rain, snow, 
insects or any other foreign material that may 
plug the vent or vent line. When installing 
outdoors, point the spring case vent of the 
regulator and of the controller downward to 
allow condensate to drain. This minimizes the 
possibility of freezing and accumulation of 
water or other foreign materials entering the 
vent and interfering with proper operation.
Controller installations should be adequately 
protected from physical damage.
The equipment should not receive any type 
of shock causing damage to the casing and 
therefore causing leaks.
No modication should be made to the 
structure of the equipment (drilling, grinding 
and soldering).
Under enclosed conditions or indoors, 
escaping gas may accumulate and be an 
explosion hazard. In these cases, the vent(s) 
should be piped away from the regulator/
controller to the outdoors.
Failure to install a downstream control line 
could result in a hazardous condition. Install 
downstream control line(s) to the controller 
when construction uses external pressure 
registration. The regulator and controller 
will not control pressure or shut off if a 
downstream control line is not installed on 
those constructions where external pressure 
sensing line is required.
If the controller is exposed to an overpressure 
condition, it should be inspected for any 
damage that may have occurred. Controller 
operation within ratings does not preclude the 
possibility of damage from external sources or 
from debris in the pipeline.
General Installation Instructions
Note
The VSX4 and VSX8 Series can be rotated 
360° for easy installation and maintenance.
Install, use and maintain in accordance to all applicable 
codes and standards.
Before proceeding to installation:
•  Ensure that the controller is compatible with the gas 
being regulated.
•  Check for damage that might have occurred 
during shipment.
•  Check for and remove any dirt or foreign material that 
may have accumulated in the regulator or controller body.
•  Ensure that the external or internal sense port is clean.
•  When applying pipe sealing compound to piping and 
ttings, always apply to external threads.
•  Verify that:
 - Equipment limits of utilization (PS, TS) 
correspond to the desired operating conditions.
 - The inlet is protected by an appropriate device(s) to 
avoid exceeding the allowable limits (PS, TS).
 - The controller and its springs correspond to the desired 
operating conditions of associated regulator.
•  Connect downstream control line tubing to the 1/4 NPT 
connection in the lower casing and to the downstream 
pipe respecting a minimum distance of four times its 
diameter (see Figure 6).
•  Periodically check all vent openings to be sure that they 
are not plugged.
REGULATOR SETPOINT, 
mbar / psig
CONTROLLER STANDARD SETTINGS
UPSO / Minimum OPSO(1)(2) / Maximum OPSO(3) / Maximum
Pd< 35 / 0.51 Pdx 0.5 Pdx 2.0 Pdx 2.0 + 10 mbar / 0.145 psig
35 / 0.51 < = Pd< 60 / 0.87 Pdx 0.5 Pdx 1.7 Pdx 1.7 + 10 mbar / 0.145 psig
60 / 0.87 < = Pd< 160 / 2.32 Pdx 0.6 Pdx 1.5 Pdx 1.5 + 10 mbar / 0.145 psig
160 / 2.32 < = Pd< 180 / 2.61 Pdx 0.7 Pdx 1.4 Pdx 1.4 + 10 mbar / 0.145 psig
180 / 2.61 < = Pd< 300 / 4.35 Pdx 0.7 Pdx 1.4 - - - -
300 / 4.35 < = PdPdx 0.7 Pdx 1.3
The VSX4 Series assembly part number (without valve plug and controller springs): LP: GE35589X012, HP: GE35590X012
The VSX8 Series assembly part number (without valve plug and controller springs): LP: ERCA02667A0, HP: ERCA02668A0 
1. Regulator without relief valve (or with relief valve set above controller setting).
2. When selecting OPSO set points, the outlet pressure rating of the regulator should be considered.
3. Regulator with relief valve (set below controller setting).
Table 5. Controller Standard Factory Settings