
 
 
1592027600 XW90LT RTC GB r1.1 10.02.2012.doc XW90LT 3/6 
CoF Compressor OFF time with faulty probe: (0 to 255min) time during which the 
compressor is OFF in case of faulty thermostat probe. With CoF=0 compressor is 
always active. 
DISPLAY 
CF Temperature measurement unit: (°C; °F) °C = Celsius; °F = Fahrenheit. 
WARNING: When the measurement unit is changed the SET point and the values of 
the parameters HY, LS, US, ot, ALU and ALL have to be checked and modified (if 
necessary). 
rES Resolution (for °C): (in=1°C; dE=0.1°C) allows decimal point display. 
Lod Instrument display: (P1; P2, P3, P4, SET, dtr) it selects which probe is displayed by 
the instrument. P1 = Thermostat probe; P2 = Evaporator probe; P3 = Third probe 
(only for model with this option enabled); P4 = Fourth probe, SET = set point; dtr = 
percentage of visualization. 
rEd X-REP display (optional): (P1; P2, P3, P4, SET, dtr) it selects which probe is 
displayed by X- REP. P1 = Thermostat probe; P2 = Evaporator probe; P3 = Third 
probe (only for model with this option enabled); P4 = Fourth probe, SET = set point; 
dtr = percentage of visualization. 
dLY Display delay: (0 to 20min00s; res. 10s) when the temperature increases, the 
display is updated of 1°C or 1°F after this time. 
dtr Percentage of the second and first probe for visualization when Lod=dtr: (0 to 
99; 100=P1, 0=P2) if Lod=dtr it allows to set the visualization according to the 
percentage of the first and second probe, as for the following formula (dtr(P1-P2)/100 
+ P2). 
DEFROST 
EdF Defrost mode (only for controller with RTC): 
-rtC: Real Time Clock mode. Defrost time follows Ld1÷Ld6 parameters on 
workdays and Sd1÷Sd6 on holidays. 
 in: interval mode. The defrost starts when the time idf is expired. 
tdF Defrost type: (EL; in) EL = electrical heater; in = hot gas. 
dFP Probe selection for defrost termination: (nP; P1; P2; P3; P4) nP = no probe; 
P1 =thermostat probe; P2 = evaporator probe; P3 =configurable probe; P4 = Probe on 
Hot Key plug. 
dtE Defrost termination temperature: (-55 to 50°C; -67 to 122°F) (enabled only when 
EdF=Pb) sets the temperature measured by the evaporator probe, which causes the 
end of defrost. 
idF Interval between defrost cycles: (0 to 120hours) determines the interval of time 
between two defrost cycles. 
MdF (Maximum) length for defrost: (0 to 255min) when P2P=n, (not evaporator probe: 
timed defrost) it sets the defrost duration. When P2P=Y (defrost end based on 
temperature) it sets the maximum length for defrost. 
dSd Start defrost delay: (0 to 99min) this is useful when different defrost start times are 
necessary to avoid overloading the plant. 
dFd Temperature displayed during defrost: (rt; it; SEt; dEF) rt = real temperature; 
it = temperature at defrost start; SEt = set point; dEF = “dEF” label. 
dAd MAX display delay after defrost: (0 to 255min) sets the maximum time between the 
end of defrost and the restarting of the real room temperature display. 
Fdt Drip time: (0 to 120min) time interval between reaching defrost termination 
temperature and the restoring of the control’s normal operation. This time allows the 
evaporator to eliminate water drops that might have formed due to defrost. 
dPo First defrost after start-up: (n; Y) n= after the idF time, Y= immediately. 
dAF Defrost delay after continuous cycle: (0.0 to 24h00min, res. 10min) time interval 
between the end of the fast freezing cycle and the following defrost related to it. 
FANS 
FnC Fans operating mode: (C-n; o-n; C-Y; o-Y) C-n = runs with the compressor, OFF 
during defrost; o-n = continuous mode, OFF during defrost; C-Y = runs with the 
compressor, ON during defrost; o-Y = continuous mode, ON during defrost. 
Fnd Fans delay after defrost: (0 to 255min) interval between end of defrost and evaporator 
fans start. 
FCt Temperature differential to avoid fan short cycles: (0 to 59°C; 0 to 90°F) (N.B.: 
FCt=0 means function disabled) if the difference of temperature between the evaporator 
and the room probes is higher than FCt value, the fans will be switched on. 
FSt Fans stop temperature: (-55 to 50°C; -67 to 122°F) setting of temperature, detected 
by evaporator probe, above which fans are always OFF. 
Fon Fan ON time: (0 to 15min) with Fnc=C_n or C_Y, (fan activated in parallel with 
compressor) it sets the evaporator fan ON cycling time when the compressor is off. With 
Fon=0 and FoF≠0 the fan are always off, with Fon=0 and FoF=0 the fan are always 
off. 
FoF Fan OFF time: (0 to 15min) 
With FnC=C_n or C_Y, (fan activated in parallel with compressor) it sets the evaporator 
fan off cycling time when the compressor is off. 
With Fon=0 and FoF≠0 the fan are always off, with Fon=0 and FoF=0 the fan are 
always off. 
FAP Probe selection for fan management: (nP; P1; P2; P3; P4) nP = no probe; 
P1 =thermostat probe; P2 = evaporator probe; P3 =configurable probe; P4 = Probe on 
Hot Key plug. 
AUXILIARY THERMOSTAT CONFIGURATION – OAx = AUS 
ACH Kind of regulation for auxiliary relay: (Ht; CL) Ht = heating; CL = cooling. 
SAA Set Point for auxiliary relay: (-55.0 to 150.0°C; -67 to 302°F) it defines the room 
temperature set point to switch auxiliary relay. 
SHY Differential for auxiliary output: (0.1 to 25.5°C; 1 to 45°F) intervention differential for 
auxiliary output set point. 
ACH=CL, AUX Cut in is [SAA+SHY]; AUX Cut out is SAA. 
ACH=Ht, AUX Cut in is [SAA–SHY]; AUX Cut out is SAA. 
ArP Probe selection for auxiliary: (nP; P1; P2; P3; P4) nP = no probe, the auxiliary relay 
is switched only by the digital input; P1 = Probe 1 (Thermostat probe); P2 = Probe 2 
(evaporator probe); P3 = Probe 3 (display probe); P4 = Probe 4. 
Sdd Auxiliary relay off during defrost: (n; Y) n= the auxiliary relay operates during 
defrost. Y= the auxiliary relay is switched off during defrost. 
ALARMS 
ALP Probe selection for alarm: (nP; P1; P2; P3; P4) nP = no probe, the temperature 
alarms are disabled; P1 = Probe 1 (Thermostat probe); P2 = Probe 2 (evaporator 
probe); 
P3 = Probe 3 (display probe); P4 = Fourth probe. 
ALC Temperature alarms configuration: (Ab; rE) Ab = absolute temperature, alarm 
temperature is given by the ALL or ALU values. rE = temperature alarms are referred 
to the set point. Temperature alarm is enabled when the temperature exceeds the 
[SET+ALU] or [SET-ALL] values. 
ALU MAXIMUM temperature alarm: 
If ALC=Ab: [ALL to 150.0°C or ALL to 302°F] 
If ALC=rE: [0.0 to 50.0°C or 0 to 90°F] 
when this temperature is reached the alarm is enabled, after the ALd delay time. 
ALL Minimum temperature alarm: 
If ALC=Ab: [-55°C to ALU; -67 to ALU] 
If ALC=rE: [0.0 to 50.0°C or 0 to 90°F] 
when this temperature is reached the alarm is enabled, after the ALd delay time. 
AFH Differential for temperature alarm recovery: (0.1 to 25.5°C; 1 to 45°F) intervention 
differential for recovery of temperature alarm. 
ALd Temperature alarm delay: (0 to 255 min) time interval between the detection of an 
alarm condition and alarm signalling. 
dAo Exclusion of temperature alarm at start-up: (0.0 to 24h00min, res. 10min) time 
interval between the detection of the temperature alarm condition after instrument power 
on and alarm signalling. 
CONDENSER TEMPERATURE ALARM 
AP2 Probe selection for temperature alarm of condenser: (nP; P1; P2; P3; P4) 
nP = no probe; P1 = thermostat probe; P2 = evaporator probe; P3 = configurable probe; 
P4 = Probe on Hot Key plug. 
AL2 Low temperature alarm of condenser: (-55 to 150°C; -67 to 302°F) when this 
temperature is reached the LA2 alarm is signalled, possibly after the Ad2 delay. 
Au2 High temperature alarm of condenser: (-55 to 150°C; -67 to 302°F) when this 
temperature is reached the HA2 alarm is signalled, possibly after the Ad2 delay. 
AH2 Differential for temperature condenser alarm recovery: 0.1 to 25.5°C; 1 to 45°F 
Ad2 Condenser temperature alarm delay: (0 to 255 min) time interval between the 
detection of the condenser alarm condition and alarm signalling. 
dA2 Condenser temperature alarm exclusion at start up: 0.0 to 24h00min, res. 10min. 
bLL Compressor off with low temperature alarm of condenser: (n; Y) n= compressor 
keeps on working; Y= compressor is switched off till the alarm is present, in any case 
regulation restarts after AC time at minimum. 
AC2 Compressor off with high temperature alarm of condenser: (n; Y) n= compressor 
keeps on working; Y= compressor is switched off till the alarm is present, in any case 
regulation restarts after AC time at minimum. 
AUXILIARY RELAYS 
tbA Alarm relay silencing (with oAx =ALr): (n; Y) n= silencing disabled: alarm relay stays 
on till alarm condition lasts. Y= silencing enabled: alarm relay is switched OFF by 
pressing a key during an alarm. 
oA3 Third relay configuration (1-3): (dEF; FAn; ALr; LiG; AUS; onF; db; dEF2; HES) dEF 
= defrost; FAn = do not select it; ALr = alarm; LiG = light; AUS = Auxiliary relay; onF = 
always on with instrument on; db = neutral zone; dEF2 = do not select it; HES = night 
blind. 
oA4 Fourth relay configuration (22-23): (dEF; FAn; ALr; LiG; AUS; onF; db; dEF2; HES) 
dEF = defrost; FAn = do not select it; ALr = alarm; LiG = light; AUS = Auxiliary relay; 
onF = always on with instrument on; db = neutral zone; dEF2 = do not select it; HES = 
night blind. 
oA5 Fifth relay configuration (20-21): (dEF; FAn; ALr; LiG; AUS; onF; db; dEF2; HES) 
dEF = defrost; FAn = do not select it; ALr = alarm; LiG = light; AUS = Auxiliary relay; 
onF = always on with instrument on; db = neutral zone; dEF2 = do not select it; HES = 
night blind. 
AoP Alarm relay polarity: (CL; oP) it set if the alarm relay is open or closed when an alarm 
occurs. CL = terminals closed during an alarm; oP = terminals open during an alarm. 
DIGITAL INPUTS 
i1P First digital input polarity: (oP; CL) oP = the digital input is activated by opening the 
contact; CL = the digital input is activated by closing the contact. 
i1F First digital input configuration: (EAL; bAL; PAL; dor; dEF; ES; AUS; Htr; FAn; 
HdF; onF; Sbt) EAL = external alarm: “EA” message is displayed; bAL = serious alarm 
“CA” message is displayed; PAL = pressure switch alarm, “CA” message is displayed; 
dor = door switch function; dEF = activation of a defrost cycle; ES = energy saving; 
AUS = auxiliary relay activation with oA2=AUS; Htr = type of inverting action (cooling or 
heating); FAn = fan; HdF = Holiday defrost (enable only with RTC); onF = to switch the 
controller off; Sbt = to activate Sabbath mode. 
i2P Second digital input polarity: (oP; CL) oP = the digital input is activated by opening 
the contact; CL = the digital input is activated by closing the contact. 
i2F Second digital input configuration: (EAL; bAL; PAL; dor; dEF; ES; AUS; Htr; FAn; 
HdF; onF; Sbt) EAL = external alarm: “EA” message is displayed; bAL = serious alarm 
“CA” message is displayed; PAL = pressure switch alarm, “CA” message is displayed; 
dor = door switch function; dEF = activation of a defrost cycle; ES = energy saving; 
AUS = auxiliary relay activation with oA2=AUS; Htr = type of inverting action (cooling or 
heating); FAn = fan; HdF = Holiday defrost (enable only with RTC); onF = to switch the 
controller off; Sbt = to activate Sabbath mode. 
did Digital input 1 alarm delay: (0 to 255 min) delay between the detection of the external 
alarm condition and its signalling. 
When i1F= PAL, it is the interval of time to calculate the number of pressure switch 
activation. 
doA Door open alarm delay: 0 to 255 min. 
nPS Number of pressure switch activation: (0 to 15) Number of activation, during the did 
or d2d interval, before signalling an alarm event (i1F, i2F=PAL). 
If the nPS activation during did or d2d time is reached, switch off and on the 
instrument to restart normal regulation. 
odC Compressor status when open door: (no; FAn; CPr;F_C;) no = normal; 
FAn = normal; CPr = compressor OFF, F_C = compressor OFF.