
Mounting Procedure Mounting the Gas Detector • 5
• Halocarbon and hydrocarbon refrigerants are
heavier-than-air gases and as such, the gas
detectors should be located near ground level
(6 to 18 inches from the floor).
2.2.3. Refrigerated Spaces
In refrigerated spaces, gas detectors should be
located away from doors, in the return airflow to the
evaporators on a sidewall (below head-high is
preferred), or on the ceiling, not directly in front of an
evaporator, nor in any direct airflow. In large rooms
with multiple evaporators, gas detectors should be
mounted on the central line between two adjacent
evaporators, as turbulence will result in airflows
mixing.
2.2.4. Chillers
In the case of small water- or air-cooled enclosed
chiller units, mount the gas detector to monitor
airflow to the extract fans. With larger models also
place a gas detector inside the enclosure under or
adjacent to the compressors.
For enclosed air-cooled chillers or the outdoor unit
for variable refrigerant volume and variable
refrigerant flow (VRV/VRF) systems, mount the gas
detector to monitor airflow to the extract fan. With
large units also place a gas detector inside the
enclosure under or adjacent to the compressors.
2.3. Mounting Procedure
To open the housing as received, use a flat blade
screwdriver and depress the top latch. While pushing
the latch, grasp the back edge of the housing near the
latch and pull the back away.
When mounted, the housing is simply opened by
pressing the top latch with a suitable screwdriver or
other flat blade. With the top latch depressed, pull the
housing apart by grasping the sides and pulling
straight out. With the housing separated, the
mounting base with terminal blocks will be visible.
See Figure 2-1.
NOTE: Gas detectors should be positioned just
far enough back from any high-pressure parts
to allow gas clouds to form and be detected.
Otherwise, a gas leak might pass by in a high-
speed airflow area and go undetected by the gas
detector.
• Make sure that pits, stairwells, and trenches are
monitored since they may fill with stagnant pockets
of gas.
• For racks or chillers pre-fitted with refrigerant gas
detectors, these should be mounted so as to monitor
the compressors.
• Do not mount the gas detector directly to pipes or
structures that are subject to strong vibration.
CAUTION: Do not apply caulking or other
material around the gas detector base. The gas
detector relies on air exchange through the
spaces between the base and the gas detector
housing. Do not obstruct the small gap around the
housing and the base with any material.
Step Mounting Procedure
1 Open the housing (see Figure 2-1).
2 Position the base to the pre-determined
(acceptable) mounting location. Use the gas
detector base to mark the mounting locations
as needed. The hole pattern on the backplate is
sized to mount the gas detector onto various
electrical junction boxes. The other holes may
be used as needed to mount the gas detector to
other structures, or onto a wall.
3For Wall Mount, attach the MRLDS-250 base
to the mounting surface using two #6 screws
(provided) through two of the 7 mounting holes,
and be careful not to over-tighten the screws. Re-
fer to Figure 2-2 for the locations of mounting
holes on the base.
For Junction Box Mount, attach the MRLDS-
250 base to the junction box (using mounting
hardware provided with your junction box)
through the two junction box holes. Refer to
Figure 2-2 for the locations of the two junction
box mounting holes on the base.
4Unless you are ready to wire the device (see
Section 3, Wiring and Configuration),
carefully snap the cover onto the base unit.
Table 2-1 Mounting Procedures