ENDA EUC942 User manual

1/5
Read this document carefully before using this device. The guarantee will be expired by
damaging of the device if you don't attend to the directions in the user manual. Also we don't
accept any compensations for personal injury, material damage or capital disadvantages.
ENDA EUC942 PID UNIVERSAL CONTROLLER
* 96 x 96mm sized.
* Selectable sensor type.
* Selectable 0-20mA or 4-20mA input.
* Soft-Start.
* Automatic calculation of PID parameters (SELF TUNE).
* Selectable Heat/Cool control.
* Communication vai RS-485 ModBus protocol (Optional).
* Selectable 0-20mA or 4-20mA analog control output.
* Relay output can be programmable as second alarm or control output.
* AL1 relay output for first alarm out.
* Input offset feature.
* In the case of sensor failure relay state can be
selected.
* Panel or ModBus can be done through the control outputs.
periodical running or
* Parameter access protection on 3 levels.
* Programming by using keypad or Modbus.
* CE marked according to European Norms.
Thank you for choosing ENDA EUC942 universal controller.
* Selectable analog, SSR or relay control output.
Enter PID parameters of the system if they are known at the beginning.
Otherwise, Self-Tune should be activated.
AL1
CNT/AL2
AN/SSR
UNIVERSAL CONTROLLER
EUC 942
ENDA
PV
SV
SET
ASETCSET
OUTPUTS
Selectable as Control or Alarm2 output. Relay : 250V AC, 2A ( for resistive load), NO/NC.
Selectable as 0-20mA, 4-20mA analog output or logic control output.
(Alarm1 output). Relay : 250V AC, 2A ( for resistive load), NO/NC selectable.
AL1
ANL/SSR
Mechanical 30.000.000 operation; Electrical 300.000 operation
Life expectancy for relay
CONT./AL2
ENVIRONMENTAL CONDITIONS
Height Max. 2000m
80 up to 31 decreasing linearly 50 at 40 . % %
Ambient/storage temperature
Max. Relative humidity 0 ... +50 / °C -25... +70°C (with no icing)
°C °C
Rated pollution degree According to EN 60529 Front panel : IP65
Rear panel : IP20
Do not use the device in locations subject to corrosive and flammable gases.
ELECTRICAL CHARACTERISTICS
Supply 90-250V AC, 50/60Hz or 9-30V DC/7-24V AC
Power consumption Max. 7VA
2.5mm² screw-terminal connections
Wiring
Line resistance
Data retention
EMC
Safety requirements EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B for standard EN 61000-4-3)
EEPROM (minimum 10 years)
EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)
For thermocouple max.100ohm, for 3 wired PT100 max. 20ohm
CONTROL
Control type Single set-point and alarm control
On-Off / P, PI, PD, PID (selectable)
Control algorithm
A/D converter 15 bits
Sampling time
Proportional band
Derivative time
Integral time
Control period
Hysteresis
Output power
500ms
Adjustable between 0 and 100 . If Pb=0 , On-Off control is selected.% % %
Adjustable between 0.0 and 100.0 minutes
Adjustable between 0.00 and 25.00 minutes
and 250 secondsAdjustable between 1
1 and 50 Adjustable between °C/F
The ratio of power at a set point can be adjusted between 0 and 100% %
HOUSING
Housing type Suitable for flush-panel mounting according to DIN 43 700.
Dimensions W96xH96xD50mm
Weight Approx. 410g (after packing)
Self extinguishing plastics.
Enclosure material
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
J (Fe-CuNi) Thermocouple
K (NiCr-Ni) Thermocouple
T (Cu-CuNi) Thermocouple
S (Pt/0Rh-Pt) Thermocouple
R (Pt13Rh-Pt) Thermocouple
0-20 mA
4-20 mA
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
0... 600
0...1200
0... 400
0...1600
0...1600
°C
°C
°C
°C
°C
+32... +1112
+32... +2192
+32... +752
+32... +2912
+32... +2912
°F
°F
°F
°F
°F
PT100 Resistance Thermometer
PT100 Resistance Thermometer EN 60751
EN 60751 -200...600
-99.9...300.0
-999...4000
-999...4000
°C
°C 0,2% ( )of full scale
0,2% ( )of full scale 1 digit
1 digit
0,2% ( )of full scale 1 digit
0,2% ( )of full scale 1 digit
0,2% ( )of full scale
0,2% ( )of full scale
0,2% ( )of full scale
1 digit
1 digit
1 digit
0,2% ( )of full scale 1 digit
0,2% ( )of full scale 1 digit
-328... +1112
-99.9...+543.0°F
°F
°C °F
TECHNICAL SPECIFICATIONS
Input type Temperature range Accuracy
EUC942-E-04-201312

2/5
A1.tp.
IndE.
A2.tp.
IndE.
A1.St.
HI.
A2.St.
HI.
A1.P.e.
on
A1.Hy.
2
A2.Hy.
2
ALr.o. ConF.
A1.p.e. = State of Alarm1 output in the
case of sensor failure.
If A1.p.e.= On , the alarm output is
energized during the sensor failure.
If A1.p.e.= oFF, the alarm output is not
energized during the sensor failure.
A2.p.e. =
case of sensor failure.
If A2.p.e.= On, the alarm output is
energized during the sensor failure.
If A2.p.e.= oFF, the alarm output is not
energized during the sensor failure.
NOTE! If C.ot.S. = .out1, this
parameter is not seen.
State of Alarm2 output in the
A1. =
output.
Adjustable between 1 and 50°C.
Hysteresis decimal scale value can be
adjusted between 0.1°C and 5.0°C for
Hy. Hysteresis of the Alarm1
A2. =
output.
Adjustable between 1 and 50°C.
NOTE! If C.ot.S. =.out1, this
parameter is not seen.
Hy. Hysteresis of the Alarm2
A1.tP. =
Four kinds of functions can be selected.
indE. = Independent
dE. = Deviation
bAnd = Band
bAn.i. = Band with inhibition
Function of Alarm1 output.
A2.tP. =
Four kinds of functions can be selected.
indE. = Independent
dE. = Deviation
bAnd = Band
bAn.i. = Band with inhibition
NOTE! If C.ot.S. = .out1, this
parameter is not seen.
Function of Alarm2 output.
A1.St. =
If independent or deviation alarm is
selected, this parameter can be Lo.
and Hi.. For Lo. alarm output is
energized below the alarm set point. For
Hi. alarm output is energized above the
alarm set point. If band alarm is
selected, this parameter can be bIHI
or boHI. bIHI means alarm is
activated inside the band.boHI means
alarm is activated outside the band.
The state of Alarm1.
A2.St. =
If independent or deviation alarm is
selected, this parameter can be Lo.
and Hi.. For Lo. alarm output is
energized below the alarm set point. For
Hi. alarm output is energized above the
alarm set point. If band alarm is
selected, this parameter can be bIHI
or boHI. bIHI means alarm is
activated inside the band.boHI means
alarm is activated outside the band.
NOTE! If C.ot.S. = .out1, this
parameter is not seen.
The state of Alarm2.
InP.
FE.cn.
C.Hi.L.
600
C.Lo.L.
0
oFFS.
0
inP. = .
Pt = PT100 -200 to +600°C
Pt.0 = PT100 -99.0 to +300.0°C
FE.cn. = J (Iron vs. Copper-Nickel) 0 to +600°C
nc.nA. = K (Nickel-Cr.vs. Nickel-Alum.) 0 to +1200°C
c.cn. = T (Copper vs. Copper-Nickel) 0 to +400°C
P10.r. = S (Platinum-10%Rhodium vs. Pt.) 0 to +1600°C
P13.r. = R (Platinum-13%Rhodium vs. Pt.) 0 to +1600°C
0-20 = 0-20 mA -999 to 3000
4-20 = 4-20 mA -999 to 3000
Note : If the selected input type is changed, the value of
C.Hi.L, C.Lo.L , A.Hi.L., A.Lo.L. parameters changes
automatically.
Type of input and scale
C.Hi.L. =
If InP. or UnIt. parameters are changed, the maximum
value of the C.Hi.L. parameter changes to the maximum
scale value of the selected input. The minimum value is the
value of C.Lo.L. parameter.
Set point upper limit.
C.LoL. =
If InP. or UnIt. parameters are changed, the minimum
value of the C.Lo.L. parameter changes to the minimum
scale value of the selected input. The maximum value is the
value of parameter.
Set point lower limit.
C.Hi.L.
oFFS. =
Offset value is added to the measurement value.
Adjusted between -99 and +99°C.
The normal value is 0.
Decimal scale value can be adjusted between -9.9°C and 9.9°C
for PT100.
Offset value.
If key is pressed while holding key, the programming mode is enabled.
C.HyS.
6
SET
CSET
SET
CSET
Modification of Parameter
When holding key, the value of parameter flashes and using keys the requested value can be adjusted.
A1.H.L.
600
A2.H.L.
600
A1.L.L.
0
A2.L.L.
0
UnIt =
Selectable as °C or °F.
Note : If the temperature unit is changed, the value of the
UPL., Lol., A.UP.L., A.Lo.L. Parameters changes
automatically.
NOTE! IfInp parameter is selected TC or PT100, this
parameter is seen.
The temperature unit.
A1.H.L
If InP. or UnIt. parameters are changed, the maximum
value of the A1.H.L. parameter changes to the maximum
scale value of the selected input type. Minimum of A1.H.L.
parameter is the value of A1.L.L. parameter.
= Alarm1 value upper limit.
A2.H.L
If InP. or UnIt. parameters are changed, the maximum
value of the A2.H.L. parameter changes to the maximum
scale value of the selected input type. Minimum of A2.H.L.
parameter is the value of A2.L.L. parameter.
NOTE! If C.ot.S. = .out1, this parameter is not seen.
= Alarm2 value upper limit.
A1.L.L. =
If InP. or UnIt. parameters are changed, the minimum
value of the A1.L.L. parameter changes to the minimum
scale value of the selected input type. The maximum value
is the value of A1.H.L. parameter.
Alarm1 value lower limit.
A2.L.L. =
If InP. or UnIt. parameters are changed, the minimum
value of the A2.L.L. parameter changes to the minimum
scale value of the selected input type. The maximum value
is the value of A2.H.L. parameter.
NOTE! If C.ot.S. = .out1, this parameter is not seen.
Alarm2 value lower limit.
ASET ASET
C.ot.S. = Type of control output
out1 = Out1 control output.
0-20 = Analog control output.
( 0mA %0 energy, 20mA %100 energy )
Out1 = Alarm2 output.
4-20 = Analog control output.
( 4mA %0 energy, 20mA %100 energy )
Out1 = Alarm2 output.
s.s.r = SSR control output.
Out1=Alarm2 output.
S.S.t.S. = Soft Start timer set point value
This parameter indicates the time to reach set
point value when the device is first energized.
Adjustable between 0 and 250 minutes.
If 0 is selected, soft start feature will be enable
and the device reaches set point value quickly.
NOTE! Setting Pb = 0, sotf start feature will be
disable.
ASET
C.HyS.
5
C.HyS.
6
SET
CSET
Con.o.
Pb
4
C.oT.S.
Out1
tI
4.0
td
1.00
Ct
20
P.SEt.
0
C.HyS.
2
C.StA.
HEAt
Pr.Er.
0
SET
CSET
SET
CSET
ASET
SET
CSET
SET
CSET
C.HyS.
6
ASET
Page 3/5
ConF. Page 3/5
A2.P.e.
oFF
S.S.T.S.
0 fL.Co.
5
fL.Co. = Coefficient of digital filter.
Filter for display value.
Adjustable between 1 and 32. If this parameter is 1, digital
filter runs most quick. If the parameter is 31, the filter run
most slow. The value of parameter should be increased in
interference.
Pb = Proportional band.
Adjustable between 0% and 100%
Setting Pb = 0% On-Off control is
selected.
Ti = Integral time.
Adjustable between 0.0 and 100.0 minutes.
If ti = 0.0, integral effect is not used.
Setting Pb = 0 this parameter is not seen.
td = Derivative time.
Adjustable between 0.00 and 25.00 minutes.
If td = 0.00, derivation effect is not used.
Setting Pb = 0 this parameter is not seen.
Ct = Control period.
Adjustable between 1 and 250 seconds.
Setting Pb = 0 and this
parameter is not seen.
C.ot.S.= Out1
P.SEt. = The ratio of output power at the set
point.Adjustable between 0% and 100%.
If this parameter is set to 0, the output power
becomes 0 at the set point. If it is adjusted to
50% output power becomes 50% at the set
point. Using this parameter the energy
requirements of the system is adjusted at the
set point. So the set point can be achieved by
minimum fluctuations and in the shortest time.
Setting Pb = 0, this parameter is not seen.
C.StA. = Configuration of the control output.
C.StA. = HEAt means heating control.
C.StA. = cooL means cooling control.
Pr.Er. = This parameter is used to adjust the
control output during a sensor failure.
Adjustable between 0% and 100%.
If this parameter is adjusted to a value closer to
the energy requirements of the system at the set
point, process temperature is prevented to rise or
drop to dangerous levels.
If key is pressed and held 0.6 seconds, the value of the selected parameter changes rapidly. If waited enough,
the value increases 100 at each step. After 1 second following the release of the key, initial condition is returned.
The same procedure is valid for the decrement key.
C.HYS. = Hysteresis of the control output.
Adjustable between 1 and 50 °C/F.
Adjustable between 0,1 and 5,0 ,if
inp=Pt.0 setting Pb=0 , this parameter is
seen. Hysteresis decimal scale value can be
adjusted between 0.1°C and 5.0°C for PT100.
°C/F
Unit.
°C
A.o.L.L.
A.o.H.L.
A.o.L.L. =Minimum analog output value (%
output) ,adjustable between 0 and 100.
A.o.H.L. =Maximum analog output value (%
output) ,adjustable between 0 and 100.
EUC942-E-04-201312

3/5
S.tun.
ASET
SET
CSET
ASET
Entering from the programming mode to the run mode:
If no key is pressed within 20 seconds during programming mode, the data is stored automatically and the run mode is entered.
Alternatively, the same function occurs first pressing key and then pressing keys together.
Before starting sef-tune
procedure, be sure A.tun
parameter is YES
in the SECU menu.
S.Str.
run
SET
CSET
SET
CSET
SET
CSET
S.Str.
run
SECU.
ASET
S.cod.
0
A.Con.
P.yES
A.ALr.
P.yES
A.CNF.
P.yES
A.tun.
yES
ASET
S.cod. =
code.
It should be 666.
Security menu access
A.Con. = CoN.o
access level code.
nonE = Invisible
P.yES = Modification can be done.
P. no = Only visible.
Parameters of menu
A.ALr.. = ALr.o
menu access level code.
nonE = Invisible
P.yES = Modification can be done.
P. no = Only visible.
Parameters of
A.CNf. = ConF.
access level code.
nonE = Invisible
P.yES = Modification can be done.
P. no = Only visible.
Parameters of menu
A.tun. = S.tun.
access level code.
no = Invisible
yES = Self tune can be done.
Parameters of menu
SET
CSET
ASET
ASET
25
Pid.t.
After
PID is
calculated
Page 2/5
ConF. Page 2/5
d.adr.
1
baud
off
d.adr. = Device address.
Adjusable between 1 and 247. Difference addresses
should be selected for every device.
Baud= Modbus baud rate.
Selectable 1200, 2400, 4800 and 9600.
If baud= off, Modbus communication will be
disable.
U.sC.l.
-999
U.sC.H.
4000
d.pnt.
0
U.sC.l. = Lower scale value for mA inputs.
Adjustable between -999 and the (U.sC.H. - 100)
NOTE! If Inp is selected one of the mA input types, this
parameter is seen.
U.sC.H. = Upper scale value for mA inputs.
Adjustable between (U.sC.l. + 100) and 4000.
NOTE! If Inp is selected one of the mA input types,
this parameter is seen.
d.pnt. = Decimal point for mA inputs.
Adjustable between 0 and 2.
NOTE! If Inp is selected one of the mA input types,
this parameter is seen.
Process value is
equal or lower than
60%of the set point ?
Yes
No
25
REdY.
Press
any key
70
TE.Hi.
When process value decreases
appropriate temperature
to self tune
Press any key
to deactivate
the self-tune procedure.
25
P.SE.t.
press and hold
While holding key, run message flashes. Then when key is pressed, self tune mode is entered if there is no probe failure. If process value is
appropriate to begin self tune, rEdY. message flashes. Then press any key to see Pid.t. message and self tune procedure begins.
Process value must be equal or lower than 60%of the setpoint to begin self tune procedure. If not, tE.Hi. message flashes and device waits to decrease
appropriate temperature to begin self tune. Then rEdY. message flashes and press any key to begin sellf tune procedure.
Before self tune procedure, A.tun. parameter must be selected yES from the SECU menu.If self tune is achieved A.tun. parameter becomes no automatically
and S.tun menu is canceled. Before self tune procedure, temperature setpoint value should be adjusted. When self tune procedure begins with no failure,
Pid.t. message flashes and remains during the calculation of PID parameters. When PID parameters are calculated, P.SE.t. message flashes. Then the device
heats until setpoint value according to PID parameters and calculates the energy requirement for stable temperature and writes P.SE.t. parameter as %and run
mode enters.
If any key is pressed while Pid.t. message flashes, self tune prosedure is deactivated before calculation of PID parameters. If any key is pressed while P.SE.t.
message flashes, then self tune prosedure is deactivated as PID parameters are calculated and P.SE.t. parameter is done 0.
t..oF.E.
no
t.oF.E. = Control outputs on/off key,activation parameter.
If t.oF.E =no,To make the on/off outputs; key is not used.
If T.Of.E=yES, To make the on/off outputs; key is used.
EUC942-E-04-201312

4/5
MODIFICATION OF CONTROL AND ALARM SET POINTS
ALARM1 AND ALARM2 OUTPUT TYPES
A1.tP.=indE
Independent Alarm
A1.tP.= DE.
Deviation Alarm
Band Alarm
A1.tP.= bAnd
A1.tP.= BAn.i.
Band Alarm With Inhibition
A.StA.= Hi
A1.St.= boHi
A.StA.= Lo
A1.St.= biHi
ASV
SV SV
SV
SV+ASV
SV+ASV
SV-ASV
OFF OFF
OFF
OFF OFF
OFF
-300
300
+300
300
ON ON
ON
ON ON
ON
ON ON
OFF OFF
Beginning
of procedure
SV =Set point of CONT output ASV = Set point of AL1 output (ASV min. = 0, ASV max. = 300 )
SV = ASV = Set point of CONT output Set point of alarm output
(ASV min. =-300, ASV max. = +300)
(ASV min. = 0, ASV max. = +300)
(
ASV max = end of scale)
ASV min = beginning of scale
SV = ASV = Set point of CONT output Set point of AL1 output
Band alarm is possible Band alarm is possible
Beginning
of procedure
SV SV
SV+ASV SV+ASV
SV-ASV SV-ASV
a1.Hy. A1.Hy..
A1.Hy.
A1.Hy.
C.SEt
150
- - - -
- - - -
PFA
150
PSC
150
A1.sE.
250
C.SEt
150
A1.sE.
250
A1.sE.
249
First, press and hold key until the massage C.Set appears on the display. Then, the value is adjusted by using keys.
SET
CSET
SET
CSET
SET
CSET
SET
CSET
ASET ASET ASET
When CSET is released, it
returns to normal operation.
When ASET is released, it
returns to normal operation.
130
150
PV PV
PV PV PV PV
PV
PV
PVPV
SV SV
SV SV SV SV
C.SEt
149
PV
SV SV
SV
SV
SV
Error Messages
First, press and hold key, alarm setpoint value appears on the display. Then, the value is adjusted by using keys.
If C.ot.S different from out1. Alarm1 and Alarm2 setpoint values can be adjusted in sequence when per press key.
.
ASET
ASET
SET
CSET
ASET
NOTE: The maximum of is the value of parameter and the minimum of it is the value of parameter.
If independent alarm is selected, A1.SE. and values can be adjusted between the limits of the full scale.
If deviation alarm is selected, A1.SE. and A2.SE. values can be adjusted between - and + .
If band alarm is selected, A1.SE. and A2.SE. values can be adjusted between 0 and +300.
C.SEt C.Hi.L. C.Lo.L.
A2.SE.
300 300
Temperature value is
higher than the scale Temperature value is
lower than the scale Temperature sensor
is broken or over temperature PT100 or a sensor
line is short circuited
150 150
(
ASV max. = +30.0)
If ,inP = Pt..0 ASV min. = -30.0,
(If , inP = Pt..0 ASV min. = 0.0, ASV max. = +30.0)
TERMS
( 2 ) SV display
Character heights
( 3 ),( 4 ),( 5 ),( 6 ) Keypad
( 7 ) State indicator
( 1 ) PV display
PV mmdisplay :20
SV display :14 mm
4 digits 7 segment yellow LED
4 digits 7 segment red LED
Micro switch
3 red LEDs for Control, Alarm1 and SSR outputs
AL1
CNT/AL2
AN/SSR
UNIVERSAL CONTROLLER
EUC 942
ENDA
PV
SV
SET
ASETCSET
( 7 )
( 1 )
Mnemonic parameter code during programming
Process value during normal operation
( 2 )
Data value during programming
Set point during normal operation.
( 4 )
If only this key is pressed in normal operation, software version number is seen.
Parameter selection key during programming
Decrement key during normal operation
( 3 )
Parameter selection key during programming
Increment key during normal operation and programming
( 5 )
Menu selection key during programming
Alarm set key during normal operation
( 6 ) Control
Parameter selection key during programming
set key during normal operation
EUC942-E-04-201312

SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.
Yukarı Dudullu Barbaros Cd. No:18 34775 - ÜMRANİYE/İSTANBUL-TÜRKİYE
Tel : +90 216 499 46 64 Pbx. Fax : +90 216 365 74 01
url : www.enda.com.tr 5/5 EUC942-E-04-201312
Gasket
Depth
Panel cut-out
AL1
CNT/AL2
AN/SSR
UNIVERSAL CONTROLLER
EUC 942
ENDA
PV
SV
SET
ASETCSET
98mm
96mm
104mm
99mm
90.5mm
90.5mm
57mm
Panel
50mm
1
2
DIMENSIONS
ENDA EUC942 is intended for installation in control panels. Make sure that the device is used only for intended purpose.
shielding must be grounded on the instrument side. During an installation, all of the cables that are connected to the device
must be free of energy. The device must be protected against inadmissible humidity, vibrations, severe soiling and make sure
that the operation temperature is not exceeded. All input and output lines that are not connected to the supply network must
be laid out as shielded and twisted cables. These cables should not be close to the power cables or components. The
installation and electrical connections must be carried on by a qualified staff and must be according to the relevant locally
applicable regulations.
The
CONNECTION DIAGRAM
Note ) Panel thickness should be maximum 10mm.
2) If there is no 60mm free space at back side of the device,
it would be difficult to remove it from the panel.
: 1
Flush mounting
clamp
-While pressing both side of
the device in direction 1, push it
in direction 2.
For removing the device from
the panel:
Logic output of the instrument is not
electrically insulated from the
internal circuits. Therefore, when
using a grounding thermocouple, do
not connect the logic output
terminals to the ground.
1) Mains supply cords shall meet
the requirements of IEC 60227 or
IEC 60245.
2) In accordance with the safety
regulations, the power supply
switch shall bring the identification
of the relevant instrument and it
should be easily accessible by the
operator.
Note
Holding screw
0.4-0.5Nm
Equipment is protected throughout
by DOUBLE INSULATION.
For J-K-T-S-R type thermocouple :
Use suitable compensation cables. Don't use
jointed cables. Pay attention to the polarities
of the thermocouple cables as shown in the
figure right are connected to the .
For resistance thermometer :
When 2 wired PT100 is used, terminals 9
and 10 must be short circuited.
Fuse should
be connected.
90-250V AC or
21.6-26.4V AC
50/60Hz 5VA
230V or 9-30V DC/7-24 AC
Supply
switch
Cable size: 1,5mm²
Neutral
Line
SENSOR INPUT :
2
1
TC
-
+
-
+
8
9
8
10
PT100
0-20mA or
4-20mA input
-
-
+
+
8
9
NOTE :
Fuse
F 100 mA
250V AC
SUPPLY :
9
Order Code - : EUC942-
2- Modbus Option
RS........RS-485 Modbus communication
None....No RS-485 Modbus communication
1- Supply Voltage
230VAC...90-250V AC
SM...........9-30V DC / 7-24V AC
1 2
Screw-terminal connections
Enviroment temperature
measurement sensor
SN: XXXXXXXXX
AL1 AC 250V 2A
RESISTIVE LOAD
18
297 14 156 133 10
411
5 12
ENDA
INDUSTRIAL ELECTRONICS
EUC942-230VAC-RS
PID UNIVERSAL CONTROLLER
CONT./AL2 OUT
AC 250V 2A
RESISTIVE LOAD
+
-
PT100 TC
(mA inp).
-
+
RS-485 COM.
RS- 485
ANL/SSR
OUT
B
A
+
-
8 680407 713196
Made in Turkey
SN: XXXXXXXXX
AL1 AC 250V 2A
RESISTIVE LOAD
18
297 14 156 133 10
411
5 12
ENDA
INDUSTRIAL ELECTRONICS
EUC942-230VAC
PID UNIVERSAL CONTROLLER
CONT./AL2 OUT
AC 250V 2A
RESISTIVE LOAD
+
-
PT100 TC
(mA inp).
ANL/SSR
OUT
+
-
8 680407 713189
Made in Turkey
90-250V AC +10% -20%
50/60Hz 7VA
90-250V AC +10% -20%
50/60Hz 7VA