5. Operating parameter description
&RPPXZLQ,, 0DWUL[
)HOG 3DUDPHWHU 6LJQLILFDQFH
9:25.,1*3$5$0(7(56
V0H0 Process Variable (PV)
Measured Temperature
PV regarding the selected unit [°C or °F] V2H2, corrected by bias value
entered in field V0H5, in case of error the PV will be 9999 or -9999
V0H1 Cold junction (RJ)
Temperature
Temperature of cold junction (terminal temperature) according to the
selected unit [C or F] V2H2 when "internal" RJ Mode V0H3 is defined.
V0H2 Input Filter
Selection range: 0 .. 32s
Damping of the input signal in seconds, according to the reaction time
to filter the input.
V0H3 Cold junction (RJ) Mode
Select: Internal or External
The smartgrad TMD833 field transmitter has an "internal" cold junction
compensation for thermocouples. If "external" is selected, the reference
temperature must be indicated in V0H4.
V0H4 (RJ) External Value, Selection range:
-50°C .. +94°C or -58°F .. +201,19°F
Before setting up the External Value of Cold junction, the Measuring
Unit [°C or °F] in V2H2 must be defined.
V0H5 Bias Input
Selection range: -10 .. 10 Units
Parallel shifting of the Linearisation to correct Sensor drifts or
Thermometer installation inaccuracy.
9&$/,%5$7,21&+$1
V2H0 Input Sensor, Selection
RTD Thermometer: Pt100, Ni100, Pt1000
Thermocouples: Type B, E, J, K, L, R, S, T, N or U
Voltage: mV Full scale
Resistance: 400 Ohms Full scale or 4000 Ohms Full scale
Not used: Pt100/TT-CAL, Pt100/TT-CAL and Ni/TT-CAL
V2H2 Measuring unit
Select: °C or °F
Selection of Process Variable unit, the unit is applied to the fields
V0H0 - V0H1 - V0H4 - V2H4 - V2H5
V2H3 Output Action
Select: DIR. or REV. DIR. = Direct: 4 .. 20 mA / REV. = Reverse: 20 .. 4 mA
V2H4 (PV) Value for 4 mA
Selection regarding Sensor Type
Zero value of PV in the selected unit. Before setting up this value, the
Measuring Unit [°C or °F] in V2H2 must be defined. The value must be
internal the input range of the thermometer.
V2H5 (PV) Value for 20 mA
Selection regarding Sensor Type
Upscale value of PV in the selected unit. Before setting up this value,
the Measuring Unit [°C or °F] in V2H2 must be defined. The value must
be within the input range of the thermometer.
V2H6
Operation Mode
Resistance wire connection
Select: 2 WIRE, 3 WIRE or 4 WIRE
Connection to the Sensor, applicable to RTD Thermometers and
Resistance input.
V2H7 2 WIRE Compensation
Selection range: 0 .. 30 Ohms
If the 2 WIRE connection in V2H6 is selected, the value to be inserted is
the resistance of the connection wires with 0.01 Ohms resolution.
V2H8 Safety Alarm
Select: MAX. or MIN.
MAX.: Alarm output = 21 mA / MIN.: Alarm output = 3.8 mA.
If self-diagnostics detect a sensor burnout or transmitter failure, the
analogue signal will be driven to the selected value.
V2H9 Instrument address
Selection range: 0 .. 15
Instrument address in the BUS structure. For point to point
communication, the address must be 0 !
For multi-drop connection the address can be set from 1 to 15
96(59,&(
V9H0 Error Code This field shows the transmitter status, see chapter 6. for details.
V9H1 Last Diagnostic This field shows the previous status of the instrument.
V9H5 Simulation
Select: OFF or ON
Set up of output simulation. If ON is selected, the analogue signal will
be driven to the value indicated in V9H6 !
V9H6 SIM. Value
Selection range: 3.8 mA .. 21 mA
The output simulation value for a "Test" period can be entered here, if
simulation is selected in field V9H5 !
V9H9 Default Values
Putting 833 in this field sets all the parameters to the default values,
see chapter 5.1 !
Note: The indicated BUS address will not be changed.
9$86(5,1)250$7,21
VAH0 TAG Number
An 8 character alpha-numeric string is available to enter measuring
point designation. With Commuwin II configuration the first digit must
be a letter or _ !
VAH2 Software Version Contains information relating to the instrument software version.
VAH3 Modification Contains information relating to the smartgrad TMD833 field transmitter.
VAH4 Serial Number Contains information relating to the circuit board production.
5.1 Standard configuration
Unless otherwise requested the smartgrad
TMD833 field transmitter is delivered with default
values according to the following standard
setting:
Pt100 Sensor, Measuring unit [°C]
Measuring range: -200°C .. +850°C
Output: 4 .. 20 mA
Safety Alarm: MIN.: Alarm output = 3.8 mA
Other Values to zero.
These default values will also be implemented, if the code 833 is placed in the field V9H9 !