- FIELD WIREABLE QD CONNECTORS - THREE-PHASE
Safety Symbols
+DANGER: This indicates a hazardous situation, which if
not avoided, will result in death or serious injury.
*WARNING: This indicates a situation where failure to
follow instructions may be a safety hazard or cause
equipment malfunction. Use extreme caution and follow
instructions carefully.
;WARNING: Risk of burn. Failure to follow instructions
may result in burn injury.
✓NOTE: This indicates information particularly important
for optimal system operation.
SAFETY
IMPORTANT SAFETY INSTRUCTIONS.
SAVE THIS INFORMATION.
Follow all safety and assembly instructions when installing En-
phase Three-Phase Field Wireable QD Connectors.
DISCONNECT (if needed)
To disconnect Enphase Three-Phase Field Wireable QD Connectors,
release the two connectors by pressing down the snap with a screw-
driver. You can then separate the connectors
* WARNING: Never plug in or disconnect the connectors under load.
The connectors are not suitable for interrupting the current.
Safety Instructions
+DANGER: Risk of electric shock. Do not use Enphase
equipment in a manner not specied by the manufacturer.
Doing so may cause death or injury to persons, or damage
to equipment.
+DANGER: Risk of electric shock. Be aware that installation
of this equipment includes risk of electric shock. Do not use
without rst removing AC power from the Enphase System.
Disconnect the power coming from the photovoltaics
before servicing or installing.
+DANGER: Risk of electric shock. Never plug in or disconnect
the connectors under load. The connectors are not suitable
for interrupting the current.
+DANGER: Risk of electric shock. Risk of re. Before making
any connections verify that the circuit breakers are in the off
position. Double check all wiring before applying power.
+DANGER: Risk of electric shock. Risk of re. Only use
electrical system components approved for wet locations,
including but not limited to conduit ttings.
+DANGER: Risk of electric shock. Risk of re. Only qualied
personnel should install, troubleshoot, or replace the En-
phase Three-Phase Field Wireable QD Connector.
+DANGER: Risk of electric shock. Improper use of the Three-
Phase Field Wireable QD Connector or its components may
result in a shock, re or explosion. To reduce these risks,
disconnect all wiring before attempting any maintenance.
+DANGER: Risk of electric shock. Risk of re. Ensure that all
AC and DC wiring is correct and that none of the AC wires
are pinched, shorted, or damaged.
+DANGER: Risk of electric shock. Risk of re. Do not attempt
to repair or alter the Enphase Three-Phase Field Wireable
QD Connector.
+DANGER: Risk of electric shock. Risk of re. Make sure the
conductors are not damaged. If the exposed wires are dam-
aged, the system may not function properly.
*WARNING: Risk of equipment damage. Enphase male and
female connectors must only be mated with the matching
male/female connector.
*WARNING: Risk of equipment damage. This product is
intended for operation in an environment having a maximum
ambient temperature of 105°C(221°F).
*WARNING: When installing the cabling, secure any loose
cable to minimize tripping hazard
*WARNING: Before installing or using the Enphase Three-
Phase Field Wireable QD Connector, read all instructions
and cautionary markings in the technical description, on the
Enphase System, and on the photovoltaic (PV) equipment.
*WARNING: For eld connections, use 10 or 12 AWG wires
insulated for a minimum of 75°C.
✓NOTE: Using unapproved attachments or accessories may
result in damage or injury.
✓NOTE: When looping the Enphase QD Cable, do not form
loops smaller than 3.62 inches (9.2 cm) in diameter.
✓NOTE: Perform all electrical installations in accordance with
all applicable local electrical codes: the Canadian Electri-
cal Code, part 1; the National Electrical Code (NEC); ANSI
requirements; and NFPA 70.
✓NOTE: To ensure optimal reliability and to meet warranty re-
quirements, install the Enphase Three-Phase Field Wireable
QD Connectors according to the instructions in this guide.
✓NOTE: Protection against lightning and resulting voltage
surge must be in accordance with local standards.
✓NOTE: The connector is considered to be in compliance
with UL 6703 only when assembled in the manner specied
by these assembly instructions.
✓NOTE: For exible wires, we recommend using ferrules acc.
to DIN 46228 that are crimped with jointing clamp.
✓NOTE: Cable used with Enphase Three-Phase Field Wireable
QD Connectors must meet the following requirements:
• Min/max outer insulation diameter (including the
clear second insulator): 8mm / 21mm
• Wire size: 2.5mm2 to 6mm2
Enphase Customer Support: enphase.com/en-us/support/contact