FIELD-WIREABLE CONNECTORS
Check that you have Enphase Field Wireable Q Connectors as needed for
your installation. Both female and male connectors are sold in packs of ten:
• Field-Wireable Q connector (female): (Q-CONN-10F)
• Field-Wireable Q connector (male): (Q-CONN-10M)
Make sure you have the following required tools:
• Diagonal cutter
• Wire stripper
• Crimp tool: Multi-Contact PV-CZM-18100, -19100, or -22100
• Channel lock pliers or torque wrench
• Enphase disconnect tool
When to Use Field-Wireable Q Connectors
Use Enphase eld-wireable connectors with Enphase Q-Cable or eld
cable to:
• Easily connect Q cables on the roof without complex wiring
• Use male connectors to make connections from any Q Aggregator
open connector
• Use female connectors to make connections from any Q Cable
open connector
• Make a jumper to connect with a remote part of the array: Use
female to female for cable-to-cable connections, or male to female
for aggregator-to-cable extensions
• Use a mated pair of connectors to splice two cut ends of cable
PREPARATION
Enphase
disconnect
tool
Safety Instructions
+DANGER: Risk of electric shock. Do not use Enphase
equipment in a manner not specied by the manufacturer.
Doing so may cause death or injury to persons, or damage
to equipment.
+DANGER: Risk of electric shock. Be aware that installation
of this equipment includes risk of electric shock. Do not use
without rst removing AC power from the Enphase System.
Disconnect the power coming from the photovoltaics before
servicing or installing.
+DANGER: Risk of electric shock. Risk of re. Before making
any connections verify that the circuit breakers are in the off
position. Double check all wiring before applying power.
+DANGER: Risk of electric shock. Risk of re. Only use
electrical system components approved for wet locations,
including but not limited to conduit ttings.
+DANGER: Risk of electric shock. Risk of re. Only qualied
personnel should install, troubleshoot, or replace the En-
phase Field Wireable Connector.
+DANGER: Risk of electric shock. Improper use of the Field
Wireable Connector or its components may result in a shock,
re or explosion. To reduce these risks, disconnect all wiring
before attempting any maintenance.
+DANGER: Risk of electric shock. Risk of re. Ensure that all
AC and DC wiring is correct and that none of the AC wires
are pinched, shorted, or damaged.
+DANGER: Risk of electric shock. Risk of re. Do not attempt
to repair or alter the Enphase Field Wireable Connector.
+DANGER: Risk of electric shock. Risk of re. Make sure
the conductors are not damaged. If the exposed wires are
damaged, the system may not function properly.
*WARNING: Risk of equipment damage. Enphase male and
female connectors must only be mated with the matching
male/female connector.
Safety Symbols
+DANGER: This indicates a hazardous situation, which if not
avoided, will result in death or serious injury.
*WARNING: This indicates a situation where failure to
follow instructions may be a safety hazard or cause
equipment malfunction. Use extreme caution and follow
instructions carefully.
;WARNING: Risk of burn. Failure to follow instructions may
result in burn injury.
✓NOTE: This indicates information particularly important for
optimal system operation.
SAFETY
IMPORTANT SAFETY INSTRUCTIONS.
SAVE THIS INFORMATION.
Follow all safety and assembly instructions when installing
Enphase Field Wireable Connectors.
Safety Instructions
*WARNING: Risk of equipment damage. This product is
intended for operation in an environment having a maximum
ambient temperature of 55ºC (131ºF).
*WARNING: When installing the cabling, secure any loose
cable to minimize tripping hazard
*WARNING: Before installing or using the Enphase Field
Wireable Connector, read all instructions and cautionary
markings in the technical description, on the Enphase Sys-
tem, and on the photovoltaic (PV) equipment.
✓NOTE: Using unapproved attachments or accessories may
result in damage or injury.
✓NOTE: When looping the Enphase Q Cable, do not form
loops smaller than 4.75 inches (12 cm) in diameter.
✓NOTE: Perform all electrical installations in accordance with
all applicable local electrical codes: the Canadian Electri-
cal Code, part 1; the National Electrical Code (NEC); ANSI
requirements; and NFPA 70.
✓NOTE: To ensure optimal reliability and to meet warranty
requirements, install the Enphase Field Wireable Connectors
according to the instructions in this guide.
✓NOTE: Protection against lightning and resulting voltage
surge must be in accordance with local standards.
✓NOTE: The connector is considered to be in compliance with
UL 6703 only when assembled in the manner specied by
these assembly instructions.
✓NOTE: Cable used with Enphase Field Wireable connectors
must meet the following requirements:
• Min/max outer insulation diameter (including the clear 2nd
insulator): 3.45mm / 3.65mm
• Number of conductor strands / size:19 strands of 0.47 mm
• Wire size: 12 AWG
Revision History
Rev 01 Initial release 02/21/2017
B) Make sure the gasket is pre-installed inside the
cover, then slide the cover and gasket over the
cable.
C) Attach the terminals to the cable:
• Strip the outer jacket to 32 mm (1.25 in.) and strip the
inner insulation to 9.5 mm (3/8 in.).
• Load the open end of each terminal in the 12 gauge
slot of the crimp tool, ush with the edge of the slot.
• Crimp the end of the terminal over the stripped copper
wires.
• Do NOT crimp over insulation.
D) Insert terminals into connector body. Each terminal
should click into place.
E) Assemble connector body and cover. Listen for a click
as they engage.
F) Tighten the nut to 7 Nm with channel lock pliers or a torque
wrench.
Connector body
Terminals
Cover
Nut
FEMALE CONNECTOR PARTS
MALE CONNECTOR PARTS
Gasket
Connector body
Terminals
Cover
NutGasket
A) Slide the nut over the cable.
PARTS
© 2017 Enphase Energy. All rights reserved.
Enphase Customer Support: enphase.com/en-us/support/contact
ASSEMBLY
Follow the steps to assemble Enphase Field-Wireable Connectors.
FEMALE MALE
* WARNING: Risk of equipment failure. Do not
mix male and female connector parts when
assembling connectors.

This manual suits for next models

2

Other enphase Cables And Connectors manuals

enphase ET17-240-40 User manual

enphase

enphase ET17-240-40 User manual

enphase IQ Series User manual

enphase

enphase IQ Series User manual

enphase Q-CONN-3P-10F User manual

enphase

enphase Q-CONN-3P-10F User manual

enphase Ensemble COMMS-KIT-01 User manual

enphase

enphase Ensemble COMMS-KIT-01 User manual

enphase Q-CONN-3P-10F User manual

enphase

enphase Q-CONN-3P-10F User manual

enphase CT-200-SOLID User manual

enphase

enphase CT-200-SOLID User manual

enphase EP200G-LITKIT User manual

enphase

enphase EP200G-LITKIT User manual

enphase QD-CONN-10F User manual

enphase

enphase QD-CONN-10F User manual

enphase Engage Cable User manual

enphase

enphase Engage Cable User manual

Popular Cables And Connectors manuals by other brands

Danfoss DEVI 140F0955 installation guide

Danfoss

Danfoss DEVI 140F0955 installation guide

Tait T02-00034-EAAA installation instructions

Tait

Tait T02-00034-EAAA installation instructions

Koganei RBP006RCA instruction manual

Koganei

Koganei RBP006RCA instruction manual

EFOY Mastervolt manual

EFOY

EFOY Mastervolt manual

BGS technic BGS 3321 instruction manual

BGS technic

BGS technic BGS 3321 instruction manual

Amphenol H4 Cable Series instruction manual

Amphenol

Amphenol H4 Cable Series instruction manual

Hubbell HBLC40123 installation instructions

Hubbell

Hubbell HBLC40123 installation instructions

Amphenol HVSL1200 Guidelines

Amphenol

Amphenol HVSL1200 Guidelines

Techno THB.381.A2 Series manual

Techno

Techno THB.381.A2 Series manual

Philips SWV3565 Specifications

Philips

Philips SWV3565 Specifications

SIIG JU-CSL111-S1 user manual

SIIG

SIIG JU-CSL111-S1 user manual

Philips SWA7534W Specifications

Philips

Philips SWA7534W Specifications

Rextron VSA12 user manual

Rextron

Rextron VSA12 user manual

Eaton 600 A 15 kV class T-OP II Assembly/installation instructions

Eaton

Eaton 600 A 15 kV class T-OP II Assembly/installation instructions

LEGRAND Galion 2 824 54 manual

LEGRAND

LEGRAND Galion 2 824 54 manual

Panasonic CA-LSR01U Installation

Panasonic

Panasonic CA-LSR01U Installation

Philips Sonicare 300 SerieS user manual

Philips

Philips Sonicare 300 SerieS user manual

Amphenol EGT Series Assembly Work Instructions

Amphenol

Amphenol EGT Series Assembly Work Instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.