4
PMC-E FORCED DRAFT EVAPORATIVE CONDENSERS
Method of Shipment
Forced draft units are shipped either fully assembled (small units) or with the coil section(s) separate
from the basin/fan section(s). These sections have mating flanges and will join together in a
waterproof joint when sealed and bolted together as described in the following instructions.
Miscellaneous items, such as sealer, self-tapping screws and any other required materials, are
packaged and placed inside the pan for shipment.
NOTE: All casing sections are factory inspected prior to shipment to verify proper fit for rigging.
Please take extra care to handle and rig each section per the instructions of this manual to
avoid possible distortion and poor casing alignment. It is advisable to check each section upon
receipt and during each lift to ensure that the factory alignment has not been altered. Should
the field inspection indicate the section alignment (“square”) has been altered, please contact
the factory or your local EVAPCO representative for additional instructions to obtain proper
section fit.
Storage
Do not place tarps or other coverings over the top of the units if the units are to be stored before
installation. Excessive heat can build up if the units are covered causing possible damage to the PVC
eliminators. For extended storage beyond six months rotate the fan and fan motor shaft(s) monthly.
Also, the fan shaft bearings should be purged and regreased prior to startup.
General
For extended lifts, or where hazards may exist, it is recommended that safety slings and spreaders be
employed for safety. Refer to the extended lift information in this bulletin.
International Building Code Provisions
The International Building Code (IBC) is a comprehensive set of regulations addressing the structural
design and installation requirements for building systems–including HVAC and industrial
refrigeration equipment. Since June 2008, all 50 states plus Washington, D.C. have adopted the
International Building Code. The code provisions require that evaporative cooling equipment and all
other components permanently installed on a structure must meet the same seismic design criteria
as the building. The PMC-E condensers are compliant with the latest IBC codes.
All items attached to the EVAPCO PMC-E evaporative condenser must be independently reviewed
and isolated to meet applicable wind and seismic loads. This includes piping, ductwork, conduit, and
electrical connections. These items must be flexibly attached to the EVAPCO unit so as not to
transmit additional loads to the equipment as a result of seismic or wind forces.
Structural Steel Support
Two structural I-beams running the length of the unit are required for supporting the unit. These
beams should be located underneath the outer flanges of the unit as shown in Figure 1. See Table 1
for steel support dimensions.
Mounting holes, 3/4”(19mm) in diameter, are located in the bottom flange for bolting to the struc-
tural steel. Refer to the recommended structural steel support drawing and certified print for exact
bolt hole location. Bolt the basin/fan section to the steel support before rigging the coil section.
Beams should be sized in accordance with accepted structural practices. Maximum deflection of the
beam under the unit should be 1/360 of the unit length, not to exceed 1/2”(13mm). Deflection may
be calculated by using 55% of the operating weight as a uniform load on each beam (see certified
print for operating weight).