Faraday MPC-1500 Plus User manual

Faraday, LLC / 805 South Maumee Street / Tecumseh, Michigan 49286
Phone 517-423-2111 Fax 517-423-2320
Copyright©2001 Faraday,LLC, AllRightsReserved
MPC-1500 PlusPlus
Fire Alarm System Control Unit
Owner’s Manual
12530-120 / 12530-240
12540-120 / 12540-240
P/N 447203
Issue I
7/2001

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I i
Table of Contents
I. INTRODUCTION ..................................................................................................................I-1
CONTROL UNIT LIMITATIONS.............................................................................................I-1
INSTALLATION AND WARRANTY INFORMATION................................................................I-2
Installer Information:.........................................................................................................I-2
Original Purchaser Information:.........................................................................................I-2
PREFACE ............................................................................................................................I-3
II. DESCRIPTIONS..................................................................................................................II-1
SYSTEM DESCRIPTION.....................................................................................................II-1
HARDWARE CONFIGURATION ..........................................................................................II-1
MINIMUM CONTROL UNIT CONFIGURATION.....................................................................II-2
Power Supply .................................................................................................................II-2
Addressable Device Circuits ............................................................................................II-2
Notification Appliance Circuits..........................................................................................II-2
RS485 Communications Circuit........................................................................................II-2
Status Relays .................................................................................................................II-2
City Tie Connection.........................................................................................................II-2
RS232 Printer Connection ...............................................................................................II-2
OPTIONAL CONTROL UNIT CONFIGURATION...................................................................II-3
Initiating Device Circuits ..................................................................................................II-3
Addressable Device Circuits ............................................................................................II-3
Notification Appliance Circuits..........................................................................................II-3
Isolated Printer Connection..............................................................................................II-3
User Programmable Relays .............................................................................................II-3
Digital Alarm Communicator ............................................................................................II-3
Digital Alarm Communicator ............................................................................................II-3
BATTERY SETS..................................................................................................................II-4
AUXILIARY MODULES........................................................................................................II-4
Remote LCD Annunciator................................................................................................II-4
Serial Relay Unit and Serial Relay Extender .....................................................................II-4
Serial Annunciator Unit and Serial Annunciator Extender...................................................II-4
Network Interface Board..................................................................................................II-4
Auxiliary Power Supplies .................................................................................................II-4
ADDRESSABLE DEVICES ..................................................................................................II-5
Faraday Addressable Detectors .......................................................................................II-5
Other Faraday Addressable Devices ................................................................................II-5
System Sensor Addressable/Analog Sensors ...................................................................II-5
Other System Sensor Addressable Devices......................................................................II-6
PROCESSOR CONTROLLED OUTPUT ZONES...................................................................II-6
Output Sounding Patterns ...............................................................................................II-6
Control of Audible Silencing.............................................................................................II-6
Audible Silence Inhibit.....................................................................................................II-6
EVENT HISTORY................................................................................................................II-7
GENERAL DESIGN FEATURES ..........................................................................................II-8
Environmental.................................................................................................................II-8
Power Limiting ................................................................................................................II-8
Ground Fault Detection ...................................................................................................II-8
Transient Protection ........................................................................................................II-8
Security Functions ..........................................................................................................II-8
REGULATORY STANDARDS ..............................................................................................II-8
Underwriters Laboratories................................................................................................II-8
GENERAL SPECIFICATIONS ..............................................................................................II-9

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I ii
Environmental.................................................................................................................II-9
Primary Supply ...............................................................................................................II-9
Secondary and Trouble Power Supply..............................................................................II-9
Auxiliary Power Outputs ..................................................................................................II-9
Addressable Device Circuits ............................................................................................II-9
Notification Appliance Circuits........................................................................................II-10
Status Relays ...............................................................................................................II-10
RS485 Communications Circuit......................................................................................II-10
City Tie.........................................................................................................................II-10
RS232 Printer Output ....................................................................................................II-11
Initiating Device Circuits (Optional board P/N 12503).......................................................II-11
DACT Expansion Module (Optional module P/N 12513) ..................................................II-11
Alarm Relay Board (Optional board P/N 12402)..............................................................II-11
III. CONTROL UNIT OPERATION............................................................................................III-1
OPERATION INSTRUCTIONS ............................................................................................ III-1
A. Standby Condition.....................................................................................................III-1
B. Alarm Condition ........................................................................................................III-1
C. Trouble Condition .....................................................................................................III-2
D. Supervisory Condition ...............................................................................................III-2
E. Maintenance.............................................................................................................III-2
ADDITIONAL OPERATING PROCEDURES......................................................................... III-3
A. Lamp Test................................................................................................................III-3
B. Drill..........................................................................................................................III-3
C. Recall ......................................................................................................................III-3
D. Pre-Alarm.................................................................................................................III-3
E. General Alarm ..........................................................................................................III-3
F. Tornado....................................................................................................................III-3
G. History .....................................................................................................................III-4
12530/12540 OPERATING INSTRUCTIONS........................................................................ III-5
12506 OPERATING INSTRUCTIONS .................................................................................. III-6
IV. CONTROL UNIT INSTALLATION ...................................................................................... IV-1
PARTS SUPPLIED.............................................................................................................IV-1
CAUTIONS ........................................................................................................................IV-1
CONTROL UNIT LOCATION...............................................................................................IV-1
ENCLOSURE MOUNTING..................................................................................................IV-1
A. Surface Mounting Instructions -12530....................................................................... IV-2
B. Surface Mounting Instructions -12540....................................................................... IV-3
C. Semi-Flush Mounting Instructions -12530................................................................. IV-4
D. Semi-Flush Mounting Instructions -12540................................................................. IV-5
E. Knock-Outs ............................................................................................................. IV-6
F. Main Termination Board Installation........................................................................... IV-6
G. Loop Driver Board Installation................................................................................... IV-7
H. Transformer Mounting.............................................................................................. IV-8
I. Front Plate Assembly................................................................................................ IV-9
J. Front Plate Mounting ...............................................................................................IV-10
K. Door Assembly.......................................................................................................IV-11
L. AC Supply Connection.............................................................................................IV-11
M. Battery Installation..................................................................................................IV-11
N. Powering the Control Unit........................................................................................IV-12
O. Checking Supervised Circuits..................................................................................IV-12
P. Optional Modules ....................................................................................................IV-12
Q. System Wiring........................................................................................................IV-12
R. Check System Operation.........................................................................................IV-12
V. SYSTEM WIRING............................................................................................................... V-1

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I iii
CONTROL UNIT WIRING OVERVIEW ................................................................................ V-1
WIRING SEPARATION....................................................................................................... V-2
PRIMARY AND SECONDARY POWER WIRING.................................................................. V-3
PRINTER WIRING.............................................................................................................. V-3
AUXILIARY POWER OUTPUT WIRING............................................................................... V-4
System Power Requirement Calculations ........................................................................ V-4
Auxiliary Power Supply................................................................................................... V-4
Battery Size Calculations................................................................................................ V-4
CITY TIE AND STATUS RELAYS WIRING .......................................................................... V-5
NAC WIRING..................................................................................................................... V-5
RS485 COMMUNICATIONS CIRCUIT................................................................................. V-6
Remote Device Power.................................................................................................... V-6
Remote Device Data...................................................................................................... V-6
ADDRESSABLE DEVICE CIRCUIT..................................................................................... V-7
Addressable Device Wiring Diagrams.............................................................................. V-7
Addressable/Analog Sensors .........................................................................................V-11
Addressable Modules....................................................................................................V-17
VI. PROGRAMMING THE CONTROL UNIT............................................................................. VI-1
MAIN TERMINATION BOARD JUMPERS............................................................................VI-1
MAIN LOGIC BOARD JUMPERS ........................................................................................VI-2
LOOP DRIVER BOARD JUMPERS .....................................................................................VI-2
CONVENTIONAL EXPANSION BOARD JUMPERS .............................................................VI-2
LOOP/SIGNAL EXPANSION JUMPERS ..............................................................................VI-3
REMOTE LCD ANNUNCIATOR JUMPER............................................................................VI-4
REMOTE LCD ANNUNCIATOR SWITCHES........................................................................VI-4
SERIAL RELAY UNIT JUMPERS ........................................................................................VI-4
SERIAL RELAY UNIT SWITCHES.......................................................................................VI-5
SERIAL ANNUNCIATOR UNIT JUMPERS ...........................................................................VI-5
SERIAL ANNUNCIATOR UNIT SWITCHES .........................................................................VI-5
KEYPAD PROGRAMMING.................................................................................................VI-6
PROGRAMMING SECURITY ..............................................................................................VI-6
VII. MAINTENANCE............................................................................................................... VII-1
GENERAL.........................................................................................................................VII-1
QUICK TEST.....................................................................................................................VII-2
VIII. APPENDIX-A: REFERENCE DATA ................................................................................. VIII-1
WIRE SELECTION GUIDES .............................................................................................VIII-1
Resistance of Solid Copper Wire.................................................................................. VIII-1
Initiating Device Circuit Wire Selection Guide................................................................ VIII-1
Notification Appliance Circuit Wire Selection Guide....................................................... VIII-2
Addressable Device Circuit Wire Selection Guide.......................................................... VIII-2
BATTERY SIZE CALCULATIONS .....................................................................................VIII-3
IX. APPENDIX-B: COMPATIBLE DEVICES ............................................................................ IX-1
DEVICES FOR ADDRESSABLE DEVICE CIRCUITS............................................................IX-1
Faraday Addressable Modules....................................................................................... IX-1
Faraday Addressable Detectors ..................................................................................... IX-1
Faraday Bases ............................................................................................................. IX-1
Faraday Accessories..................................................................................................... IX-1
System Sensor Addressable/Analog Sensors ................................................................. IX-2
System Sensor Bases ................................................................................................... IX-2
System Sensor Addressable/Analog Modules ................................................................. IX-2
System Sensor Accessories .......................................................................................... IX-2
DEVICES FOR INITIATING DEVICE CIRCUITS...................................................................IX-3
Manual Stations ............................................................................................................ IX-3

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I iv
Waterflow Switches....................................................................................................... IX-3
Supervisory Switches .................................................................................................... IX-4
Contact Type Heat Detectors ......................................................................................... IX-4
UL Compatible Two-Wire (Circuit Powered) Smoke & Heat Detectors .............................. IX-5
UL Compatible Four-Wire (Separately Powered) Smoke Detectors .................................. IX-6
DEVICES FOR NOTIFICATION APPLIANCE CIRCUITS ......................................................IX-7
Notification Appliances .................................................................................................. IX-7
Accessory Devices.......................................................................................................IX-10
DEVICES FOR AUXILIARY POWER OUTPUTS ................................................................ IX-11
Door Holders ...............................................................................................................IX-11
Relays.........................................................................................................................IX-11
X. APPENDIX-C: TROUBLESHOOTING ................................................................................. X-1
TROUBLESHOOTING INDICATORS....................................................................................X-1
DEFINITIONS FOR EVENT HISTORY ENTRIES ..................................................................X-1
A. General.................................................................................................................... X-1
B. System Troubles....................................................................................................... X-2
C. System Events ......................................................................................................... X-3
XI. APPENDIX-D: INSTALLATION INSTRUCTIONS................................................................ XI-1
12522 Loop Driver Board -447202................................................................................ XI-3
12503 Conventional Expansion Board -446992............................................................. XI-5
12504 Class A Adapter -446993................................................................................... XI-7
12505 Loop/Signal Expansion -446994......................................................................... XI-9
12506 Remote LCD Annunciator –446983...................................................................XI-11
12507/12508 Serial Relay Unit/Serial Relay Extender -447073 .....................................XI-13
12509/12510 Serial Annunciator Unit/Serial Annunciator Extender -447074...................XI-15
401403 Fire Alarm Accessory Enclosure -447138 ........................................................XI-17
12511 Serial Isolation Board -447065..........................................................................XI-19
12513 DACT Expansion Module -447153....................................................................XI-21
12401A Class A Adapter -447062 ...............................................................................XI-25
12402 Alarm Relay Board -446062..............................................................................XI-27
12408 Auxiliary Power Supply –446066.......................................................................XI-29
12410 Digital Communicator Cable -446060 ................................................................XI-35
XII. APPENDIX-E: GLOSSARY .............................................................................................. XII-1

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I I-1
I. INTRODUCTION
CONTROL UNIT LIMITATIONS
This control unit may not show an alarm condition without compatible initiating devices (smoke detectors,
etc.) and notification devices (horn, lights, etc.) connected to it. Electrical ratings of the initiation and
notification appliances must be compatible with the electrical ratings of the control unit and must be
properly interconnected. The wiring used for interconnection must be large enough to carry the total
current for all appliances without excessive voltage drop.
The control unit must be connected to a dedicated primary electrical source that has a high degree of
reliability and adequate capacity for this control unit. The only means of disconnecting this power source
shall be available only to authorized personnel and clearly marked "Fire Alarm Circuit Control".
The control unit must also have connected to it a battery set (24v) that has enough capacity to properly
operate the system for 24 or 60 (depending on system type) hours standby and 5 minutes alarm per
NFPA 72 (chapter 1). These batteries do lose capacity with age. Batteries must be replaced when they
fail to provide the control unit with the required standby and alarm power or after 4 years, whichever
happens first. These batteries must be checked for performance at least two (2) times a year or more
often if local requirements dictate.
Fire alarm control units cannot last forever. Even though this control unit was made to last for the
expected life of the fire alarm system, any part could fail at any time. Therefore a regular test program
should be followed and documented to make sure that each part of the system is tested as in Chapter 7
of NFPA 72 or more often if dictated by local code requirements. Malfunctioning units must be replaced
or repaired immediately by factory authorized service personnel.
NOTE: This control unit is designed to show an alarm condition when the
initiating devices connected to it detect specific conditions. These conditions
may or may not represent a life-threatening condition. Also, evacuation of a
building or area unnecessarily may subject individuals to an unnecessary
hazard. Therefore, it is most important that the building owner, manager, or
representative promulgate, distribute, and/or post instructions describing
steps to be taken when the fire alarm control unit signals an alarm condition.
These instructions should be developed in cooperation and conformance with
representatives of the local authority having jurisdiction.
As a backup or precautionary measure, it is strongly suggested that one of these steps should be to notify
the local fire department of an abnormal condition even where the DACT option (or similar device) is
included in the system.

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I I-2
INSTALLATION AND WARRANTY INFORMATION
Warranty Information: Faraday, LLC (the Manufacturer) provides a limited warranty to the original
purchaser of this product. The original purchaser is the party to whom the manufacturer issued its sales
order, generally the manufacturer's distribution. In order to preserve this warranty, it is important that only
persons who have been properly trained and authorized by the manufacturer service the product.
Other parties involved in the installation of this product may have also provided a warranty, which may be
different from that of the manufacturer. The manufacturer will only be responsible to the original
purchaser and only for the manufacturer's own warranty. For further information regarding the
manufacturers warranty, contact the original purchaser.
OWNER'S MANUAL: The owner's manual does not purport to cover all the details or variations in the
equipment described, nor does it provide for every possible contingency to be met in connection with
installation, operation and maintenance. All specifications subject to change without notice. Should
further information be desired or should particular problems arise which are not covered sufficiently, the
matter should be referred to the installer or original purchaser listed below.
Installer Information:
Company:
Installer:
Phone:
Address:
City:
State:
Zip:
Date installed:
Installer's signature:
Original Purchaser Information:
Company:
Phone:
Address:
City:
State:
Zip:
Purchaser's purchase order number:
Date purchased:
Faraday sales order acknowledgment number:
Original purchaser's signature:

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I I-3
PREFACE
Along with the use of this instruction manual, the appropriate following standards and the manufacturer's
instructions for initiating and notification devices should be used to install and maintain a functioning fire
alarm signaling system.
NFPA 70 National Electrical Code
NFPA 72 National Fire Alarm Code
NFPA 101 Life Safety Code
For other standards that may apply contact the authority having jurisdiction.
For NFPA publications, contact:
National Fire Protection Association
Batterymarch Park
Quincy, Massachusetts 02269

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I I-4
This page is intentionally blank.

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I II-1
II. DESCRIPTIONS
SYSTEM DESCRIPTION
The 12530/12540 is an advanced modular fire alarm control unit. It features addressable/analog
detection, programming, and memory capability. Its base configuration includes two addressable device
circuits, with four conventional notification appliance circuits.
The 12530 control unit mounts in a 24" x 14-3/8" back-box with overall cover size of 24-9/16" x 14-3/4".
The 12540 control unit mounts in a 35-11/16" x 14-3/8" back-box with overall cover size of 35-31/32" x
14-3/4". Operating controls and indicators are mounted on the plate with a polycarbonate decal for
identification. An 80-character LCD display provides specific indications for addressable devices while
LEDs indicate general panel status.
Semi-flush mounting kits are available for the enclosure.
HARDWARE CONFIGURATION
The main termination board mounts in the rear of the enclosure. The power supply is physically
contiguous with the main board. The 12530/12540 main termination board provides the interface for
external analog system connections, for the addressable device circuit, four notification appliance circuits,
remote signaling and indicating interfaces, and the electronics of the main system power supply. Optional
boards mount on or plug into the main termination board.
The main logic board mounts on the front plate, allowing it to carry the controls and displays which must
be accessible.
All normal operation is controlled from the front of the control unit via push-button switches. Displays are
provided by an 80-character, alphanumeric, backlit LCD display and by discrete LED indicators for major
control unit functions.
The 80-character LCD display is used to display event data, including alarms and troubles, identification
of zone or device, and presentation of history. The display is controlled by a set of four push-button
switches commanding the control processor. A back light is included in the display to assure visibility in
low light, but to conserve power, it is only activated during a reported event or on operation of a display
control switch.
Individual LEDs on the panel are provided to indicate SYSTEM ALARM, PREALARM, SUPERVISORY,
ALARM SILENCED, SYSTEM TROUBLE and AC POWER ON. Direct push-button controls are provided
for ALARM SILENCE, TROUBLE SILENCE/ACKNOWLEDGE, MENU and SYSTEM RESET. These
switches require concurrent use of the security keyswitch.

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I II-2
MINIMUM CONTROL UNIT CONFIGURATION
Power Supply
A 4A, 24V nominal power supply provides all operating power to the control unit for both standby and
alarm conditions. Sufficient battery charging capability is available to charge sealed lead-acid batteries
within code requirements for 60 hour quiescent plus 5 minutes alarm. The cabinet will hold batteries only
up to 10 AH. The back-up battery is 24V, maintained by floating on the power supply. The power supply
is physically contiguous with the main board.
Addressable Device Circuits
The main termination board has an addressable loop driver board supporting two addressable device
circuits, that is programmed for connection to Faraday or System Sensor addressable devices.
Faraday Addressable Devices:
Each addressable device circuit drives up to 60 addressable devices, detectors and/or modules.
System Sensor Addressable Devices:
Each addressable device circuit drives up to 99 addressable sensors and 99 addressable
modules.
Notification Appliance Circuits
The base control unit has four notification appliance circuits (NACs). Each circuit can be selected to give
continuous output or one of eight sounding patterns available in the control unit. There is also a system
coder capable of zone coded operation. All of the NACs are power limited and can be wired for Class B
(Style Y) operation or Class A (Style Z) operation with the Faraday 12504 Class A Adapter.
RS485 Communications Circuit
The control unit has a RS485 Communications Circuit that will drive up to 16 remote LCD annunciators
and 8 Serial Relay Units and Serial Annunciator Units on the RS485 communication line.
Status Relays
Five dry relay contacts are provided. These contacts are dedicated to alarm, trouble, supervisory, AC
failure and processor failure indications. The relay contacts are form C and are rated 2A@30VDC or
0.5A@30VAC, resistive.
City Tie Connection
The city tie connection provides reverse polarity, local energy or shunt operation. The polarity reversal
connections provide an alarm circuit with trouble and/or supervisory output.
RS232 Printer Connection
The RS232 printer connection will allow event data to a serial printer, terminal or computer or data from
and to a Network Interface Board.

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I II-3
OPTIONAL CONTROL UNIT CONFIGURATION
A maximum control unit configuration can include all of the minimum configuration items plus additions as
noted below. Details of these accessories are given in Appendix D.
Initiating Device Circuits
The Faraday 12503 Conventional Expansion Board provides four initiating device circuits. The IDCs can
be wired for Class B (Style B) operation or Class A (Style D) operation with the Faraday 12401A Class A
Adapter. Up to two 12503 boards may be used.
Addressable Device Circuits
The Faraday 12522 Loop Driver Board with the Faraday 12505 Loop/Signal Expansion board provides
two additional addressable device circuits. Only one 12505 board may be used.
Faraday Addressable Devices:
Each addressable device circuit drives up to 60 addressable devices, detectors and/or modules.
System Sensor Devices:
Each addressable device circuit drives up to 99 addressable sensors and 99 addressable
modules.
Notification Appliance Circuits
The Faraday 12503 Conventional Expansion Board provides two additional notification appliance circuits
(NACs). Each circuit can be selected to give continuous output or one of eight sounding patterns
available in the control unit. There is also asystem coder capable of zone coded operation. All of the
NACs are power limited and can be wired for Class B (Style Y) operation or Class A (Style Z) operation
with the Faraday 12401A Class A Adapter. Up to two 12503 boards may be used.
The Faraday 12505 Loop/Signal Expansion board provides four additional notification appliance circuits
(NACs). Each circuit can be selected to give continuous output or one of eight sounding patterns
available in the control unit. There is also a system coder capable of zone coded operation. All of the
NACs are power limited and can be wired for Class B (Style Y) operation or Class A (Style Z) operation
with the Faraday 12504 Class A Adapter. Only one 12505 board may be used.
Isolated Printer Connection
The Faraday 12511 Serial Isolation Board will convert the RS232 printer connection to an isolated output.
User Programmable Relays
The Faraday 12402 Alarm Relay Board provides 12 dry relay contacts. These relay may be programmed
to activate from a device or zone. The relay contacts are form C and are rated 1A@30VDC or
0.5A@30VAC, resistive.
Digital Alarm Communicator
The Faraday 12410 Digital Communicator Cable may be used with the Faraday 15128 Digital Alarm
Communicator. This will allow control unit status data to be sent to a remote receiving station.
Digital Alarm Communicator
The Faraday 12513 DACT (Digital Alarm Communicator Transmitter) Expansion Module provides
telephone line connections for communication with a DACR (Digital Alarm Communicator Receiver). The
DACT Expansion Module options are set through the control unit programming sequence.

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I II-4
BATTERY SETS
The 12530/15240 control unit is designed to use only sealed lead-acid or equivalent batteries for back-up
power. Attaching a close-coupled battery box, if required, may use battery sets beyond the physical
capacity of the enclosure (10 AH).
AUXILIARY MODULES
Remote LCD Annunciator
The Faraday 12506 remote LCD annunciator consists of a backlit 80 character LCD alphanumeric
display, 4 menu buttons, 4 dedicated buttons for operator interaction, 6 LED indicators, and a security
key-switch. The display and controls on the annunciator are the same as those on the front of the control
unit, including a key-switch for security. The back light operates only when the data are being accessed,
to conserve power.
Up to sixteen annunciators may be addressed by the communications circuit, but some may require
12408 auxiliary power supplies, depending on the total accessory power loading.
Serial Relay Unit and Serial Relay Extender
The Faraday 12507 includes a processor board and a relay board. The processor board receives
commands from the control unit for activating the relays and transmits supervision and control functions
to the control unit. The processor board can control up to 3 relay boards. Each relay board provides 8
relays with form C contacts. The control unit can address up to 8 Serial Relay Units and/or Serial
Annunciator Units. Faraday 12408 auxiliary power supplies will be required to power units beyond the
control unit capability.
Serial Annunciator Unit and Serial Annunciator Extender
The Faraday 12509 includes a processor board and an annunciator driver board. The processor board
receives commands from the control unit for activating the outputs and transmits supervision and control
functions to the control unit. The processor board can control up to 4 annunciator driver boards. Each
driver board provides 16 supervised outputs for LEDs or incandescent lamps. The control unit can
address up to 8 Serial Relay Units and/or Serial Annunciator Units. 12408 auxiliary power supplies will
be required to power units beyond the control unit capability.
Network Interface Board
The Faraday 12523 Network Interface Board provides an interface between the associated control unit
RS232 connection and an MPC-NET network. The Network Interface Board is powered from the control
unit auxiliary power output. For further installation instructions, see the MPC-NET manual P/N 447259.
Auxiliary Power Supplies
The Faraday 12408 Auxiliary Power Supply can be used to provide additional power for notification
appliance circuits. The 12408 has two 1.5A power-limited outputs and a trouble relay contact for
monitoring by the control unit.

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I II-5
ADDRESSABLE DEVICES
Faraday Addressable Detectors
The control unit processor sends the sensitivity and pre-alarm settings to the detectors and polls the
detectors as to their status. The detector determines normal, trouble, pre-alarm or alarm conditions and
relays the status to the control unit.
Variable Thresholds
The obscuration level for alarm can be adjusted from the control unit on a permanent or time-variable
basis. This facility also means that the control unit can display information on individual points for
maintenance or service.
Operator Alerts
The control unit can trigger an alarm or trouble automatically on the occurrence of a number of conditions
of the detector. These include:
•Maintenance alert
•Pre-alarm alert
•No response
•Incorrect response
Other Faraday Addressable Devices
Heat Detectors
Addressable heat sensing detectors may be intermixed on the circuit for locations where heat sensing
may be the most effective detection mode. The heat detectors may be programmed, through the control
unit, for rate of rise operation.
Addressable Modules (Monitor and Control)
In addition to detectors, the circuit can communicate with addressable modules, allowing initiating devices
or notification appliances with local power sources, and supervising the power sources.
Manual Stations
Addressable manual stations may be intermixed on the circuit with proper response programmed into the
control unit.
System Sensor Addressable/Analog Sensors
Since an analog fire sensor is essentially a transducer rather than a warning device, all of the operating
controls are included in the control unit processor program. The control unit interprets the pulse widths
from the sensor and determines normal, trouble or alarm conditions.
Variable Thresholds
The obscuration level for alarm can be adjusted from the control unit on a permanent or time-variable
basis. This facility also means that the control unit can display information on individual points for
maintenance or service. These displays include:

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I II-6
•Status
•Current % obscuration for smoke sensors
Operator Alerts
The control unit can trigger an alarm or trouble automatically on the occurrence of a number of conditions
of the sensor devices. These include:
•Maintenance alert
•Pre-alarm alert
•No response
•Incorrect response
Other System Sensor Addressable Devices
Heat Sensors
Compatible heat sensing addressable devices may be intermixed on the circuit for locations where heat
sensing may be the most effective detection mode.
Addressable Modules (Monitor and Control)
In addition to sensors, the circuit can communicate with addressable modules, allowing initiating devices
or notification appliances with local power sources, and supervising the power sources.
Manual Stations
Single and dual-stage manual stations with monitor modules may be intermixed on the circuit with proper
response programmed into the control unit. For fastest response, manual stations should be connected
so that their address is 1-9.
PROCESSOR CONTROLLED OUTPUT ZONES
While the notification appliance circuits are essentially hardware circuits, the fact that the outputs are
commanded and controlled by the processor does provide more versatility than in a total hardware
system. All functional selections are included in the control unit programming process.
Output Sounding Patterns
The notification appliance circuits are operable in different sounding patterns. Any circuit is selectable to
any of eight software-generated patterns or continuous sounding. For convenience, three of the patterns
are preprogrammed for March Time, Temporal, and Californian patterns.
Control of Audible Silencing
It is possible to select an “auto-silence” mode, adjustable from 0 to 255 minutes. Each notification
appliance circuit programmed for alarm silence sequence, will be silenced upon time-out of the auto-
silence timer. The alarm silenced LED will flash, indicating the auto-silence time-out.
Audible Silence Inhibit
In addition to designation of waterflow zones, the entire control unit may be programmed to inhibit audible
silence for 0, 1, 3, or 6 minutes from the last alarm. System reset may also be inhibited.

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I II-7
EVENT HISTORY
The control unit includes a non-volatile memory recording up to 2000 system events. Identified alarm,
trouble, supervisory trouble, and other significant events will be recorded along with the date and time of
occurrence, and can be inspected by operating front panel push buttons.
Events recorded in the history are:
•Alarm, Trouble, or Supervisory conditions.
•Drill, Tornado, Recall and General Alarm.
•Activation of NACs or modules used for sounders or strobes.
•Unit used for command functions. (Silence, acknowledge, reset, etc.)
•PAS_INHIBIT switch activation.
•Alarm silence (manual and automatic).
•System reset.
•Power up.
•Entry to Programmer Mode.
•Secondary configuration edited.
•Validity check on backup configuration. (Errors detected or no errors detected)
•Running of comparison function. (Same or different)
•Replacement of primary configuration.
•Execution of Auto-program.
•Exit from Programmer Mode.
•System time or date change.
•Input point disable/enable.
•Start and stop ofwalk test.
•Expiration of Walk Test Timer.
•Expiration of re-ring timer.
•Alarm/trouble/supervisory Acknowledgment.
•Trouble/supervisory restored to normal.
•Alarm verification counter rollover.
•Pre-alarm activation.
•Pre-alarm acknowledgment/restore.
•Alarm of zone with no outputs.
•Activation of points defined for logging.
•Sensor maintenance alerts

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I II-8
GENERAL DESIGN FEATURES
Environmental
All hardware is suitable for use in an interior or protected location.
Power Limiting
The city tie circuitry is not power limited when programmed for Local Energy or Shunt operation. The AC
power and battery wiring are not power limited. All other circuits leaving the control unit are power limited,
provided the proper installation rules are maintained.
Ground Fault Detection
The control unit provides ground fault detection and a ground fault will trigger the common fault buzzer
and system trouble LED. There are separate LEDs on the main termination board to indicate positive and
negative ground faults.
Transient Protection
Transient protection devices are provided where needed to meet the requirements of UL864.
Security Functions
Processor control and addressing allow inclusion of several functions to assure security of the system.
Multi-level password protection of programming functions prevents unauthorized configuration changes.
Device type supervision: If the type reported by an addressable sensor or module, does not agree with
the configuration, the system reports a trouble.
Device address supervision: The system checks that all configured devices on the addressable device
circuit responds to an address poll. If a configured device is missing, the system reports a trouble. The
system also polls unused addresses periodically. If a device responds to such a poll of a non-configured
device, the system reports a trouble. Two devices addressed the same also cause a trouble to be
reported.
The RS485 devices also are checked for no response and un-programmed address responses.
REGULATORY STANDARDS
The 12530/12540 control unit meets the requirements of industry and government regulatory agencies as
noted.
Underwriters Laboratories
The 12530/12540 Fire Alarm control unit is listed under UL Standard 864 for compliance to NFPA
Standard 72 for fire service

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I II-9
GENERAL SPECIFICATIONS
Operating specifications for the 12530/12540 are as follows:
Environmental
•Operating temperature
32 -120°F (0 -49°C)
•Relative humidity
Up to 85% @ 86°F (30°C)
Primary Supply
•Primary Input Voltage:
120 VAC (50/60 Hz) nominal (12530/12540-120)
240 VAC (50/60 Hz) nominal (12530/12540-240)
•Maximum primary input current:
3.0A at 120 VAC
1.5A at 240 VAC
Secondary and Trouble Power Supply
•24 volt lead-acid battery set:
•Maximum Charge Voltage: 28.0 VDC
•Maximum Charge Current: 2.75 A
•Maximum Input Current: 4.66A
•Battery capacity: 7-38 A.H. (over 10 A.H. requires separate enclosure)
Auxiliary Power Outputs
•Current:
0.9 amp maximum for remote annunciators
0.9 amp maximum for auxiliary power outputs, DACT power and option boards
•Non-Resettable Power Outputs
Power limited
Voltage: 24 VDC nominal
Ripple: 1.5 VAC maximum
•Resettable Power Output
Power limited
Voltage: 24 VDC nominal
Ripple: 1.5 VAC maximum
Addressable Device Circuits
•Power limited
•Supervised
•Voltage: 24 VDC nominal
•Maximum Current (shorted): 0.25A
•Maximum wire loop resistance: 20 ohms/line
Faraday Addressable Devices:
•Two Style 4 or 6 circuits
•Expandable to four Style 4 or 6 circuits with optional boards
•60 detectors and modules max.
System Sensor Devices:
•Two Style 4, 6 or 7 circuits
•Expandable to four Style 4, 6 or 7 circuits with optional boards
•99 sensors (smoke, heat) max
•99 monitor and control modules max.

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I II-10
Notification Appliance Circuits
•Four Class B, Style Y circuits
Convertible to Class A, Style Z circuits with optional adapter
•Expandable to 12 Class B, Style Y circuits
Convertible to Class A, Style Z circuits with optional adapter
•Power limited
•Supervised
•Maximum Standby Current: 3.4mA
•Alarm Voltage: 24 VDC nominal
•Maximum Alarm Current: 1.5 A
•Maximum Ripple: 1.5 VAC
•Maximum Loop Drop Voltage: 1.0 VDC
Status Relays
Includes alarm, supervisory, trouble, power failure and processor failure.
•Contact Rating:
2A, 30 VDC maximum, resistive
0.5A, 30 VDC maximum, resistive
•Contact Type:
Form “A” or “B” Contact for processor failure relay (jumper selected)
Form “C” Contact for alarm, supervisory, trouble and power failure relays.
RS485 Communications Circuit
•Power limited
•Supervised
•Voltage: 24 VDC nominal
•Current:
0.9 amp maximum for remote annunciators
•Maximum wire loop resistance: 25 ohms/line
•Communications: RS485
City Tie
•Reverse Polarity: Alarm with Trouble and/or Supervisory operation
Power limited
Supervised by receiver for short or open circuit.
Supervised by control unit for grounded circuit.
Voltage: 24 VDC nominal
Current: 0.014A maximum
Ripple: 1.5 VAC maximum
•Local Energy
Not power limited
Supervised for open or grounded circuit by control unit.
Voltage: 24 VDC nominal
Standby Current: 0.014A maximum
Alarm Current: 0.510A maximum
Ripple: 1.5 VAC maximum
Maximum wire loop resistance: 30 ohms
Trip coil impedance: 14.5 ohms
•Shunt
Not power limited
Contact Rating: 0.150A, 30VDC maximum, resistive
Maximum wire loop resistance: 6 ohms

12530/12540 OWNER'S MANUAL
P/N 447203 Issue I II-11
RS232 Printer Output
•Power limited
•Not supervised
•Voltage Range: -15 VDC to +15 VDC
•Maximum Current (shorted): 0.050A
•Baud Rate: 4800
•Maximum wire loop resistance: 25 ohms
Initiating Device Circuits (Optional board P/N 12503)
•Expandable in groups of 4 to 8 Class B, Style B circuits with optional expansion boards
Convertible to Class A, Style D circuits with optional adapter
•Power limited
•Supervised
•Standby Voltage Range: 16-27 VDC
•Maximum Standby Current: 10.3 mA
•Maximum Smoke Detector Current: 3 mA
•Maximum Alarm Current: 48 mA
•Maximum Ripple: 1.5 VAC
•Maximum Wire Loop Resistance: 100 ohms
DACT Expansion Module (Optional module P/N 12513)
•Power limited
•Supervised for short or open circuit
•Maximum Voltage: 60 VDC
•Maximum Current (shorted): 0.100 A
Alarm Relay Board (Optional board P/N 12402)
•Power limited
•Contact Rating:
1 A, 30VDC maximum, resistive
0.5 A, 30VAC maximum, resistive
This manual suits for next models
4
Table of contents