12.A4
Utility Model - IB12A4 - 02/22
Finder S.p.A. con unico socio
10040 ALMESE (TO) - ITALY
ENGLISH
12.A4 DIGITAL ASTRO TIME SWITCH with ON/OFF CONTACT
OUTPUT and (0-10 V or PWM) SIGNAL OUTPUT
The 0-10 V / PWM output signal can be programmed to ramp up or
down to the programmed output value
, at a predetermined rate
of change (PI)
“Switching” times are easily set using either the seasonally variable
times of the Astro SUNSET and Astro SUNRISE functions, or the specic,
xed time-of-day of the TIMED function - or any combination of all three.
DISPLAY INDICATORS
ASetting
BDays of the week (1=Mon...7=Sun)
CHoliday program
DPermanent Manual Mode (active)
EChannel A functions:
Astro ON, Astro OFF, Pulse (TIMED event + 0-10 V / PWM)
FDay - Advanced/Retarded - % output signal
G
Time, postcode (CP), percentage change in output power per
second (PI), year (Y), day (D), month (M), hours (H), minutes (M),
Daylight saving ON/OFF, Holiday program [Start: D (day), M (month).
Finish: D (day), M (month)] PIN, exit menu (END)
H- Low battery (with power supply)
- Time switch without external power (powered by battery)
ICancel
L
Event memory location (max 50) - Country, Leading two characters of CP,
PI, [Coor: geographic coordinates in degrees: N(North) / S(South),
E(East) / W(West), TZ(Time zone)], Y(year), D(day), M(month), H(hour),
M(minutes), Daylight saving ON/OFF (EU: Europe, BR: Brazil, MX: Mexico)
[holiday program: Start: day(D), month(M); Finish: day(D), month(M)]
MSaved event
WIRING DIAGRAM: output 0-10V
WIRING DIAGRAM: output PWM
SETTINGS (examples)
ABack-lit display (only when externally powered)
4a Setting: Country (IT), CP (leading two characters of CP), percentage
change in output power per second (PI), year(Y), day(D),month(M),
hour(H), minutes(M), Daylight saving ON/OFF (EU: Europe, BR: Brazil,
MX: Mexico), PIN, exit menu (END)
4b Holiday program
(Start: day/month. Finish: day/month), PIN, exit menu (END)
4c Setup by geographic coordinates. Start at 4a, select Country IT
or CP 00 stage, scroll down with . Continue by setting the
coordinates and time zone. Latitude: North (N) - South (S).
Longitude: East (E) - West (W). Time zone(TZ)
F
5
4A
1
2
3
4
PROGRAMMING (examples)
ABack-lit display (only when externally powered)
BNP: New Programming event
C01, 02..: event memory location (Max 50)
5.1 ASTRO ON: Signies programming the Astro SUNSET conditions -
advance/retard D- applicable days E- required % output setting
(0-10V / PWM) F
5.2 ASTRO OFF: Signies programing the Astro SUNRISE conditions -
advance/retard D- applicable days E- required % output setting
(0-10V / PWM) F
5.3 PULSE: Signies programing the conditions for a TIMED event -
time of event G- applicable days E- required % output setting
(0-10V / PWM) F
DAdvance or retard from the Astro time (up to 90 minutes)
ESet applicable day(s) of the week (1 = Mon ... 7 = Sun)
FSet % value of the output signal (0-10 V / PWM)
GSet time of day for TIMED event (00:00 ... 23:59)
MANUAL MODE (Manually change the current output value)
Pushing the joystick towards (6a) or towards (6b) it is possible
to modify the value of the output signal between 1% and 99%.
Note: the output contact (11-14) will be open for values below 10%,
and will be closed for values above 10%.
NB: This setting will remain in force until the next programmed event.
PERMANENT MANUAL MODE
By activating the permanent manual mode 7a, the program of events
will be ignored (whilst the current signal output level is maintained).
De-activating the mode 7b, and the device returns to follow the program
of events, responding to the next occurring event.
DELETION of all programmed events
ABack-lit display (only when externally powered)
DELETION of a single programmed event
ABack-lit display (only when externally powered)
NOTE
- Battery replacement: BATTERY CR 2032 (LiMnO2) 3V, 230mAh.
Complies with Article 11, EU directive 2006/66/CE.
Dispose of batteries according to local regulations
- Back-lit display (only when externally powered)
- ASTRO times vary over the year
- PWM 0% = output contact open
- (0-10 V) ≤9% = output contact open
- Maximum cable length: 20 m (0-10 V) - 10 m (PWM)
- PWM: setting 0-99% - resolution 1%
- 0-10 V: setting 0-99% - resolution 1%
5
6
7
8
9