|8 QS204210 Rev C
MOUNTING ECHOPOD®
The sensor should always be mounted perpendicular to the liquid surface using the provided Viton®mounting
gasket. Make sure that there are no restrictions or obstacles in the path of the acoustic signal. For further
mounting information, please refer to the EchoPod®manual and instruction video located at flowline.com.
EchoPod®has 1” NPT or G threads and requires care in fitting selection and mounting to reduce any coupling of the
ultrasonic signal to the mounting structure. The below fittings are recommended.
Installation in existing 2” fittings:
Use a LM52-1400 2” thread x 1” thread adapter or a LM52-1410 2”
slip x 1” thread adapter. Adapters with an air gap around the 1 inch
threads are recommended.
Installation in plastic tanks (use one of the following):
Use a 1” bulkhead fitting, such as the LM52-1890 bulkhead fitting.
Use a larger bulkhead fitting, such as the LM52-2890 with a
reducer bushing such as the LM52-1400.
Weld a plastic 1” half coupling to the tank top.
Installation in metal tanks (use one of the following):
Use the LM52-1890 bulkhead fittings.
Use a flange with a 1” riser, such as the LM52-1850 (where the
thread is above the plane of the flange). Do not use a blind
flange with a tapped 1” thread.
Use a larger flange with a 2” thread and add a reducer bushing
such as the LM52-1400.
Note: While installations directly into a 1”metal fitting are not
recommended, acceptable results may be obtained if the 1” fitting
is a half coupling in form and the outer diameter of the coupler is
tightly wrapped with vinyl tape.
Installation in open tanks and sumps:
1) Use Flowline's LM50-1001-1 side mount bracket.
Note: The Side Mount Bracket (LM50 series) is not
designed for use with stand pipes or as a method to secure
stand pipes. There are too few threads to properly hold the
sensor and the stand pipe.
LM52-1400
LM52-1410
LM52-2890
LM52-1850
LM50-1001