
070.750-IOM2 (JUN 22)
Page 17
HPS 273 and 407 Rotary Screw Compressor
Operation
Operation Before starting up the compressor
Before the start-up, complete the prestart check. See
Prestart checklist in the Forms section.
Calibrating the linear transmitter
A critical step in the start-up procedure is calibrating the
linear transmitters to determine slide valve and slide stop
position and travel. See Figure 10 for linear transmitter.
While it is possible to calibrate the linear transmitters on
the compressor unit, it cannot be done automatically by
the unit controller. The transmitters are electronic devices
that use a 4 mA to 20 mA signal; but because the trans-
mitters are used in a variety of compressor models the
operating range is usually narrowed to 6 mA to 10 mA,
where 6 mA corresponds to the minimum endpoint posi-
tion (0% slide valve or 0% slide stop position) and 10 mA
corresponds to the maximum endpoint position (100%
slide valve or 100% slide stop position). In many cases the
high-pressure compressors is mounted on units using heat
trace and insulation, which can affect the calibration and
operation of the linear transmitters. Calibrate the linear
transmitters with the unit heat trace on and insulation
applied.
Note: The slide valve travel is relatively short because of
the low rotor L/D ratios. As a result, it is important
to use an amp meter during the calibration process
that has a high resolution readout, minimum of
three to four decimal places.
If exposing the mounted transmitter to high temperatures,
a split sensor or transmitter is available. The sensor is in-
stalled under the insulation and exposed to the heat while
the transmitter, connected by a cable, is mounted outside
the insulation and exposed to the ambient air.
Determining the slide valve and slide stop posi-
tion and travel
The slide valve and slide stop travel check is necessary
to define the absolute end positions (0% to 100%) of the
slide valve and slide stop’s movements and is applicable
to all three Vi options. The calibration process is done
automatically by controller, which subsequently uses these
measurements to calculate the Vi and capacity of the
compressor.
The risk of over-compression, and subsequent damage
to the compressor, makes the calibration process of the
linear transmitter and slide valve/stop even more critical
for applications involving high-pressure compressors.
For example, operating a HPS compressor that has a 2.2 to
5.0 Vi with a suction pressure of 10.3 bar (400 psig) at full
load and the maximum slide stop position generates nearly
206.8 bar (3,000 psig) discharge pressure, well above
the design working pressure of the compressor. Operat-
ing the compressor at a high-pressure differential, and
in the unloaded condition, may cause the compressor to
fill with oil and cause slugging. These examples underline
the need to make compressor selections at the lowest Vi
range necessary to achieve the optimal Vi for the system’s
operating conditions. It also demonstrates why not to use
a variable-speed drive motor and the slide valve position
to regulate the compressor load at the same time. Frick
suggests performing the calibration check daily.
Operation and start-up instructions
The Frick HPS 273 and 407 rotary screw compressors are
components in an integrated system. Because of this, the
compressor operation requires some specic conditions to
ensure trouble-free running.
The information in this section provides logical step by
step instructions to
correct
ly start up and operate the HPS
rotary screw compressor in your unit. Only matters that
may inuence the
correct
operation of the Frick HPS 273
and 407 compressors are included.
WARNING
The compression process creates noise and operat-
ing screw compressors are loud. Wear the correct
hearing protection when near the compressor during
operation. If people are expected to be in the vicinity
of the running compressor for extended time periods,
provide warnings.
Note: You must read the following subsections and ensure
that you understand the information before at-
tempting to start or operate the unit.
Ambient temperature effect on
compressor operation
Warning
Everything must be heat traced and insulated, even the
compressor.
Warning
When the ambient temperature is below the satura-
tion temperature that the compressor is operating at,
condensing may occur, which may result in damage to
the compressor.
Pay particular attention to the potential for condensa-
tion in units operating with high-pressure compressors.
Their applications often involve conditions where the
ambient temperature is below the saturated tempera-
ture that it is operating at. Additional precautions to
prevent condensation during start up, shutdown, and
when the unit is at standstill are noted in the following
section.
Insulate the package oil separators, the oil piping, and the
oil lter as a minimum requirement. This can preserve the
heat generated by the oil heaters, prevent condensation,
and secure lubrication at start-up.
Always insulate the oil separator for heat pump and fuel
gas compression applications. It is often necessary to
insulate the complete suction line for heat pumps in order
to prevent condensation and possible slugging. In these
cases, heating wires are necessary.
With an automated valve, regulate oil ow to the main
oil port being used (SM-2 or SM-1) in order to continu-
ously achieve the highest possible discharge temperature
needed.