
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
Page 18
SETPOINTS DISPLAY, Page 1B:
Dead Band - This is a + (plus) or - (minus) value above or
below the setpoint at which the compressor will neither load
nor unload. A dead band of 1 is the default value. It is ad-
justable between .5 lb to 5 lb in increments of .5.The [Step]
key is used to select this setpoint; then press the [Change]
key to toggle through the selections.
Proportional Band - This setpoint is used to determine the
amount of time the load/unload solenoid is energized, ac-
cording to how far from the setpoint the actual control pres-
sure is. The smaller the number, the longer a load/unload
signal will be sent; 10% is the default value. Selections are
2, 5, 10, 15, 20, or 25%.The [Step] key is used to select this
setpoint; then press the [Change] key to toggle through the
selections.
CycleTime - Cycle time is the amount of time between the
beginning of each load/unload response. Ten seconds is
the default value.“Cycle Time”is adjustable between 5 and
30 seconds in 5 second intervals.The [Step] key is used to
select a setpoint; then press the [Change] key to toggle
through the selections.
Low % FLA - This setpoint is used to determine if the cou-
pling has broken; 20% is the default value. It is adjustable
from 0 to 100% FLA.Use the [Step] key to select a setpoint;
then enter the desired setpoint and press the [Enter] key.
SETPOINTS DISPLAY, Page 2:
MLC STOP LD - The Motor Load Control Stop Load, re-
ported as a percentage of the motor, full-load amps (FLA),
will prevent the compressor capacity control pistons from
loading when the setpoint is equaled or exceeded. NOTE:
Consult motor manufacturer for recommended setpoint.
MLC FORCE ULD - The motor Load Control Force Unload,
reported as a percentage of the motor,full-load amps (FLA),
will force the compressor to unload until the motor, full-load
amps (FLA) fall within 1% of the setpoint or lower. NOTE:
Consult motor manufacturer for recommended setpoint.
HI DISCH CUTOUT -The High Discharge Pressure Cutout,
reported inpounds per square inch gauge(g), willshut down
the compressor if the discharge pressure equals or exceeds
this setpoint.
HI DISCH ALARM - The High Discharge Pressure Alarm,
reported in pounds per square inch gauge (g) will trigger a
prealarm if the discharge pressure equals or exceeds this
setpoint.
CT FACTOR - The Current Transformer Factor records the
proper current transformer factor to match the compressor
motor FLA rating to the current transformer primary rating.
The CTF factor is programmable and its correct value is
determined by the following formula:
1024 x FLA (Full Load Amps *)
CTF = 10x CT (Current Transformer Primary Amps **)
* See motor nameplate.
** See CT located in starter panel.
EXAMPLE: FLA = 230 Amps
CT = 300 (300:5)
1024 x 230
CTF = = 78 (Round to whole number)
10 x 300
OPERATION
AUX 1 and AUX 2 - May be configured for either an alarm or
shutdown and with either a normally closed (NC) or nor-
mally open (NO) contact.
TO CHANGETHE ADJUSTABLE SETPOINTS:
Adjustable Setpoints are stored in RAM (random access
memory) and are easily changed in the field.
Adjustable Setpoints are lost if
power is interrupted and the bat-
tery is not fully charged.To facili-
tate reentry, we suggest that a list of Adjustable
Setpoints be affixed to one end of the microprocessor
cabinet for reference.
NOTE:The followingprocedurealso applies to the chang-
ing of the Security, Setback, and Auto Cycle display
setpoints.
1. Press the [CHANGE] key to rotate the display to the Ad-
justable Setpoints display.
2. Press the [STEP] key to move or step a set of flashing
bracketsthroughthe varioussetpoints.A setpointis selected
for change or update when it is enclosed by the flashing
brackets.
NOTE:The DAY indicator, itself,will flash when selected
for change or update.
3. Having selected the setpoint to be changed, the [NU-
MERIC KEYPAD] may be used to enter the new setpoint.
NOTE: All digits must be entered, including zeros. For
example, (01.0).
NOTE:The DAY,AUX 1,and AUX 2 setpoints,once selected,
are changed or updated by pressing the [CHANGE] key.
NOTE:Certain setpoints may be reported in either pounds
per square inch gauge (g) or inches of mercury (hg).To
toggle between (g) and (hg),having selected the setpoint,
press the [+/-] key to toggle between (g) and (hg).
4. In the event that an incorrect setpoint is keyed in com-
pletely or partially, press the [CLEAR] key to restore the
original setpoint. Pressing the [CLEAR] key a second time
will eliminate the flashing brackets.
5. Having keyed the desired setpoint, press the [ENTER]
key.The new setpoint will be entered and the flashing brack-
ets will move or step to the next setpoint.
NOTE: A setpoint entry outside the parameters of the
Adjustable Setpoint display will be refused and the origi-
nal Adjustable setpoint will be restored.
NOTE: To clear any time values [STEP] to the desired
setpoint, press [CHANGE] and then press [CLEAR].
HOWTO DETERMINE
ADJUSTABLE SETPOINTS:
Adjustable Setpoints should reflect values compatible with
normal system operation.Too high a Low Suction Pressure
Alarm setpoint may cause nuisance prealarms. Similarly,
cutout setpoints should not fall within what are considered
normal plant operation.As a rule of thumb, set the Low Suc-
tion Pressure Alarm 5 PSIG lower than the lowest normal
suction pressure.The Low Suction Pressure Cutout should
be 5 to 10 PSIG lower than the Low Suction Pressure Alarm
setpoint.