
Soloclim
13
EN
Electrical installation
Soloclim is equipped with a 1,5 metre long cord with plug
for connection to an earthed power socket. The power
supply should be protected by a circuit breaker 1P+N,
6A, type C. If the cable is damaged it must be replaced
by a qualied service technician. The installation, which
should be preceded by an isolator switch with a contact
separation of at least 3 mm, should only be wired by a
competent electrician and in accordance with the latest
edition of IEE wiring regulations.
pening the unit ig
The unit shold not be opened by any unauthorised
personnel. Opening the unit is only necessary for adapting
it to a high wall installation or to access the terminal block.
1. Switch off the power and disconnect the unit.
2. Remove the upper grill by lifting it straight up starting
with the front edge.
3. Remove the lter by pulling it slightly towards the front,
then lifting it straight up.
4. Unscrew the two screws securing the front panel and
remove the panel. Note! The display is protected by
double-sided tape on the inside of the front.
Drainage ig
The unit is supplied with a drip tray for collecting the
condensation which should be channelled to a suitable
place for drainage. The drip tray is tted with a 0,6 m long
drainage tube with a safety drain. Size and position are
shown on the drilling template and g.8.
1. Remove the nozzle from drainage tube, or replace the
tube with a longer drainage tube. Be careful not to
squeeze the tube.
2. The whole tube must be coated with anti-condensation
insulation indoors and in the wall.
3. Direct it towards a suitable location for drainage and
keep a downward slope of minimum 3%.
4. Insulate junction points.
If no external drainage is prepared, do not remove the
nozzle from the drainage tube. It is possible to empty
the drip tray using the safety drain. When the drip tray is
full, the unit will stop and error code "OF" appears on the
display. See trouble shooting.
Collecting condensation in a container Fig.8b.
If the condensation is channelled to a water tank, or
similar, it should not be hermetically sealed. Prevent the
end of the drainage tube from immerse in the water.
Open drain Fig.8b.
If the condensation is not collected, check that the
expelled water does not cause any damage or problems
to people or objects. The water could freeze if the outdoor
temperatures are below zero, thus creating a hazard. In
this case, appropriate barriers should be installed in order
to prevent people from approaching the area.
igh wall installation
The unit can be installed near the oor or higher up on
the wall. The factory setting is made for low installation,
with the air ow directed upwards. High wall installation
is recommended when the unit is to be used for cooling
only. The bottom plate SCSFH1 is necessary for high wall
installation (ordered separately).
Adjustment of deector (changing air ow direc-
tion) Fig.11.
1. Switch off the power and disconnect the unit.
2. Remove grille and front panel (see Opening the unit).
3. Position the bottom plate SCSFH1 and x with the
screws provided.
4. Remove the xing screws of the right support bracket
for the air deector.
5. Rotate the bracket 180°.
6. Reinstall the bracket.
7. Reassemble the front panel and grille.
8. Proceed with the settings on the control panel.
After adjusting the air deector direction, the
settings on the control panel must be changed.
9. Press the deector key on the display for 10 seconds.
10. The symbol "dn" appears (low wall) ashing.
11. Press the deector key again.
12. The symbol "uP" appears on the display (high wall).
13. Wait 2 seconds until the new setting is memorised.
For the unit to work properly, the settings on the control
panel must be changed each time the orientation of air
deector is changed.
7. Verify that the bracket ts securely into the interlocking
points on the unit.
8. Fix the anchor bracket to the wall.
For easier connections, a spacer can be used to keep the
lower part of the unit away from the wall.
Access to the terminal block Fig.10.
Access to the terminal block is only necessary when
replacing the wired cable or when using the CP presence
contact.
1. Switch off the power and disconnect the unit.
2. Remove grille and front panel (see Opening the unit).
3. Unscrew the screws of the terminal block cover and
remove it.
It is possible to remove the unit's cable with plug and
connect the power supply directly to the terminal block.
This is recommended for high wall installation.
4. Disconnect the power cord from the terminal block.
5. Connect the power supply, checking that it has
a suitable earth connection and dimensionning
(minimum cable area: 1,5 mm2). Minimum cable area
for SC23DCI1000N is 2,5 mm2.
CP presence contact connection Fig.10.
When the CP contact opens (very low voltage, connected
to a potential free contact) the unit switches to stand-by
mode and CP appears on the display. This contact enables
the connection of an external device such as: prescence
sensor, window opening contact, remote on/off, activation
badge. A double insulation cable should be used. The CP
contact should always be used for the SC23DCI1000N to
avoid overheating. See wiring diagrams.