Frico Pamir 3200 User manual

Pamir 3200
....9
EN ....12
FR
Original instructions

Pamir 3200
2
Minimum distances / Distances minimales
min 60
Fig. 1
1045 / 1555 / 2045
1068 / 1578 / 2068
256
10 458
167
min 500
99
min 500 min 500 167165
1045 / 1555 / 2045
1068 / 1578 / 2068
256
10 458
167
min 500
99
min 500 min 500 167165
2 m - PAF3220
1045 / 1555 / 2045
1068 / 1578 / 2068
256
10 458
167
min 500
99
min 500 min 500 167165
1 m / 1,5 m - PAF3210 / PAF3215

Pamir 3200
3
Fig. 2 Connections
Gland
Knock-out
Knock-out
Knock-out
ø17, 5ø17,5
ø32,5
ø25,5
ø20,5
ø1
7, 5
Gland
Gland
FC Frico Control
Gland = press-étoupe
Knock-out =opercule
PC board FC is integrated within the air
curtain at delivery.
La carte électronique de la régulation FC est
intégrée au rideau d’air à la livraison.
A B
C
Gland
Fig. 3: Open the unit / Ouvrir l’appareil

Pamir 3200
4
min 500 mm
Fig. 4: Mounting with wall brackets / Installation avec des consoles pour montage mural
PAF3210 2 pcs
PAF3215 2 pcs
PAF3220 3 pcs
A
BC
D
Ø8 (3x)
Ø7
Ø16
213
37
260
75 35 20

Pamir 3200
5
Accessories / Accssoires
Item
number
Type Used for Consists
of
Dimensions
25256 PA3PF15* PAF3210/3215 4 pcs
25257 PA3PF20* PAF3220 6 pcs
18056 PA34TR15* PAF3210/3215 4 pcs L: 1 m
18057 PA34TR20* PAF3220 6 pcs L: 1 m
19568 PA2P15* PAF3210/3215 2 pcs L: 1 m
19569 PA2P20* PAF3220 3 pcs L: 1 m
PA34TR
*) See separate manual. / Consultez la notice associée.
PA2PPA3PF

Pamir 3200
6
Item
number
Type Name Dimensions
74684
FCDA
FC Direct 89x89x26 mm (FCCF)
74685
FCSA
FC Smart 89x89x26 mm (FCCF)
74686
FCPA
FC Pro 89x89x26 mm (FCCF)
74687
FCBA
FC Building 89x89x26 mm (FCCF)
Control systems / Système de régulation
FCBC05/10/25
FCSC10/25
FCDC
FCTXRF
FCBC05FCDCFCCF
Item
number
Type Dimensions
74694
FCRTX
39x39x23 mm
74695
FCOTX
39x39x23 mm
74699
FCLAP
89x89x26 mm
17495
FCDC
74718
FCBC05 5 m
74719
FCBC10 10 m
74720
FCBC25 25 m
74721
FCSC10 10 m
74722
FCSC25 25 m
74703
FCTXRF for FC Smart, FC Pro
89x89x26 mm
Accessories / Accessoires
FCDA - FC Direct FCSA - FC Smart
FCPA - FC Pro FCBA - FC Building
FCLAP
See separate manual for FC. / Consultez la notice de FC.
FCBC10FCDCFCCF FCLAP
FCBC10FCDCFCCF FCLAP FCTXRF FCBC10FCDCFCCF FCBAP
FCSC10
FCRTX
FCSC10
FCOTX
FCBC10
The air curtain must be supplemented with a control system.
Un système de régulation doit être intégré au rideau d’air.

Pamir 3200
7
*1) Lowest/highest airow of totally 3 fan steps.
*2) Sound power (LWA) measurements according to ISO 27327-2: 2014, Installation type E.
*3) Sound pressure (LpA). Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area: 200
m². At lowest/highest airow.
*4) ∆t = temperature rise of passing air at maximum heat output and lowest/highest airow.
Item
number
Type Output
steps
[kW]
Airow*1
[m3/h]
∆t*4
[°C]
Sound
power*2
[dB(A)]
Sound
pressure*3
[dB(A)]
Motor
[W]
Amp.
motor
[A]
Voltage [V]
Amperage [A]
(heat)
Weight
[kg]
251417 PAF3210E08 3/5/8 1100/1750 22/13 72 46/57 168 0,65 400V3N~/11,6 31
251418 PAF3215E12 3,9/8/12 1700/2750 21/13 75 46/59 283 1,0 400V3N~/17,3 42
251419 PAF3220E16 6/10/16 2300/3500 22/13 76 50/60 366 1,3 400V3N~/23,1 59
3Electrical heat / Chauffage électrique - Pamir 3200 E (IP20)
Technical specications Voltage motor: 230V~
*1) Débit d’air mini/maxi de 3 étages de ventilation au total.
*2) Mesures de la puissance acoustique (LWA) selon la norme ISO 27327-2 : 2014, Installation de type E.
*3) Pression acoustique (LpA). Conditions : Distance de l’appareil : 5 mètres. Facteur directionnel : 2. Surface
d’absorption : 200 m². Au débit d’air minimal/maximal.
*4)∆t = augmentation de température sous un débit d’air mini / maxi et une puissance maximale.
Etages de puissance
Débit d'air
Puissance acoustique
Pression acoustique
Tension moteur
Intensité moteur
Tension/Intensité chauffage
Poids
=
=
=
=
=
=
=
=
Output steps [kW]
Airow*1[m3/h]
Sound power*2 [dB(A)]
Sound pressure*3 [dB(A)]
Voltage motor [V]
Amperage motor [A]
Voltage / Amperage heat
Weight [kg]

Pamir 3200
8
PAF3200 E
Wiring diagrams for control system in the FC manual.
Schémas de raccordement du système de régulation disponibles dans la notice du
système FC.
PAF3210E08
PAF3215E12
PAF3220E16
255058
C3 = l ow power
Over heat
cut-out
°C
Over heat
cut-out
°C
C1 = l ow power
C3 C1
C 4 = h i gh power C4 C2
L2L3 P EL 1 LN
NF2 F3F1H1 H2N
Heating
Trafo
Motor
B rown
M
~
Left motor
C
°
Blue
Run
B lack
Run
Ri ght motor
~
M
B rown
C
°
Blue
B lack
White
Blue
NMid c 1L o w b1L
B l ack
Red
Orange
Y el oow
Y el l ow
LowN L Mid
Blue
B l ack
Red
c 1b 1
Orange
White
Inlet sensor
O ut l et sens or
GND
0 -1 0 V
PWM
A la rm
Motor
I1 I2 O1O2
Sen s o r
A1 A2
GND
GND
B1B2 D1 D 2
ON
O FF
Termination
Actuator
2 4 VW T A
+12V
HI
LO
GND
+12V
HI
LO
BU S 1 BU S 2
E1 E2 - +
GND
FC BASEPC B T3
2m version only
L1L2L3 LPE N
230V IN
L
PE N
PE
C 2 = h i gh power
400V 3~ 400V 3N~
Uniquement PAFEC20

Pamir 3200
9
EN
Electrical installation
The installation, which should be preceded by
an isolator switch with a contact separation
of at least 3 mm, should only be wired by a
competent electrician and in accordance with
the latest edition of IEE wiring regulations.
The air curtain has an integrated PC board
which is connected to the selected external
control system FC. FC must be ordered
separately. The PC board is accessed via cable
glands on the top of the unit. See Fig. 2. FC is
supplied pre-programmed. Communication-
and sensor cables are connected to the PC
board.
Should more than one air curtain be
controlled by a single FC, an additional
communication cable FCBC per unit will be
required. See manual for FC.
The electrical connection is made on the top
of the unit. Pierce the gland with a screwdriver
before entering the cable. See Fig. 2. Control
(230V~) and power supply for heat (400V3~)
should be connected to a terminal block in the
terminal box. 2-metre and longer units require
dual power supplies. See dimension drawing
and wiring diagram.
The largest cable diameter for the terminal
block is 16 mm². The cable glands used must
meet the protection class requirements. In the
distribution board, it is to be indicated that ”the
air curtains can be supplied from more than
one connection”.
General Instructions
Read these instructions carefully prior to
installation and use. Keep this manual for
future reference.
The product may only be used as set out in
the assembly and operating instructions. The
guarantee is only valid should the product be used
in the manner intended and in accordance with
the instructions.
Application
Pamir 3200 is an air curtain with electrical
heating and a recommended installation height
of 3,2 m. Protection class: IP20.
Operation
Air is drawn in at the top of the unit and blown
downwards shielding the door opening and
minimizing heat loss. To achieve the optimum
curtain effect the unit must extend the full
width of the door opening.
The grille for directing the outlet air is
adjustable and is normally angled outwards to
achieve the best protection against incoming
air.
The eciency of the air curtain depends on
the air temperature, the pressure differencial
across the doorway and any wind load.
NOTE! Negative pressure in the building
considerably reduces the eciency of the air
curtain. The ventilation should therefore be
balanced.
Mounting
The air curtain is installed horizontally with
the outlet air grille facing downwards as close
to the door as possible. The product must be
mounted in such a way to allow future service
and maintenance. Minimum distance from
outlet to oor for electrically heated units is
1800 mm. For other minimum distances, see
g. 1
Mounting with wall brackets (g. 4)
1. Mount the brackets on the wall, see g.4A
and dimension drawing. If the wall is uneven
the brackets must be compensated for this.
2. Hook on the unit at the lower edge of the
brackets. (Fig.4B)
3. Bend the top of the console over the the unit
and slide the units screws along the rail into
the slots on the consoles. (Fig.4C) When the
bracket is bent once, it must be replaced if
bent back more than 45 °.
4. Lock the nuts against the brackets. (Fig.4D)
Horizontal mounting on the ceiling
Threaded rods, hanging brackets and ceiling
mounting brackets for ceiling mounting are
available as accessories, see accessories pages
and separate manuals.
[kW]
[V]
[mm2]
0 230V~ 1,5
PAF3210E08 8 400V3~ 2,5
PAF3215E12 12 400V3~ 4
PAF3220E16*18 400V3~ 2,5
8 400V3~ 2,5
Type Output Voltage Minimum
area*
Control
*1) 2 m units are connected with two power supplies.
*2) Dimensioning of external wiring shall comply with
applicable regulations and local deviations may occur.
Installation and operating instructions

Pamir 3200
10
EN
Temperature control
Temperature control of FC maintains the
exhaust temperature. Should the temperature
exceed the preset value, the overheating alarm
Maintenance
Since fan motors and other components are
maintenance-free, no maintenance other than
cleaning is necessary. The level of cleaning can
vary depending on local conditions. Undertake
cleaning at least twice a year. Inlet and exhaust
grilles, impeller and elements can be vacuum
cleaned or wiped using a damp cloth. Use a
brush when vacuuming to prevent damaging
sensitive parts. Avoid the use of strong alkaline
or acidic cleaning agents.
Start-up
When the unit is used for the rst time or after
a long period of non-use, smoke or an odour
may result from dust or dirt which has collected
on the element. This is completely normal and
disappears after a short time.
Adjustment of the air curtain and airow
The direction and speed of the airow should
be adjusted considering the load on the
opening. Pressure forces affect the airstream
and force it inwards towards the premises
(when the premises are heated and the
outdoor air is cold).
The airstream should, therefore, be directed
outwards to withstand the load. Generally
speaking, the higher the load, the greater the
angle required.
Basic setting fan speed
The fan speed when the door is open is
set using the control. Note that the airow
direction and the fan speed may need ne
adjustment depending on the loading of the
door.
Service, repairs and maintenance
For all service, repair and maintenance rst
carry out the following:
1. Disconnect the power supply.
2. The front hatch is removed by removing the
screws on the top of the unit and then detach
the bent edge at the bottom. (Fig.3)
3. After the service, repair and maintenance
reattach the front hatch. Place the hatch at
the lower edge with the bent edge and fasten
on top with screws.
Note that when carrying out work where the
end is removed, the outlet grille also detaches.
will activate. For more information see the FC
manual.
Overheating
The air curtain unit with electrical heating is
equipped with an overheat protection. If it is
deployed due to overheating, reset as follows:
1. Disconnect the power supply with the isolator
switch.
2. Determine the cause of overheating and
rectify the fault.
3. Remove the front hatch.
4. Press the red button located inside the air
curtain unit, at the inner gable of the terminal
box.
5. Reattach the front hatch and connect the unit
again.
All motors are equipped with an integral
thermal safety cut-out. This will operate,
stopping the air curtain should the motor
temperature rise too high. The cut-out
will automatically reset when the motor
temperature has returned to within the motor’s
operating limits.
Replacing the PC board
1. The PC board is located in the terminal box.
Fig. 2
2. Mark and disconnect the cables to the PC
board.
3. Remove the screws securing the board and
lift out.
4. Install the new PC board as above in reverse
order.
Replacing heating elements/heating
package (E)
1. Mark and disconnect the cables to the
heating elements/package.
2. Remove the mounting screws securing the
heating elements/package in the unit and lift
the heating elements/package out.
3. Install the new heating elements/package in
reverse order to the above.
Replacing motor or impeller
1. Remove the front.
2. Remove gable end.
3. Remove the screw between motor and fan.
4. Disconnect the cables to the motor.
5. Remove the screws securing the motor and
lift it out together with the impeller.
6. Install the new motor and/or the new
impeller as above in reverse order.

Pamir 3200
11
EN
Troubleshooting
If the fans are not running or do not perform
properly, check the following:
• The power supply.
• That the intake grille/lter is not dirty.
• That the motor's safety cut-out has not been
deployed.
• Functions and settings of the FC control
system, see the FC manual.
If there is no heat, check the following:
• Functions and settings of the FC control
system, see the FC manual.
For units with electrical heating, also check the
following:
• Power supply to electric heater coil; check
fuses and circuit-breaker (if any).
• That the overheat protection has not been
deployed.
If the fault cannot be rectied, please contact a
qualied service technician.
Residual current circuit breaker (E)
When the installation is protected by means of
a residual current circuit breaker, which trips
when the appliance is connected, this may be
due to moisture in the heating element. When
an appliance containing a heater element has
not been used for a long period or stored in
a damp environment, moisture can enter the
element.
This should not be seen as a fault, but is
simply rectied by connecting the appliance to
the main supply via a socket without a safety
cut-out so that the moisture can be eliminated
from the element. The drying time can vary
from a few hours to a few days. As a preventive
measure, the unit should occasionally be run
for a short time when it is not being used for
extended periods of time.
Packaging
Packaging materials are chosen with
consideration to the environment and are
therefore recyclable.
Handling of product at end of working
life
This product may contain substances necessary
for the functionality of the product but
potentially dangerous for the environment. The
product should not be disposed of mixed with
general household waste but delivered to a
designated collection point for environmental
recycling. Please contact the local authority
for further details of your nearest designated
collection point.
Safety
• For all installations of electrically heated
products a residual current circuit breaker
300 mA for re protection should be used.
• Keep the areas around the air intake and
exhaust grilles free from possible obstructions!
• The unit must not be fully or partially covered as
overheating can result in a re risk!
• Lifting equipment must be used to lift the unit.
• This appliance can be used by children aged
from 8 years and above and persons with
reduced physical, sensory or mental capabilities
or lack of experience and knowledge if they
have been given supervision or instruction
concerning use of the appliance in a safe way
and understand the hazards involved. Children
shall not play with the appliance. Cleaning and
user maintenance shall not be made by children
without supervision.
• Children of less than 3 years should be kept
away unless continuously supervised.
• Children aged from 3 years and less than 8
years shall only switch on/off the appliance
provided that it has been placed or installed
in its intended normal operating position and
they have been given supervision or instruction
concerning use of the appliance in a safe way
and understand the hazards involved.
• Children aged from 3 years and less than 8
years shall not plug in, regulate and clean the
appliance or perform user maintenance.
CAUTION — Some parts of this product can
become very hot and cause burns. Particular
attention has to be given where children and
vulnerable people are present.

Art.no 255200, 2021-02-12 CH
Main offi ce
Frico AB Tel: +46 31 336 86 00
Industrivägen 41
Sweden www.frico.net
For latest updated information and information
about your local contact: www.frico.net.
Table of contents
Other Frico Air Conditioner manuals

Frico
Frico SLW400 User manual

Frico
Frico PA2500 User manual

Frico
Frico Thermozone PA2200C User manual

Frico
Frico TKW20 User manual

Frico
Frico ACC1000WL User manual

Frico
Frico ADAC090 User manual

Frico
Frico AR200 Series User manual

Frico
Frico PAEC4000W User manual

Frico
Frico Soloclim SCV21DCIN User manual

Frico
Frico AD200A User manual

Frico
Frico Thermozone AD300A/E User manual

Frico
Frico PA2210CA User manual

Frico
Frico Thermozone PA 1000 User manual

Frico
Frico PAEC4010A-NA User manual

Frico
Frico AGI6000 User manual

Frico
Frico Thermozone AC 300 User manual

Frico
Frico PAEC4000 NA Series User manual

Frico
Frico Climobile User manual

Frico
Frico PA1006 User manual

Frico
Frico AR3510W User manual