Frico AGS5515 User manual

AGS5500
Original instructions
.... 19
GB

AGS5500
2
The introduction pages consist mainly of pictures. For translation of the
English texts used, see the respective language pages.
GB

AGS5500
3
Fig.1. Dimensions
L
L/2
766
4087
147
500
450
30
AGS5515: 4 x M10
AGS5520/5525: 6 x M10
AGS5530: 8 x M10
605
555
AGS5520/5525
L
[mm]
AGS5515 1515
AGS5520 2010
AGS5525 2520
AGS5530 3030
PC board (2 x for AGS5525/5530)
WL WH
AGS5515 DN25 (1") DN20 (3/4")
AGS5520 DN32 (1 1/4") DN25 (1")
AGS5525 DN32 (1 1/4") DN32 (1 1/4")
AGS5530 DN40 (1 1/2") DN32 (1 1/4")
Inside thread
SIRe
93040
470 30
30
30
470
470
40
40
965 965
990 990
970
AGS5530

AGS5500
4
1 2 3
Fig. 3. Installation alternatives
Fig. 4. Open the unit
min 200
min 80
Fig. 2. Minimum distance

AGS5500
5
20 mm
20 mm
20 mm
AGS5500 + GWB640
AB
CD
EF
GWB640
40
640
120
Type Wall bracket
GWB640
AGS5515 2 pcs
AGS5520 3 pcs
AGS5525 3 pcs
AGS5530 4 pcs
Fig. 5. Mounting bracket GWB640

AGS5500
6
SIReBN
SIReAC
SIReAA
SIReRTX 70x33x23 mm
SIReUR 114x70x50 mm
SIReWTA
SIReCJ4
SIReCJ6
SIReCC603 3 m
SIReCC605 5 m
SIReCC610 10 m
SIReCC615 15 m
SIReCC640 40 m
SIReCC403 3 m
SIReCC405 5 m
SIReCC410 10 m
SIReCC415 15
SIRe
C
SIReB
SIReAC/SIReAA
SIReRTX
SIReUR
SIReWTA
SIReCC
SIReCJ4/SIReCJ6
VMO20 DN20
VMO25 DN25
VMOP20 DN20
VMOP25 DN25
VOS20 DN20
VOS25 DN25
VOSP20 DN20
VOSP25 DN25
VOT20 DN20
VOT25 DN25
VMT20 DN20
VMT25 DN25
VAT
VOS VOSP
VMO VMOP
VOT
VAT
VMT

AGS5500
7
Output charts water AGS5500WH
Supply water temperature: 110 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 110/80 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGS5515WH max 5500 32 47 0,13 1,2 51 45 0,42 10,9
min 2500 14 34 0,05 0,2 31 55 0,26 4,4
AGS5520WH max 8250 48 42 0,17 0,8 85 48 0,70 10,7
min 3750 22 32 0,07 0,1 52 59 0,43 4,2
AGS5525WH max 11000 62 42 0,22 0,7 111 48 0,92 10,0
min 5000 29 33 0,09 0,1 68 58 0,56 3,9
AGS5530WH max 13750 80 47 0,31 1,0 138 48 1,14 10,6
min 6250 36 37 0,12 0,2 87 59 0,72 4,5
Supply water temperature: 90 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 90/70 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGS5515WH max 5500 32 52 0,20 2,9 41 40 0,51 16,1
min 2500 15 39 0,07 0,4 26 48 0,31 6,5
AGS5520WH max 8250 48 47 0,28 1,9 69 43 0,85 15,8
min 3750 22 36 0,10 0,3 42 51 0,52 6,1
AGS5525WH max 11000 63 47 0,36 1,7 90 42 1,11 14,7
min 5000 29 36 0,13 0,3 55 51 0,68 5,7
AGS5530WH max 13750 77 50 0,47 2,2 11 3 42 1,38 15,8
min 6250 36 40 0,18 0,4 71 51 0,87 6,7
*1) Recommended outlet air temperature for good comfort and optimized output.
*2) Nominal output at given supply and return water temperature.
Supply water temperature: 80 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 80/60 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGS5515WH max 5500 33 58 0,35 8,3 34 36 0,41 11,2
min 2500 14 40 0,09 0,6 21 43 0,26 4,5
AGS5520WH max 8250 48 50 0,39 3,7 57 38 0,70 10,9
min 3750 22 38 0,13 0,5 35 45 0,42 4,3
AGS5525WH max 11000 62 50 0,51 3,3 74 38 0,91 10,1
min 5000 29 38 0,17 0,4 46 45 0,56 4,0
AGS5530WH max 13750 81 54 0,75 5,3 92 38 1,12 11,0
min 6250 35 40 0,22 0,6 58 45 0,70 4,7
Supply water temperature: 82 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 82/71 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGS5515WH max 5500 31 54 0,27 5,1 40 39 0,89 47,9
min 2500 14 40 0,08 0,6 25 47 0,55 19,0
AGS5520WH max 8250 48 50 0,37 3,3 67 42 1,49 47,6
min 3750 22 37 0,12 0,4 41 50 0,91 18,2
AGS5525WH max 11000 63 50 0,48 3,0 88 42 1,96 44,8
min 5000 29 38 0,16 0,4 54 50 1,19 1 7, 1
AGS5530WH max 13750 79 52 0,64 4,0 111 42 2,47 47,1
min 6250 36 40 0,21 0,5 70 51 1,55 19,6

AGS5500
8
Output charts water AGS5500 WL
Supply water temperature: 80 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 80/60 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGS5515WL max 5500 31 40 0,19 1,3 47 43 0,58 9,8
min 2500 14 33 0,07 0,2 28 51 0,35 3,7
AGS5520WL max 8250 49 34 0,26 2,4 78 46 0,95 27,3
min 3750 21 26 0,09 0,4 47 55 0,57 10,4
AGS5525WL max 11000 64 34 0,34 4,4 100 45 1,22 49,1
min 5000 29 26 0,13 0,8 61 54 0,74 18,7
AGS5530WL max 13750 78 36 0,44 4,9 124 45 1,51 43,2
min 6250 35 29 0,17 0,9 73 52 0,89 16,6
Supply water temperature: 70 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 70/50 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGS5515WL max 5500 32 44 0,30 2,9 37 38 0,45 6,2
min 2500 14 35 0,10 0,4 22 44 0,27 2,4
AGS5520WL max 8250 48 38 0,36 4,5 62 40 0,75 1 7, 7
min 3750 22 28 0,13 0,7 37 47 0,46 6,8
AGS5525WL max 11000 63 38 0,47 8,2 80 39 0,97 31,8
min 5000 29 28 0,17 1,3 49 47 0,59 12,3
AGS5530WL max 13750 81 41 0,67 10,6 98 39 1,19 28,9
min 6250 36 32 0,23 1,6 58 45 0,70 11,2
*1) Recommended outlet air temperature for good comfort and optimized output.
*2) Nominal output at given supply and return water temperature.
Supply water temperature: 60 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 60/40 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGS5515WL max 5500 33 48 0,63 11,9 27 32 0,32 3,4
min 2500 15 37 0,16 0,9 16 37 0,19 1,3
AGS5520WL max 8250 48 42 0,67 14,4 46 34 0,55 10,1
min 3750 21 31 0,18 1,2 28 40 0,34 4,0
AGS5525WL max 11000 65 45 1,06 38,2 59 34 0,72 18,1
min 5000 30 32 0,26 2,7 36 39 0,44 7, 2
AGS5530WL max 13750 81 45 1,30 35,0 71 33 0,87 1 7, 0
min 6250 36 35 0,35 3,4 42 38 0,51 6,7
Supply water temperature: 55 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 55/35 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGS5515WL max 5500 32 48 1,14 37,4 21 29 0,26 2,2
min 2500 14 38 0,21 1,5 13 33 0,15 0,9
AGS5520WL max 8250 49 46 1,31 52,4 37 31 0,45 7, 0
min 3750 21 32 0,23 2,0 23 36 0,28 2,8
AGS5525WL max 11000 62 46 1,68 94,3 49 31 0,59 12,6
min 5000 29 34 0,33 4,2 30 36 0,36 5,1
AGS5530WL max 13750 78 46 2,10 83,9 58 30 0,70 12,0
min 6250 37 37 0,49 6,4 34 34 0,42 4,8

AGS5500
9
AGS5500 A without heat 1
AGS5500 WL with water heat, coil for low temperature water < 80/60 °C 2
See www.frico.se for additional calculations.
Protection class: IP24.
CE compliant.
*1) Lowest/highest airflow of totally 5 fan steps.
*2) Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area: 200 m². At
lowest/highest airflow.
*3) ∆t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*4) Applicable at water temperature 80/60 °C, air temperature, in +18 °C.
*5) Applicable at water temperature 60/40 °C, air temperature, in +18 °C.
Type Output
[kW]
Airflow*1
[m3/h]
Sound
level*2
[dB(A)]
Voltage
motor
[V]
Amperage
motor
[A]
Length
[mm]
Weight
[kg]
AGS5515A 0 2500/5800 51/70 230V~ 8,1 1515 109
AGS5520A 0 3750/8700 52/72 230V~ 12,1 2010 144
AGS5525A 0 5000/11600 53/73 230V~ 16,2 2520 183
AGS5530A 0 6250/14500 55/74 230V~ 20,3 3030 218
Type Output*5
[kW]
Airflow*1
[m3/h]
∆t*3,5
[°C]
Water
volume
[l]
Sound
level*2
[dB(A)]
Voltage
motor
[V]
Amperage
motor
[A]
Length
[mm]
Weight
[kg]
AGS5515WL 26 2500/5500 19/14 4,0 50/70 230V~ 7, 7 1515 129
AGS5520WL 45 3750/8250 22/16 8,1 51/71 230V~ 11,6 2010 169
AGS5525WL 59 5000/11000 21/16 9,2 52/72 230V~ 15,4 2520 213
AGS5530WL 71 6250/13750 20/15 11,0 54/74 230V~ 19,3 3030 258
AGS5500 WH with water heat, coil for high temperature water 580/60 °C 2
Type Output*4
[kW]
Airflow*1
[m3/h]
∆t*3,4
[°C]
Water
volume
[l]
Sound
level*2
[dB(A)]
Voltage
motor
[V]
Amperage
motor
[A]
Length
[mm]
Weight
[kg]
AGS5515WH 34 2500/5500 25/18 3,8 50/70 230V~ 7, 7 1515 129
AGS5520WH 57 3750/8250 27/20 4,9 51/71 230V~ 11,6 2010 169
AGS5525WH 74 5000/11000 27/20 6,4 52/72 230V~ 15,4 2520 213
AGS5530WH 92 6250/13750 27/20 7, 6 54/74 230V~ 19,3 3030 258
Technical specifications

AGS5500
10
AGS5515 / AGS5520
C°
C°
H1 H2N
Id RoomC2 C1 Actuator 230V Supply 230V
PE L
N
Heating
L
N
~
L
N F2 F3F1 F4 F5
Trafo
N
L
Motor
SIRe B1N
Trafo
Motor
protection
Internal
sensor
AGS5520
AGS5515
C°
Black
Blue
230V
200V
175V
145V
120V
100V
N
Transformer
230V
200V
175V
145V
120V
100V
Transformer
Yellow
Red
Brown
Black
Green
N
Orange
Blue
230V~

AGS5500
11
AGS5525 / AGS5530
C°
C°
H1 H2N
Id RoomC2 C1 Actuator 230VSupply 230V
PE L
N
Heating
L
N
~
L
N F2 F3F1 F4 F5
Trafo
N
L
Motor
SIRe B1N
Trafo
Motor
protection
Internal
sensor
C°
C°
H1 H2N
Id RoomC2 C1 Actuator 230VSupply 230V
PE L
N
Heating
L
N
~
L
N F2 F3F1 F4 F5
Trafo
N
L
Motor
SIRe B1N
Trafo
Motor
protection
Internal
sensor
C°
Black
Blue
230V
200V
175V
145V
120V
100V
N
Transformer
230V
200V
175V
145V
120V
100V
Transformer
Yellow
Red
Brown
Black
Green
N
Orange
Blue
Black
Blue
230V
200V
175V
145V
120V
100V
N
Transformer
AGS5530
AGS5525
230V~

AGS5500
12
SIReB Basic
AGS5500A
Wiring diagrams for SIReAC Competent, see manual for SIRe.
C2
X5 C1
X4 ROOM
X3
Pot.
Unit ID ACTUATORSUPPLY
N L NL
PE
L
~
230V~
C2
X5 C1
X4 ROOM
X3
Pot.
Unit ID ACTUATORSUPPLY
N L NL
PE
L
~
230V~
C2
X5 C1
X4 ROOM
X3
Pot.
Unit ID ACTUATORSUPPLY
N L NL
PE
L
~
230V~
SIReCC6XX (max 10 m)
SIReCC6XX
(max 50 m)
SIReCC6XX
(max 50 m)
SIReUB1
SIReRTX
(optional)
L=2m
SIReB1/B2/B1EC
SIReB1/B2/B1EC
SIReB1/B2/B1EC

AGS5500
13
SIReB Basic
AGS5500 W
Wiring diagrams for SIReAC Competent and SIReAA Advanced, see manuals for SIRe.
C2
X5 C1
X4 ROOM
X3
Pot.
Unit ID ACTUATORSUPPLY
N L NL
PE
L
~
230V~
C2
X5 C1
X4 ROOM
X3
Pot.
Unit ID ACTUATORSUPPLY
N L NL
PE
L
~
230V~
C2
X5 C1
X4 ROOM
X3
Pot.
Unit ID ACTUATORSUPPLY
N L NL
PE
L
~
230V~
SIReCC6XX (max 10 m)
SIReB1/B2/B1EC
SIReB1/B2/B1EC
SIReB1/B2/B1EC
SIReCC6XX
(max 50 m)
SIReCC6XX
(max 50 m)
SIReUB1
SIReRTX
(optional)
SD230
SD230
SD230
L=1,5m
L=2m

AGS5500
19
GB
General Instructions
Read these instructions carefully before
installation and use. Keep this manual for
future reference.
The product may only be used as set out in
the assembly and operating instructions. The
guarantee is only valid if the product is used
in the manner intended and in accordance
with the instructions.
Operation
Air is drawn in at the front side of the unit
and blown out downwards towards the
entrance so that it shields the door opening
and minimizes heat loss.
To get the best curtain effect the unit must
extend the full width of the door opening.
The grille nearest the door is adjustable and
is normally angled outwards to achieve the
best protection against incoming cold air.
The efficiency of the air curtain depends
on the air temperature, pressure differences
across the doorway and any wind pressure.
NOTE! Negative pressure in the building
considerably reduces the efficiency of the air
curtain. The ventilation should therefore be
balanced.
Application area
The AGS5500 air curtain unit is supplied
without heating or hot water heating.
AGS5500 is intended for entrances and doors,
with installation height up to 5,5 metres.
Protection class: IP24.
Electrical installation
The installation, which should be preceded by
an omnipolar switch with a contact separation
of at least 3 mm, should only be wired by a
competent electrician and in accordance with
the latest edition of IEE wiring regulations.
The control system is pre-installed in the
air curtain with an integrated control card.
SIRe is supplied pre-programmed with quick-
fit connections. Modular cables are connected
to the control board. AGS5525/5530 have
two SIRe-cards, one of them being slave
connected. See manual for SIRe.
Operation (230V~) is connected to
terminal block in the junction box on top of
the unit. See wiring diagrams.
Connecting the water coil (W)
The installation must be carried out by an
authorised installer.
The water coil has copper tubes with
aluminium fins and is suitable for connection
to a closed water heating system. The heating
coil must not be connected to a mains
pressure water system or an open water
system.
Note that the unit shall be preceded by a
regulating valve, see Frico valve kit.
The water coil is connected on the upper side
of the unit via connections, see table fig. 1.
The connections to the heating coil must be
equipped with shut off valves to allow problem
free removal. Water coil is equipped with a
drain valve. A vent valve should be connected
at a high point in the pipe system.
Air valves are not included.
Mounting
The air curtain is installed horizontally with
the supply air grille facing downwards as close
to the door as possible. For the protection of
wider doorways, several units can be mounted
next to each other. Ensure that the service
hatch is accessible and can be fully opened.
The unit has 4 M10 fixed nuts on the upper
side (6 on 2 and 2,5 meter models, 8 on 3
meter model) for ceiling installation using
threaded bars, or for installation using wall
brackets (accessories). See fig. 5.
Adjustment of the air curtain and air flow
The direction and speed of the air flow should
be adjusted considering the load on the
opening. Pressure forces affect the air stream
and make it bend inwards into the premises
(when the premises are heated and the
outdoor air is cold).
The air stream should therefore be directed
outwards to withstand the load. Generally
speaking, the higher the load, the greater the
angle that is needed.
Assembly and operating instructions

AGS5500
20
GB
Service, repairs and maintenance
For all service, repair and maintenance first
carry out the following:
1. Disconnect the power supply.
2. The service hatch is opened by first
opening the intake grille and then unscrew
the screws in the underside of the unit, see
fig. 4.
Filter (W)
The distance between the coil plates in
combination with the hole diameter of
the intake grille protects against dirt and
blockage. This normally makes a separate
filter unnecessary.
Basic setting fan speed
The fan speed when the door is open is set
using the control. Note that the air flow
direction and fan speed may need fine
adjustment depending on the loading of the
door.
Maintenance
Since fan motors and other components are
maintenance free, no maintenance other than
cleaning is necessary. The level of cleaning
can vary depending on local conditions.
Undertake cleaning at least twice a year. Inlet
and exhaust grilles, impeller and elements
can be vacuum cleaned or wiped using a
damp cloth. Use a brush when vacuuming
to prevent damaging sensitive parts. Avoid
the use of strong alkaline or acidic cleaning
agents.
Overheating
All motors are equipped with an integral
thermal safety cut-out. This will operate,
stopping the air curtain should the motor
temperature rise too high. The cut-out
will automatically reset when the motor
temperature has returned to within the
motor’s operating limits.
Temperature control
Temperature control of SIRe maintains the
exhaust temperature. If the temperature
should exceed anyway the overheating alarm
goes off. For more information see the manual
for SIRe.
Fan replacement
1.Determine which of the fans is not
functioning.
2.Disconnect the cables to the relevant fan.
3.Remove the screws securing the fan and lift
the fan out.
4.Install the new fan as above in reverse
order.
Replacing the water coil (W)
1.Shut off the water supply to the unit.
2.Disconnect the connections to the water
coil.
3.Remove the mounting screws securing the
coil in the unit and lift the coil out.
4.Install the new coil in reverse order to the
above.
Draining the water coil (W)
The drain valve is on the underside of the coil
on the connector side. It can be accessed via
the service hatch.
Trouble shooting
If the fans are not working or do not blow properly,
check the following:
•That the intake grille/filter is not dirty.
•Functions and settings of the SIRe control
system , see manual for SIRe.
If there is no heat, check the following:
•Functions and settings of the SIRe control
system, see manual for SIRe.
For units with water coil, also check the following:
•That the water coil is air free.
•That there is enough water flow.
•That incoming water is heated enough.
If the fault cannot be rectified, please contact
a qualified service technician.

AGS5500
21
GB
Safety
•Keep the areas around the air intake
and exhaust grilles free from possible
obstructions!
•The unit may have hot surfaces during
operation and when cooling down!
•Lifting equipment must be used to lift the
unit.
•This appliance can be used by children
aged from 8 years and above and persons
with reduced physical, sensory or
mental capabilities or lack of experience
and knowledge if they have been given
supervision or instruction concerning
use of the appliance in a safe way and
understand the hazards involved. Children
shall not play with the appliance. Cleaning
and user maintenance shall not be made
by children without supervision.

AGS5500
54

AGS5500
55

Art.no: 208148, 2015-10-19 HH/CH
This manual suits for next models
4
Table of contents
Other Frico Fan manuals
Popular Fan manuals by other brands

CFM
CFM WEB-0807 Brochure & specs

Vents
Vents Simple user manual

2VV
2VV ALFA EC Series Full manual

Envirovent
Envirovent Slimline 150 Installation guide for engineer / installer

Singer
Singer DF30-5 WH instruction manual

Triangle Engineering
Triangle Engineering COMFORT COOLER CC2422 Installation and operation