Instructions 4 di 4 cod. N420000A – 04
9. Season change procedure
It is veryimportant to follow the procedure outlined inthis paragraph to avoid a systematic
alarm of the combination Soloclim+SCBR3 and the possible failure of the nebulizer.
This procedure, enabled through the display of the air conditioner, modifies the default settings of
the drain pan of the appliance by disabling its automatic closure during the summer season. This
procedure is used to avoid that during the summer season, with the opening of the drain valve of the
drain pan, the condensate itself is poured all in the 3.0 nebulizer installed under the appliance.
To activate this function:
-Press the cooling mode key on the display ofthe Soloclim for15 sec.
-The symbol “En” will appear
-Press again for 15 sec. the key
-The symbol “ds” will appear
-Let the display go backto the main screen
The condensate drain will always remain open in both seasons, guaranteeing a regular flow of
condensation.
To set the default function again, follow the same procedure and select "En".
10. Led and buzzer
The device is equipped with some light and sound signals that indicate the status and any
malfunctions:
•GREEN LED: atomizer power supply on
•ORANGE LED: atomizer running
•RED LED: atomizer in stand-by and electrical heater on
•BLINCKING RED-GREEN LED + BUZZER: alarm
The reasons for alarms may be the following:
•maximum level sensor activated
•level sensors wrong (for example the maximum level sensor is busy when normal level
sensor is off)
•bad indication of condensate temperature