
Page 20
HERMETIC COMPONENT REPLACEMENT
The following procedure applies when replacing
components in the sealed refrigeration circuit
or repairing refrigerant leaks. (Compressor,
condenser, evaporator, capillary tube, refrigerant
leaks, etc.)
1. Recover the refrigerant from the system at the
process tube located on the high side of the
system by installing a line tap on the process
tube. Apply the gauge from the process tube
to EPA approved gauges from the process
tube to the EPA approved recovery system.
Recover the CFC’s in the system to at least
5%.
2. Cut the process tube below the pinch off in the
suction side of the compressor.
3. Connect the line from the nitrogen tank to the
suction process tube.
4. Drift dry nitrogen through the system and un-
solder the more distant connection rst. (Filter
drier, high side process tube, etc.)
5. Replace the inoperative component, and
always install a new filter drier. Drift dry
nitrogen through the system when making
these connections.
6. Pressurize the system to 30 PSIG with proper
refrigerant and boost the refrigerant pressure
to 150 PSIG with dry nitrogen.
7. Leak test the complete system with the electric
halogen leak detector, correcting any leaks
found.
8. Reduce the system to zero gauge pressure.
9. Connect the vacuum pump to the high side
and low side of the system with deep vacuum
hoses, or copper tubing. (Do not use regular
hoses.)
NOTE: If the entire charge will
not enter the high side, allow the
remainder to enter the low side in small
increments while operating the unit.
12. Restart the unit several times after allowing
pressures to stabilize. Pinch off the process
tubes, cut and solder the ends. Remove the pinch
off tool, and leak check the process tube ends.
SPECIAL PROCEDURES IN THE CASE OF
COMPRESSOR MOTOR BURN-OUT
1. Recover all refrigerant and oil from the
system.
2. Remove the compressor, capillary tube and
lter drier from the system.
3. Flush the evaporator, condenser and all
connecting tubing with dry nitrogen, or equivalent,
to remove all contamination from the system.
Inspect the suction and discharge lines for carbon
deposits. Remove and clean if necessary.
10. Evacuate the system to an absolute holding
pressure of 200 microns or less.
NOTE: This procedure can be speeded up by
the use of heat lamps, or by breaking the
vacuum with refrigerant or dry nitrogen at
5,000 microns. Pressure system to 5 PSIG
and leave in the system a minimum of 10
minutes. Recover refrigerant, and proceed
with evacuation to a pressure of 200 microns
or a minimum of 10%.
11. Break the vacuum by charging the system
from the high side with the correct amount of
refrigerant specied. This will prevent boiling
the oil out of the crankcase.