Ductless_Dual_Zone_Heat_Pump_Submittal_11
Ductless Split Systems
Wall Mounted, Heat Pump Single-zone
Refrigeration line sets
Insulated line sets are available for all Friedrich split systems in
15 ft. and 35 ft. lengths. Each line set is equipped with are nuts
on both ends. Both liquid and suction lines are insulated. Line
sets can be joined together with eld supplied double female
connectors. Each system requires one line set for each indoor
unit installed. On multi-zone systems, line sets should be ordered
based on individual indoor unit capacities not total system
capacity. For example, a M18DYF uses 2 line sets for 9,000 Btu
units, not 1 for the 18,000 Btu product.
NOTE: All models have low ambient
capabilities built-in. Capacity is
reduced as 0 degrees Fahrenheit is
approached.
NOTE: All R410A models have 1/2˝
UNF 20 thread per inch charging and
vacuuming ports. An adapter must be
used for 1/4˝ gauges. Adapter part
number 67270018 is available through
Friedrich parts distributors.
Due to continuing research in
new energy-saving technology,
specications are subject to change
without notice.
Specifications
PERFORMANCE RATINGS
SYSTEM MODEL NO. M18DYF M21DYF M24DYF
INDOOR MODEL 2 x MW09Y3FM MW09Y3FM MW12Y3FM 2 x MW12Y3FM
OUTDOOR MODEL MR24DY3F MR24DY3F MR24DY3F
Capacity Cooling Btu 9500 ea. 9500 12000 12000 ea.
CapaCity Cooling Min - Max Btu 5100-11300 ea. 5100-11300 ea. 5100-13600 ea 5100-13600 ea
SenSible Heat Ratio 0.77 0.77 0.77 0.77
CapaCity Heating @ 47°F Btu 11000 ea. 11000 ea. 14000 14000 ea.
CapaCity Heating Min - Max Btu 5100-13000 ea. 5100-13000 ea. 5100-15400 ea. 5100-15400 ea.
CapaCity Heating @ 17°F Btu 9500 ea. 9500 ea. 11000 10500 ea.
HSpF 9.0 9.0 9.0
SeeR 16.5 16.5 16.5
eeR 12.2 11.2 10.4
eneRgy StaR YES NO NO
MoiStuRe ReMoval Pts/h 2.9 ea. 2.9 ea 3.7 ea. 3.7 ea.
aiRFlow (Quiet, low, Med, HigH) CFM 185,220,260,295 185,220,260,295 215,250,305,355 215,250,305,355
Sound Rating - indooR dB-A 27,29,33,37 27,29,33,37 30,34,39,42 30,34,39,42
Sound Rating - outdooR dB-A 52 52 52
opeRationg Range (Heating) °F 0 - 115 (14 - 75) 0 - 115 (14 - 75) 0 - 115 (14 - 75)
eSt. yeaRly opeRating CoSt $128 $152 $152 $184
eleCtRiCal data (all indooR unitS ReCeive poweR FRoM outdooR unit; valueS liSted aRe total)
poweR SouRCe 230/(208)-60-1 230/(208)-60-1 230/(208)-60-1
Min. aMpaCity A 15 15 15
Cooling wattS W 1600 1900 2300
Max. td FuSe/bReakeR A 20 20 20
ReFRigeRation SySteM
ReFRigeRant R410A R410A R410A
CoMpReSSoR type Inverter Inverter Inverter
ConneCtionS Flare Flare Flare
liQuid line o.d. in 1/4"1/4"1/4"1/4"
SuCtion line o.d. in 3/8"3/8"3/8"3/8"
FaCtoRy pReCHaRge ft 98' 98' 98'
Max. line lengtH ft Each unit:82 Total:98 Each unit:82 Total:98 Each unit:82 Total:98
Max. HeigHt diFFeRenCe ft 33' 33' 33'
diMenSionS & weigHt
indooR unit
w x H x d in 31 1/8" x 10 7/8" x 8 1/2" ea. 31 1/8" x 10 7/8" x 8 1/2" ea. 31 1/8" x 10 7/8" x 8 1/2" ea.
net weigHt lbs 21 ea. 21 21 21 ea.
SHipping weigHt lbs 26 ea. 26 26 26 ea.
outdooR unit
w x H x d in 35 3/8" x 32 5/8" x 13"35 3/8" x 32 5/8" x 13"35 3/8" x 32 5/8" x 13"
net weigHt lbs 136 136 136
SHipping weigHt lbs 154 154 154
USED WITH: LENGTH-FT. LIQUID SUCTION KIT#
All 9000 and
12000 Btu
indoor units
15' 1/4”3/8”T32150
35' 1/4”3/8”T32350