AOU18RLXFW Submittal
Inverter Driven Heat Pump
Job Name:_______________________________
Location: ________________________________
Engineer:________________________________
Submitted to:_____________________________
Submitted by:_____________________________
Reference:_______________________________
Outdoor Unit Power 208-230/VAC-1Ph-60Hz
Available Voltage Range 187-253VAC
Fuse Size, Max. 30A
MCA 14.5A
Compressor Inverter Driven Variable Speed DC Rotary
No. used 1
Output 2,100W
Lubrican Oil POE (RB68)
Fan type Propeller
Motor Output 100W
Airflow rate Cooling/Heating (High) 1489 / 2530CFM
Refrigerant R410A
Outdoor unit 4lbs 10.1oz
Contrlol Electronic Expansion Valve
O.D. Discharge (in) 3/8”(Flare)
O.D Suction (in) 5/8”(Flare)
Dimensions H x W x D
Uncrated (in) 32-3/4 x 35-3/8 x 13
(mm) (830 x 900 x 330)
Crated (in) 38-1/4 x 41-1/2 x 17-1/2
(mm) (970 x 1050 x 445)
Weight Outdoor
Net 135lbs (61kg)
Gross Shipping 150lbs (68kg)
Cooling
Rated Capacity 18,000BTU/h
Min-Max Capacity 7,000~23,000BTU/h
Rated Power Input 1.35kW
Max. Power Input 3.01kW
SEER 19.2
EER 13.3
Outdoor Sound Rating 47dB
Heating
Rated Capacity 21,600BTU/h
Min-Max Capacity 7,500~36,200BTU/h
Rated Power Input 1.80kW
Max. Power Input 3.01kW
HSPF 10.0
EER 12.0
Outdoor Sound Rating 50dB
Piping Lengths
Max. Piping Length (Total) 164ft
Max. Pipe Height Difference 98ft
Connection method (Flared)
Operating Range . .
Cooling 14°F~115°F DB
Heating 5°F~75°F DB
Approval:________________________________
Date:___________________________________
Construction: ____________________________
Unit #:__________________________________
Drawing #:_______________________________
Fujitsu General America, Inc.
Fairfield, NJ 07004
Toll Free: 1-888-888-3424
Fax: (973) 836-0447
www.fujitsugeneral.com
Fujitsu products are subject to continu-
ous improvements. Fujitsu reserves
the right to modify product design,
specifications and information in this
data sheet without notice and without
incuring any obligations.
Note: Specifications are based on the following conditions.
Power source of specifications : 230V
Cooling: Indoor temperature of 80°F(26.67°C)DB / 67°F(19.44°C)WB, and outdoor temperature of 95°F(35°C)DB/75°F(23.89°C)WB.
Heating: Indoor temperature of 70°F(21.11°C)DB / 60°F(15.56°C)WB, and outdoor temperature of 47°F(8.33°C)DB/43°F(6.11°C)WB.
Pipe length : 24ft. 7in.(7.5m),Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit]
ASU18RLF