Fulham FHSAC1-UNV-40C User manual

•
•
Output Wattage: 40W Max.
•
Universal Voltage: 120-277V , 50/60Hz~
•
Output Current: 250-1400mA
•
Output voltage range of 11-55V
General Specifications
Input Voltage
Input Current
Input Power
Standby Input Power
Output Current
Output Voltage Range
Output Power
Number of Output Channels
RFI/EMI
Output Type
Ambient Operating Temperature Range
Input Surge Protection
Protections
120-277VAC, 50/60Hz
0.43A @ 120VAC
54W
<0.85W
Constant Current
11-28VDC ( 250-1400mA ) , 11-40VDC ( 250-1000mA ) , 11-55VDC ( 250-730mA )
40W Max. ( Figure 1 )
1 Channel
FCC Part 15A Non-Consumer
LED Class 2
Line-Neutral 3kV , Line & Neutral-Gound 6kV , Ring Wave ANSI/IEEEC62.41
Input Current Protection
Output Open Circuit Protection
Output Short Circuit Protection
Output To Ground Short Circuit Protection
250-1400mA [ TPSB 100 ( Program Box ) , Figure 1 ] ; Record New Setting On 1"x0.5" Label
This Driver Will Operate The Following LED Modules: Any LED module designed to accept input voltage range of 11-55VDC and can operate
up to current of 250-1400mA.
Battery Type LiFePO4 6.4VDC (Part# FHSBATL2-3.2L)
Battery Capacity Available
Max. Case Temperature
3200mAh
Battery Recharge Time 12 Hours
Page 1 of 7
Driver Type
FHSAC1-UNV-40C
SPECIFICATIONS
2017-736-1 Rev A
Power Factor >0.9
<20%
THD
5W or 10W Initial @ Emergency Mode
Sound Rating A
Over Temperature Protection
Overload Protection
Dimming Controller Type / Dimming Range 0-10V / 100% - 1%,0% ( Figure 2 ) / Custom Dimming Curve / Dimmed To Off
Service Life
Approvals / Class
50,000 hours
RoHS , cURus , CEC , Dry or Damp Locations
MECHANICAL DATA 100%-1%,0% LiFePO4 E313578
0°C to 48°C(32°F to 118.4°F)
63°C(145.4°F)
•
Compact case with side leads
MECHANICAL DATA
Case Tolerance=±0.02"
FHSAC1-UNV-40C
FHSBATL2-3.2L
LED Driver with integrated emergency backup
( Min. 180 Minutes Runtime @ 5W Setting , Min. 90Minutes Runtime @ 10W Setting )
Fulham extends a limited warranty to the original purchaser or first user for a period of 5 years from the date of manufacture when properly installed
and operated under normal conditions of use. For complete terms and conditions, please refer to the Warranty Center at www.fulham.com.
Specifications subject to change without notice.

SPECIFICATIONS
Page 2 of 7
2017-736-2 Rev A
MECHANICAL DATA 100%-1%,0% LiFePO4 E313578
FHSAC1-UNV-40C
Figure 4Figure 3
Figure 5 Figure 6
Figure 2
Figure 1
700
R-SET Curve
400
500
600
700
Io (mA)
200
300
0 4 8 12 16 20
Resistor Value(Kohm)
0-10V Linear Dimming Curve
40
60
80
100
oValue (%)
0
20
0 1 2 3 4 5 6 7 8 9 10
Io
Dimming Voltge (V)
0 1 2 3 4 5 6 7 8 9 10
60
80
100
e(%)
0-10V Log Dimming Curve
0
20
40
Io Value
Dimming Voltge (V)
800
1000
1200
1400
max) (mA)
200
400
600
Io(m
Vo vs Io(max) Curve( )
10 20 30 40 50
Output Voltage (V)
90
Efficienc Vs Output Voltage at 120Vac
82
84
86
88
Efficienc (%)
750mA
1000mA
1250mA
1400mA
80
20 25 30 35 40 45 50 55
Output Voltage (V)
90
Efficienc Vs Output Voltage at 230Vac
86
88
ncy (%)
750mA
1000mA
80
82
84
20 25 30 35 40 45 50 55
Effici n
Output Voltage (V)
1250mA
1400mA
Output Voltage (V)
Fulham extends a limited warranty to the original purchaser or first user for a period of 5 years from the date of manufacture when properly installed
and operated under normal conditions of use. For complete terms and conditions, please refer to the Warranty Center at www.fulham.com.
Specifications subject to change without notice.

SPECIFICATIONS
Page 3 of 7
2017-736-3 Rev A
MECHANICAL DATA 100%-1%,0% LiFePO4 E313578
FHSAC1-UNV-40C
Figure 7 Figure 8
Figure 9 Figure 10
Figure 11 Figure 12
88
90
(%)
Efficienc Vs Output Voltage at 277Vac
750mA
80
82
84
86
Efficienc
1000mA
1250mA
1400mA
20 25 30 35 40 45 50 55
Output Voltage (V)
80
100
120
140
e(Khrs)
Lifetime vs Tcase
0
20
40
60
50 55 60 65 70 75 80 85
Lifetime
Tcase(°C)
6
8
10
(%)
THD Vs Output Power
277V/60Hz
230V/50Hz
0
2
4
20 25 30 35 40
THD(
Output Power (W)
120V/60Hz
p ( )
80
90
100
110
Io vs Ext.NTC Curve
10
20
30
40
50
60
70
80
Io Ratio (%)
0
0 2 4 6 8 10 12 14 16 18 20
Resistor of Ext.NTC on Module (Kohm)
60
70
80
90
100
110
tio (%)
Io vs Tcase(driver)
0
10
20
30
40
50
50 60 70 80 90 100
Io Rat
Tcase(°C)
0.95
1.00
r
Power Factor Vs Output Power
277V/60Hz
0.75
0.80
0.85
0.90
Power Factor
230V/50Hz
120V/60Hz
20 25 30 35 40
Output Power (W)
Fulham extends a limited warranty to the original purchaser or first user for a period of 5 years from the date of manufacture when properly installed
and operated under normal conditions of use. For complete terms and conditions, please refer to the Warranty Center at www.fulham.com.
Specifications subject to change without notice.

WIRING DIAGRAMS
LED OUTPUT
CHANNEL
GRAY( - )
PURPLE( + )
Un-Switched Line
WHT(COMMON)
YEL/BLK( L )
BLK( L )
Switched or
Un-Switched Line
LED OUTPUT LEAD
TEST SWITCH / LED INDICATOR
DIMMING
0-10V
LED MODULE WITH NTC
(NTC OPTIONAL)
LED MODULE
RIGHT VIEW
1-Emergency Power Switch:
5W or 10W(10W @ ON)
ON
2-Self-Diagnostic:
Effective @ ON
ON OFF
1 2
BATTERY SWITCH
Emergency
Power Switch
FHSAC1-UNV-40C
FHSBATL2-3.2L
NTC INPUT LEAD
NOTE: 1.The driver must be grounded.
2.Once assembly, installation or servicing is complete,
set the BATTERY SWITCH to the ON position.
SPECIFICATIONS
Page 4 of 7
2017-736-4 Rev A
MECHANICAL DATA 100%-1%,0% LiFePO4 E313578
SELF DIAGNOSTIC INSTRUCTIONS / OPERATION:
Ø
INPUT SIDE LENGTH
BLACK 12"[304.8mm]
WHITE 12"[304.8mm]
YEL/BLK 16"[406.4mm]
OUTPUT SIDE LENGTH
LED OUTPUT 8"[203.2mm]
TEST LEAD 8"[203.2mm]
PURPLE 12"[304.8mm]
GRAY 12"[304.8mm]
Case Dimensions
Length 6.32"[160.5mm]
Width 3.05"[77.6mm]
Height 1.14"[29mm]
FHSAC1-UNV-40C
If Dip Switch 2 (Self-Diagnostic Switch) is set to the OFF position:
The self diagnostic feature is disable. A functionality test shall be manually conducted every thirty(30) days to ensure
the emergency LED light source illuminates as intended. A full discharge test shall be conducted once a year; the LED
light source shall illuminate for a minimum of ninety (90) minutes for the 10W load (Dip Switch 1 is set to the ON position)
or one hundred eighty (180) minutes for 5W load (Dip Switch 1 is set to the OFF position).
If Dip Switch 2 (Self-Diagnostic Switch) is set to the ON position:
The self diagnostic feature is enable .The emergency LED driver will conduct a self check for thirty (30) seconds every
thirty (30) days; and ninety (90) minutes or one hundred eighty (180) minutes self check every 12 months. After every self
check the LED indicator light will indicate a status signal. A single self-diagnostic test can be activated by pressing the test
switch three (3) times. Refer to Indicators Status Table for details.
When user toggle the Dip Switch, the LED indicator on Switch button would flash 3 times, 2.5S ON/0.5S OFF for Enabled,
while 0.5S ON/2.5S OFF for Disabled.
Fulham extends a limited warranty to the original purchaser or first user for a period of 5 years from the date of manufacture when properly installed
and operated under normal conditions of use. For complete terms and conditions, please refer to the Warranty Center at www.fulham.com.
Specifications subject to change without notice.

SPECIFICATIONS
Page 5 of 7
2017-736-5 Rev A
MECHANICAL DATA 100%-1%,0% LiFePO4 E313578
FHSAC1-UNV-40C
Fulham extends a limited warranty to the original purchaser or first user for a period of 5 years from the date of manufacture when properly installed
and operated under normal conditions of use. For complete terms and conditions, please refer to the Warranty Center at www.fulham.com.
Specifications subject to change without notice.
TEST SWITCH OPERATIONS:
1. EM Test: Press and hold test button (>1s)to enter EM mode for testing in normal AC powered .
2. Manual Self-Diagnostic(When Self-Diagnostic Enabled - Dip Switch 1 set to the ON position): After charging twelve
(12) hours or battery fully charged, quickly press the test button three(3) times within three(3) seconds to force the
controller to enter a Self-Diagnostic cycle. To quit the self-diagnostic cycle after engaged press and hold the test button
for ten(10) seconds.
TEST SWITCH INDICATOR STATUS:
Programming:
This driver can be programmed using the TPSB-100(E). Programming features include the following:
* Output Current :250-1400mA
* Dimming Curve
* LED NTC Thermal Protection
LED Indicators Status EM Driver Status/Mode
• Solid Green Sys tem OK/AC OK(Self-diagnos tic Enabled or Dis abled).
• Slow Flashing Red, 4s on/1s off Battery not detected, check battery s witch or connection.
• Flas hing Red, 1s on/1s off Battery Failure, replace battery.
• Flas hing Green, 1s on/1s off Self-Diagnos tic tes t underway.
• Fas t Flas hing Red, 0.1s on/0.1s off Abnorm al driver perform ance, replace driver.
• Very Slow Flas hing Red, 4s on/4s off Over tem perature.
• None. Both LEDs OFF Norm al working in EM m ode.
• Green/Red alternative flas hing, 1s green/1s red. No load or output over voltage protection triggered.

ACCESSORIES(Optional):
General Specifications
•
FHS-TSTWL-BC: Wet Location Rated - Bi-Color - Lighted Push Button Test Switch.
• Stainless Steel
• IP67
LED Color
Waterproof
Ambient Operating Temperature Range
Red/Green
IP67 (Switch Side Only)
-25°C to 55°C
>100,0000 Cycles
Mechanical Life
Wet Location Test Switch
0.06"[1.6mm]
Ø.54"[13.8mm]
0.31" Max.[8mm Max.]
Panel
Thickness
Ø.472"[Ø12mm]
0.88"[22.4mm]
Ø.36"[Ø9.1mm]
LED Lamp
Ø.3"[Ø7.6mm]
Metal cap
Mounting hole: ø0.472" - 0.492"
[ø12mm-12.5mm]
The switch overall dimension
O-ring Seal
Mechanical Data Tolerance=±0.5" [12.7mm]
General Specifications
•
FHS-EXT-48-TST: Light Push Button Test Switch Extension
Wire Length
Ambient Operating Temperature Range
Warranty
48”
-25°C to 55°C
5 years
48” Extension
Mechanical Data Tolerance=±0.5" [12.7mm]
SPECIFICATIONS MECHANICAL DATA 100%-1%,0% LiFePO4 E313578
FHSAC1-UNV-40C
Page 6 of 7
2017-736-6 Rev A
Fulham extends a limited warranty to the original purchaser or first user for a period of 5 years from the date of manufacture when properly installed
and operated under normal conditions of use. For complete terms and conditions, please refer to the Warranty Center at www.fulham.com.
Specifications subject to change without notice.

SPECIFICATIONS
Page 7 of 7
2017-736-7 Rev A
MECHANICAL DATA 100%-1%,0% LiFePO4 E313578
FHSAC1-UNV-40C
Fulham extends a limited warranty to the original purchaser or first user for a period of 5 years from the date of manufacture when properly installed
and operated under normal conditions of use. For complete terms and conditions, please refer to the Warranty Center at www.fulham.com.
Specifications subject to change without notice.
Important Safety Instructions
When using electrical equipment and this lighting device basic safety precaution should
be followed at all times including but not limited to the following:
·CAUTION: Do not let power supply cords touch hot surfaces.
·CAUTION: Do not mount near gas or electric heaters.
·IMPORTANT: An un-switched AC power source of 120VAC to 277VAC is required for the
·This device is designed for use in fixtures listed for dry and damp locations.
PLEASE READ CAREFULLY AND FOLLOW ALL INSTRUCTIONS FOR YOUR OWN SAFETY
·CAUTION: Make sure all electrical connections conform to the National Electrical Code and all applicable local
regulations.
·CAUTION: Battery is rechargeable LiFePO4 type and must be recycled or disposed of properly.
·CAUTION: Do not use this emergency driver with accessory equipment other than recommended by
manufacturer; failure to follow this may cause an unsafe condition. Servicing should only be performed
by qualified service personnel.
·CAUTION: Do not use this emergency driver for other than intended use.
·CAUTION: Equipment should be mounted in locations and at heights where it will not readily be subjected
to tampering by unauthorized personnel.
yellow/black and white leads.
·IMPORTANT: A switched or un-switched AC power source of 120VAC to 277VAC is acceptable
for the black lead only.
TESTING SYSTEM: The emergency battery requires a minimum charge time of one (1) hour before testing the circuit.
A minimum of twelve (12) hours is required for a full charge.
ASSEMBLY and FIELD INSTALLATION WIRING: WARNING: AC power must be off before proceeding with assembly,
installation or servicing of emergency driver. Additionally ensure that the battery is disconnected (Battery Switch set to OFF).
RATED EMERGENCY OPERATION: Ninety (90) minutes for the 10W load or one hundred eighty (180) minutes for the 5W
load. The 10W or 5W option is determined by the position of Dip Switch 1 (Emergency Power Selection Switch).
BATTERY DISABLE PROCEDURE: Unit must be powered within 6 months. To ship a fixture with the battery
connected without draining the battery the procedure is:
1. Driver is installed in a fixture.
2. Battery is switched to the “ON” position.
3. Fixture is powered and tested.
4. Fixture is un-powered, the unit enters EM mode.
5. Battery is switched to “OFF”, wait about 3 seconds then switch the battery back to the “ON” position.
Note: Not recommended for installations where unit will be without power for more than 6 months.
Table of contents
Other Fulham Lighting Equipment manuals

Fulham
Fulham EliteControl CTBRCB02JM02 User manual

Fulham
Fulham FireHorse FHEC30 Series Instruction sheet

Fulham
Fulham FHEZ10A24 User manual

Fulham
Fulham HotSpot FHSCP-UNV-10P-L-SD Series User manual

Fulham
Fulham HotSpotLED FHSAC1-UNV-70S User manual

Fulham
Fulham FireHorse FHEM10WHU Instruction sheet

Fulham
Fulham Firehorse FHEX21 Instruction sheet

Fulham
Fulham HOTSPOT LED FHSAC1-UNV-40L User manual

Fulham
Fulham HOTSPOT FHSCP-UNV-12W-L-SD User manual

Fulham
Fulham FHS2-UNV-56S Instruction sheet