GE C70 User manual

GE
Digital Energy
Instruction Manual
Product version: 7.3x
GE publication code: 1601-9015-AB2 (GEK-119614A)
C70
Capacitor Bank Protection
and Control System
1601-9015-AB2
IISO 9001
G
N
E
I
L
M
I
U
T
L
T
E
S
I
R
G
E
E
D
R
LISTED
52TL
IND.CONT. EQ.
E83849

Copyright © 2015 GE Multilin Inc. All rights reserved.
C70 Capacitor Bank Protection and Control System Instruction Manual for version 7.3x.
C70, FlexLogic, FlexElement, FlexCurve, FlexAnalog, FlexInteger, FlexState, EnerVista,
CyberSentry, HardFiber, Digital Energy, Multilin, and GE Multilin are trademarks or
registered trademarks of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin. The content of this manual is for informational use only and is subject to
change without notice.
Part number: 1601-9015-AB2 (September 2015)

C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL iii
C70 Capacitor Bank Protection and Control System
Table of contents
1 INTRODUCTION 1.1 Safety symbols and definitions...................................................................... 1-1
1.1.1 General cautions and warnings...................................................................................... 1-1
1.2 For further assistance ..................................................................................... 1-2
2PRODUCT
DESCRIPTION
2.1 Product description.......................................................................................... 2-1
2.2 Security .............................................................................................................. 2-3
2.3 Order codes ....................................................................................................... 2-7
2.3.1 Order codes with enhanced CT/VT modules............................................................. 2-8
2.3.2 Order codes with process bus modules....................................................................2-10
2.3.3 Replacement modules.......................................................................................................2-12
2.4 Signal processing ...........................................................................................2-15
2.4.1 UR signal processing ..........................................................................................................2-15
2.5 Specifications..................................................................................................2-17
2.5.1 Protection elements............................................................................................................2-17
2.5.2 User-programmable elements ......................................................................................2-22
2.5.3 Monitoring................................................................................................................................2-23
2.5.4 Metering....................................................................................................................................2-24
2.5.5 Inputs .........................................................................................................................................2-25
2.5.6 Power supply..........................................................................................................................2-26
2.5.7 Outputs .....................................................................................................................................2-27
2.5.8 Communications ..................................................................................................................2-29
2.5.9 Inter-relay communications ...........................................................................................2-30
2.5.10 Environmental........................................................................................................................2-31
2.5.11 Type tests.................................................................................................................................2-32
2.5.12 Production tests....................................................................................................................2-32
2.5.13 Approvals .................................................................................................................................2-33
2.5.14 Maintenance...........................................................................................................................2-33
3 INSTALLATION 3.1 Unpack and inspect ......................................................................................... 3-1
3.2 Panel cutouts .................................................................................................... 3-2
3.2.1 Horizontal units....................................................................................................................... 3-2
3.2.2 Vertical units............................................................................................................................. 3-3
3.2.3 Rear terminal layout ............................................................................................................. 3-8
3.3 Wiring ................................................................................................................. 3-9

iv C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
TABLE OF CONTENTS
3.3.1 Typical wiring............................................................................................................................3-9
3.3.2 Dielectric strength ...............................................................................................................3-10
3.3.3 Control power........................................................................................................................3-10
3.3.4 CT/VT modules ......................................................................................................................3-11
3.3.5 Process bus modules .........................................................................................................3-13
3.3.6 Contact inputs and outputs............................................................................................3-13
3.3.7 Transducer inputs and outputs.....................................................................................3-20
3.3.8 RS232 faceplate port..........................................................................................................3-22
3.3.9 CPU communication ports ..............................................................................................3-22
3.3.10 IRIG-B.........................................................................................................................................3-24
3.4 Direct input and output communications .................................................3-25
3.4.1 Description..............................................................................................................................3-25
3.4.2 Fiber: LED and ELED transmitters.................................................................................3-27
3.4.3 G.703 interface......................................................................................................................3-27
3.4.4 RS422 interface.....................................................................................................................3-31
3.4.5 IEEE C37.94 interface .........................................................................................................3-33
3.5 Activate relay ..................................................................................................3-36
3.6 Install software...............................................................................................3-37
3.6.1 EnerVista communication overview ...........................................................................3-37
3.6.2 System requirements.........................................................................................................3-38
3.6.3 Install software .....................................................................................................................3-38
3.7 Configure the C70 for software access ......................................................3-39
3.7.1 Configure serial communication..................................................................................3-40
3.7.2 Configure Ethernet communication ...........................................................................3-41
3.7.3 Automatic discovery of UR devices.............................................................................3-42
3.8 Connect to the C70.........................................................................................3-42
3.8.1 Connect to the C70 in EnerVista ...................................................................................3-42
3.8.2 Use Quick Connect via the front panel RS232 port .............................................3-43
3.8.3 Use Quick Connect via a rear Ethernet port............................................................3-44
3.9 Set up CyberSentry and change default password..................................3-49
4 INTERFACES 4.1 EnerVista software interface..........................................................................4-1
4.1.1 Introduction...............................................................................................................................4-1
4.1.2 Settings files ..............................................................................................................................4-1
4.1.3 Event viewing............................................................................................................................4-2
4.1.4 File support ................................................................................................................................4-2
4.1.5 EnerVista main window .......................................................................................................4-2
4.1.6 Settings templates .................................................................................................................4-3
4.1.7 Secure and lock FlexLogic equations............................................................................4-8
4.1.8 Settings file traceability.....................................................................................................4-10
4.2 Front panel interface .....................................................................................4-12
4.2.1 Front panel display..............................................................................................................4-12
4.2.2 Front panel keypad.............................................................................................................4-12
4.2.3 Menu navigation ..................................................................................................................4-13
4.2.4 Menu hierarchy.....................................................................................................................4-13
4.2.5 Changing settings................................................................................................................4-14
4.2.6 Faceplate.................................................................................................................................4-15
4.2.7 LED indicators........................................................................................................................4-17
4.2.8 Custom LED labeling ..........................................................................................................4-20
4.2.9 Breaker control .....................................................................................................................4-25
4.2.10 Change passwords .............................................................................................................4-26
4.2.11 Invalid password entry......................................................................................................4-27
4.3 Logic diagrams ...............................................................................................4-28

TABLE OF CONTENTS
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL v
5 SETTINGS 5.1 Settings menu ................................................................................................... 5-1
5.2 Overview ............................................................................................................ 5-4
5.2.1 Introduction to elements .................................................................................................... 5-4
5.2.2 Introduction to AC sources ................................................................................................ 5-5
5.3 Product setup.................................................................................................... 5-7
5.3.1 Security ....................................................................................................................................... 5-7
5.3.2 Display properties ................................................................................................................5-25
5.3.3 Clear relay records ..............................................................................................................5-27
5.3.4 Communications ..................................................................................................................5-27
5.3.5 Modbus user map ................................................................................................................5-82
5.3.6 Real-time clock......................................................................................................................5-82
5.3.7 User-programmable fault report..................................................................................5-86
5.3.8 Oscillography .........................................................................................................................5-87
5.3.9 Data logger .............................................................................................................................5-89
5.3.10 User-programmable LEDs ...............................................................................................5-90
5.3.11 User-programmable self tests.......................................................................................5-94
5.3.12 Control pushbuttons...........................................................................................................5-94
5.3.13 User-programmable pushbuttons...............................................................................5-96
5.3.14 Flex state parameters.....................................................................................................5-101
5.3.15 User-definable displays..................................................................................................5-102
5.3.16 Direct inputs and outputs..............................................................................................5-104
5.3.17 Installation............................................................................................................................5-111
5.4 Remote resources ........................................................................................5-111
5.4.1 Remote resources configuration ...............................................................................5-111
5.5 System setup.................................................................................................5-112
5.5.1 AC inputs ...............................................................................................................................5-112
5.5.2 Power system......................................................................................................................5-114
5.5.3 Signal sources.....................................................................................................................5-114
5.5.4 Breakers.................................................................................................................................5-117
5.5.5 Disconnect switches........................................................................................................5-122
5.5.6 FlexCurves ............................................................................................................................5-125
5.6 FlexLogic ........................................................................................................5-132
5.6.1 FlexLogic operands ..........................................................................................................5-132
5.6.2 FlexLogic rules ....................................................................................................................5-145
5.6.3 FlexLogic evaluation ........................................................................................................5-145
5.6.4 FlexLogic example ............................................................................................................5-146
5.6.5 FlexLogic equation editor..............................................................................................5-151
5.6.6 FlexLogic timers .................................................................................................................5-151
5.6.7 FlexElements .......................................................................................................................5-151
5.6.8 Non-volatile latches .........................................................................................................5-155
5.7 Grouped elements........................................................................................5-156
5.7.1 Overview................................................................................................................................5-156
5.7.2 Setting group 1...................................................................................................................5-156
5.7.3 Phase current......................................................................................................................5-157
5.7.4 Neutral current...................................................................................................................5-171
5.7.5 Ground current...................................................................................................................5-183
5.7.6 Negative sequence current..........................................................................................5-185
5.7.7 Breaker failure (ANSI 50BF)...........................................................................................5-191
5.7.8 Voltage elements...............................................................................................................5-200
5.8 Control elements..........................................................................................5-217
5.8.1 Overview................................................................................................................................5-217
5.8.2 Trip bus...................................................................................................................................5-217
5.8.3 Setting groups.....................................................................................................................5-219
5.8.4 Selector switch ...................................................................................................................5-220
5.8.5 Time of day timers ............................................................................................................5-227

vi C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
TABLE OF CONTENTS
5.8.6 Capacitor control .............................................................................................................. 5-228
5.8.7 Automatic voltage regulator ....................................................................................... 5-233
5.8.8 Digital elements................................................................................................................. 5-237
5.8.9 Digital counters.................................................................................................................. 5-240
5.8.10 Monitoring elements .......................................................................................................5-242
5.9 Inputs/outputs ..............................................................................................5-254
5.9.1 Contact inputs.................................................................................................................... 5-254
5.9.2 Virtual inputs....................................................................................................................... 5-256
5.9.3 Contact outputs................................................................................................................. 5-257
5.9.4 Virtual outputs.................................................................................................................... 5-260
5.9.5 Resetting ............................................................................................................................... 5-260
5.9.6 Direct inputs and outputs ............................................................................................. 5-261
5.10 Transducer inputs/outputs.........................................................................5-265
5.10.1 DCmA inputs ....................................................................................................................... 5-265
5.10.2 RTD inputs ............................................................................................................................ 5-266
5.10.3 DCmA outputs .................................................................................................................... 5-267
5.11 Testing............................................................................................................5-270
5.11.1 Test mode function .......................................................................................................... 5-270
5.11.2 Test mode forcing............................................................................................................. 5-271
5.11.3 Force contact inputs ....................................................................................................... 5-272
5.11.4 Force contact outputs .................................................................................................... 5-272
6 ACTUAL VALUES 6.1 Actual values menu.......................................................................................... 6-1
6.2 Status..................................................................................................................6-3
6.2.1 Contact inputs..........................................................................................................................6-3
6.2.2 Virtual inputs.............................................................................................................................6-3
6.2.3 RxGOOSE boolean inputs ....................................................................................................6-3
6.2.4 RxGOOSE DPS inputs.............................................................................................................6-4
6.2.5 Contact outputs.......................................................................................................................6-4
6.2.6 Virtual outputs..........................................................................................................................6-4
6.2.7 RxGOOSE status.......................................................................................................................6-4
6.2.8 RxGOOSE statistics.................................................................................................................6-5
6.2.9 Digital counters........................................................................................................................6-5
6.2.10 Selector switches ....................................................................................................................6-5
6.2.11 Time of day timers..................................................................................................................6-6
6.2.12 Flex States ..................................................................................................................................6-6
6.2.13 Ethernet.......................................................................................................................................6-6
6.2.14 Real time clock synchronizing ..........................................................................................6-6
6.2.15 Direct inputs ..............................................................................................................................6-7
6.2.16 Direct devices status.............................................................................................................6-8
6.2.17 Remaining connection status ...........................................................................................6-8
6.2.18 Parallel Redundancy Protocol (PRP) ...............................................................................6-9
6.3 Metering.............................................................................................................6-9
6.3.1 Metering conventions...........................................................................................................6-9
6.3.2 Sources.....................................................................................................................................6-13
6.3.3 Capacitor control .................................................................................................................6-17
6.3.4 Capacitor bank......................................................................................................................6-18
6.3.5 Tracking frequency .............................................................................................................6-19
6.3.6 FlexElements..........................................................................................................................6-19
6.3.7 RxGOOSE analogs................................................................................................................6-19
6.3.8 Transducer inputs/outputs..............................................................................................6-20
6.4 Records.............................................................................................................6-20
6.4.1 User-programmable fault reports ............................................................................... 6-20
6.4.2 Event records.........................................................................................................................6-20
6.4.3 Oscillography.........................................................................................................................6-21

TABLE OF CONTENTS
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL vii
6.4.4 Data logger .............................................................................................................................6-21
6.5 Product information ......................................................................................6-22
6.5.1 Model information................................................................................................................6-22
6.5.2 Firmware revisions ..............................................................................................................6-22
7 COMMANDS AND
TARGETS
7.1 Commands menu ............................................................................................. 7-1
7.1.1 Capacitor bank automatic setting ................................................................................. 7-2
7.1.2 Virtual inputs ............................................................................................................................ 7-6
7.1.3 Clear records ............................................................................................................................ 7-6
7.1.4 Set date and time................................................................................................................... 7-7
7.1.5 Relay maintenance................................................................................................................ 7-7
7.1.6 Security ....................................................................................................................................... 7-8
7.2 Targets menu .................................................................................................... 7-9
7.2.1 Target messages.................................................................................................................... 7-9
7.2.2 Relay self-tests ........................................................................................................................ 7-9
8 APPLICATION OF
SETTINGS
8.1 Arrangement of shunt capacitor banks....................................................... 8-1
8.1.1 Overview..................................................................................................................................... 8-1
8.1.2 Externally fused capacitors ............................................................................................... 8-1
8.1.3 Internally fused capacitors................................................................................................8-2
8.1.4 Fuseless capacitors............................................................................................................... 8-2
8.1.5 Unfused capacitors ............................................................................................................... 8-3
8.2 Connections of shunt capacitor banks......................................................... 8-3
8.2.1 Grounded wye-connected banks................................................................................... 8-3
8.2.2 Ungrounded wye-connected banks.............................................................................. 8-3
8.2.3 Delta connected banks........................................................................................................ 8-4
8.2.4 H-configuration....................................................................................................................... 8-4
8.2.5 Tapped configuration........................................................................................................... 8-4
8.2.6 Summary.................................................................................................................................... 8-4
8.3 Protection methods for capacitor banks ..................................................... 8-5
8.3.1 Overview..................................................................................................................................... 8-5
8.3.2 Capacitor unbalance protection..................................................................................... 8-5
8.3.3 Protection for rack faults (arc-over within capacitor banks)...........................8-10
8.3.4 Overvoltage.............................................................................................................................8-10
8.3.5 Overcurrent.............................................................................................................................8-11
8.3.6 Loss of bus voltage..............................................................................................................8-11
8.4 Settings example............................................................................................8-11
8.4.1 Overview...................................................................................................................................8-11
8.4.2 VT and CT setup ....................................................................................................................8-12
8.4.3 Source assignment..............................................................................................................8-13
8.4.4 Bank unbalance calculations .........................................................................................8-14
8.4.5 Bank voltage differential settings.................................................................................8-16
8.4.6 Bank phase current unbalance settings ...................................................................8-18
8.4.7 Bank phase overvoltage settings .................................................................................8-19
8.4.8 Bank phase undervoltage settings..............................................................................8-20
8.4.9 Bank overcurrent protection...........................................................................................8-21
9 THEORY OF
OPERATION
9.1 Overview ............................................................................................................ 9-1
9.1.1 General operation.................................................................................................................. 9-1
9.1.2 Bank phase overvoltage (ANSI 59B) .............................................................................. 9-1
9.1.3 Voltage differential (ANSI 87V) ......................................................................................... 9-3
9.1.4 Compensated bank neutral voltage unbalance (ANSI 59NU) ........................... 9-7
9.1.5 Phase current unbalance (ANSI 60P)...........................................................................9-10

viii C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
TABLE OF CONTENTS
9.1.6 Neutral current unbalance (ANSI 60N).......................................................................9-13
10 MAINTENANCE 10.1 General maintenance ....................................................................................10-1
10.1.1 In-service maintenance....................................................................................................10-1
10.1.2 Out-of-service maintenance ..........................................................................................10-1
10.1.3 Unscheduled maintenance (system interruption) ................................................10-2
10.2 Back up and restore settings .......................................................................10-2
10.2.1 Back up settings...................................................................................................................10-2
10.2.2 Restore settings....................................................................................................................10-3
10.3 Upgrade firmware ..........................................................................................10-4
10.4 Upgrade software...........................................................................................10-5
10.5 Replace module ..............................................................................................10-6
10.6 Battery..............................................................................................................10-7
10.6.1 Replace battery for RH/RL power supply .................................................................10-7
10.6.2 Replace battery for SH/SL power supply..................................................................10-8
10.6.3 Dispose of battery ...............................................................................................................10-9
10.7 Clear files and data after uninstall ...........................................................10-12
10.8 Repairs............................................................................................................10-13
10.9 Storage ...........................................................................................................10-13
10.10Disposal..........................................................................................................10-13
AFLEXANALOG
OPERANDS
A.1 FlexAnalog items .............................................................................................A-1
B RADIUS SERVER
CONFIGURATION
B.1 RADIUS server configuration .........................................................................B-1
C MISCELLANEOUS C.1 Warranty ...........................................................................................................C-1
C.2 Revision history ................................................................................................C-1
ABBREVIATIONS
INDEX

C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL 1-1
C70 Capacitor Bank Protection and Control System
Chapter 1: Introduction
Introduction
This chapter outlines safety and technical support information.
1.1 Safety symbols and definitions
Before attempting to install or use the device, review all safety indicators in this document to help prevent injury,
equipment damage, or downtime.
The following safety and equipment symbols are used in this document.
1.1.1 General cautions and warnings
The following general safety precautions and warnings apply.
Follow the requirements of this manual, including adequate wiring size and type, terminal torque settings, voltage,
current magnitudes applied, and adequate isolation/clearance in external wiring from high to low voltage circuits.
Use the device only for its intended purpose and application.
Ensure that all ground paths are uncompromised for safety purposes during device operation and service.
Ensure that the control power applied to the device, the AC current, and voltage input match the ratings specified on
the relay nameplate. Do not apply current or voltage in excess of the specified limits.
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Indicates practices not related to personal injury.
DANGER
Ensure that all connections to the product are correct so as to avoid accidental risk of shock
and/or fire, for example such as can arise from high voltage connected to low voltage terminals.

1-2 C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
FOR FURTHER ASSISTANCE CHAPTER 1: INTRODUCTION
1
Only qualified personnel are to operate the device. Such personnel must be thoroughly familiar with all safety
cautions and warnings in this manual and with applicable country, regional, utility, and plant safety regulations.
Hazardous voltages can exist in the power supply and at the device connection to current transformers, voltage
transformers, control, and test circuit terminals. Make sure all sources of such voltages are isolated prior to
attempting work on the device.
Hazardous voltages can exist when opening the secondary circuits of live current transformers. Make sure that
current transformer secondary circuits are shorted out before making or removing any connection to the current
transformer (CT) input terminals of the device.
For tests with secondary test equipment, ensure that no other sources of voltages or currents are connected to such
equipment and that trip and close commands to the circuit breakers or other switching apparatus are isolated,
unless this is required by the test procedure and is specified by appropriate utility/plant procedure.
When the device is used to control primary equipment, such as circuit breakers, isolators, and other switching
apparatus, all control circuits from the device to the primary equipment must be isolated while personnel are
working on or around this primary equipment to prevent any inadvertent command from this device.
Use an external disconnect to isolate the mains voltage supply.
1.2 For further assistance
For product support, contact the information and call center as follows:
GE Digital Energy
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Worldwide telephone: +1 905 927 7070
Europe/Middle East/Africa telephone: +34 94 485 88 54
North America toll-free: 1 800 547 8629
Fax: +1 905 927 5098
Website: http://www.gedigitalenergy.com/multilin
CAUTION
LED transmitters are classified as IEC 60825-1 Accessible Emission Limit (AEL) Class 1M. Class 1M
devices are considered safe to the unaided eye. Do not view directly with optical instruments.
NOTICE
This product is rated to Class A emissions levels and is to be used in Utility, Substation Industrial
environments. Not to be used near electronic devices rated for Class B levels.

C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL 2-1
C70 Capacitor Bank Protection and Control System
Chapter 2: Product description
Product descript ion
This chapter outlines the product, order codes, and specifications.
2.1 Product description
The C70 Capacitor Bank Protection and Control System is part of the Universal Relay (UR) series of products. It is a
microprocessor-based relay for protection and control of small, medium, and large three-phase capacitor banks. The relay
can be ordered with up to three current transformer/voltage transformer (CT/VT) modules, allowing for flexible application
in variety of bank configurations.
The key protection functions cover grounded and ungrounded, single and parallel banks. Sensitive protection functions
support compensation for both external (system) unbalance and inherent unbalance of the capacitor bank itself. Both
voltage and current-based balance protection functions are available. Algorithms are developed to automatically select
compensation settings after repairs or other alternations of the bank.
The relay supports a variety of bank configurations through flexible configurations of its AC inputs, installed voltage and
current transformers, and resulting protection techniques.
The relay incorporates an automatic voltage regulator (AVR) responding to voltage, reactive power, or power factor. A
separate timer function initiates controls on a pre-defined time/date basis. These on-off type controls are meant to
automatically close or open the associated breaker. A supervisory function is provided to program the local/remote, auto/
manual functionality, temporary inhibit closing after tripping, and other auxiliary functions, such as operation counters.
A capacitor control element provides remote/local and auto/manual control regulation, trip/close interlocking, and seal-in.
A user-programmable time delay inhibits closing until after the bank discharges itself to a safe level.
Up to six contact input/output modules can be ordered. The relay can also equipped with a serial 64/128 kbps direct input/
output module for fast and reliable peer-to-peer communication with other UR-series devices.
The C70 metering functions include true root mean square (RMS) and phasors for currents and voltages, current and
voltage harmonics and total harmonic distortion (THD), symmetrical components, frequency, power, power factor.
Diagnostic features include an event recorder capable of storing 1024 time-tagged events, oscillography capable of
storing up to 64 records with programmable trigger, content and sampling rate, and data logger acquisition of up to 16
channels, with programmable content and sampling rate. The internal clock used for time-tagging can be synchronized
with an IRIG-B signal, using the Simple Network Time Protocol (SNTP) over the Ethernet port, or using the Precision Time
Protocol (PTP). This precise time stamping allows the sequence of events to be determined throughout the system. Events
can also be programmed (via FlexLogic™ equations) to trigger oscillography data capture that can be set to record the
measured parameters before and after the event for viewing on a computer. These tools significantly reduce
troubleshooting time and simplify report generation in the event of a system fault.

2-2 C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
PRODUCT DESCRIPTION CHAPTER 2: PRODUCT DESCRIPTION
2
Several options are available for communication. A faceplate RS232 port can be used to connect to a computer to
program settings and monitor actual values. The rear RS485 port allows independent access by operating and engineering
staff. It can be connected to system computers with baud rates up to 115.2 kbps. All serial ports use the Modbus RTU
protocol. The IEC 60870-5-103 protocol is supported on the RS485 interface. Also only one of the DNP, IEC 60870-5-103,
and IEC 60870-5-104 protocols can be enabled at any time on the relay. When the IEC 60870-5-103 protocol is chosen, the
RS485 port has a fixed even parity and the baud rate can be either 9.6 kbps or 19.2 kbps. The 100Base-FX or 100Base-TX
Ethernet interface provides fast, reliable communications in noisy environments. The Ethernet port supports IEC 61850,
Modbus/TCP, TFTP, and PTP (according to IEEE Std. 1588-2008 or IEC 61588), and it allows access to the relay via any
standard web browser (C70 web pages). The IEC 60870-5-104 protocol is supported on the Ethernet port. The Ethernet port
also supports the Parallel Redundancy Protocol (PRP) of IEC 62439-3 (clause 4, 2012) when purchased as an option.
Settings and actual values can be accessed from the front panel or EnerVista software.
The C70 uses flash memory technology that allows field upgrading as new features are added. Firmware and software are
upgradable.
The following single-line diagram illustrates the relay functionality using American National Standards Institute (ANSI)
device numbers.
Table 2-1: ANSI device numbers and functions supported
Device
number Function Device
number Function
27P Phase undervoltage 59N Neutral overvoltage
50BF Breaker failure 59NU Neutral voltage unbalance
50DD Disturbance detector 59P Phase overvoltage
50G Ground instantaneous overcurrent 59X Auxiliary overvoltage
50N Neutral instantaneous overcurrent 59_2 Negative-sequence overvoltage
50P Phase instantaneous overcurrent 60N Bank neutral current unbalance
50_2 Negative-sequence instantaneous overcurrent 60P Bank phase current unbalance
51G Ground time overcurrent 67N Neutral directional overcurrent
51N Neutral time overcurrent 67P Phase directional overcurrent
51P Phase time overcurrent 67_2 Negative-sequence directional overcurrent
51_2 Negative-sequence time overcurrent 87V Bank voltage differential
59B Bank phase overvoltage

CHAPTER 2: PRODUCT DESCRIPTION SECURITY
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL 2-3
2
Figure 2-1: Single-line diagram
Table 2-2: Other device functions
2.2 Security
The following security features are available:
• Password security — Basic security present by default
• EnerVista security — Role-based access to various EnerVista software screens and configuration elements. The
feature is present by default in the EnerVista software.
Function Function Function
Breaker control Direct inputs and outputs (32) Time and date
Breaker flashover Event recorder Time synchronization over IRIG-B or IEEE
1588
Breaker restrike FlexElements™ (16) Time synchronization over SNTP
Capacitor control supervision FlexLogic equations Transducer inputs and outputs
Contact inputs (up to 96) Frequency metering User-definable displays
Contact outputs (up to 64) IEC 60870-5-103 communications User-programmable fault reports
Control pushbuttons IEC 61850 communications User-programmable LEDs
CyberSentry™ security Modbus communications User-programmable pushbuttons
Current metering: true RMS, phasors,
symmetrical Modbus user map User-programmable self-tests
Non-volatile latches Virtual inputs (64)
Data logger Non-volatile selector switch Virtual outputs (96)
Digital counters (8) Oscillography Voltage metering: true RMS, phasors,
symmetrical
Digital elements (48) Power metering
Disconnect switches Power factor metering Voltage regulator
DNP 3.0 or IEC 60870-5-104 protocol Setting groups (6) VT fuse failure
C70 Capacitor Bank Protection and Control System
52
Close
Metering
FlexElement Transducer
inputs
50DD 51N 50N
87V
50BF
51_2
51P
50_2
50P
27P
59X 59N
59_2
51G
50G
59NU 59B
60P
60N
Monitoring Trip
22 2 2 2
3
3
22
59P
2
22
834010A3.CDR
67P 67_2

2-4 C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
SECURITY CHAPTER 2: PRODUCT DESCRIPTION
2
• CyberSentry security — Advanced security available as a software option. When purchased, the options are
automatically enabled, and the default Password security and EnerVista security are disabled.
2.2.0.1 EnerVista security
The EnerVista security management system is a role-based access control (RBAC) system that allows an administrator to
manage the privileges of multiple users. This allows for access control of UR devices by multiple personnel within a
substation and conforms to the principles of RBAC as defined in ANSI INCITS 359-2004. The EnerVista security
management system is disabled by default to allow the administrator direct access to the EnerVista software after
installation. It is recommended that security be enabled before placing the device in service.
Basic password or enhanced CyberSentry security applies, depending on purchase.
2.2.0.2 Password security
Password security is a basic security feature present by default.
Two levels of password security are provided: command and setting. Use of a password for each level controls whether
users can enter commands and/or change settings.
The C70 supports password entry from a local or remote connection. Local access is defined as any access to settings or
commands via the faceplate interface. This includes both keypad entry and the through the faceplate RS232 port. Remote
access is defined as any access to settings or commands via any rear communications port. This includes both Ethernet
and RS485 connections. Any changes to the local or remote passwords enables this functionality.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the
corresponding connection password. If the connection is to the back of the C70, the remote password must be used. If the
connection is to the RS232 port of the faceplate, the local password applies.
Password access events are logged in the Event Recorder.
2.2.0.3 CyberSentry security
CyberSentry embedded security is a software option that provides advanced security services. When this option is
purchased, the basic password security is disabled automatically.
CyberSentry provides security through the following features:
• An Authentication, Authorization, Accounting (AAA) Remote Authentication Dial-In User Service (RADIUS) client that is
centrally managed, enables user attribution, provides accounting of all user activities, and uses secure standards-
based strong cryptography for authentication and credential protection
• A Role-Based Access Control (RBAC) system that provides a permission model that allows access to UR device
operations and configurations based on specific roles and individual user accounts configured on the AAA server (that
is, Administrator, Supervisor, Engineer, Operator, Observer roles)
• Security event reporting through the Syslog protocol for supporting Security Information Event Management (SIEM)
systems for centralized cybersecurity monitoring
• Strong encryption of all access and configuration network messages between the EnerVista software and UR devices
using the Secure Shell (SSH) protocol, the Advanced Encryption Standard (AES), and 128-bit keys in Galois Counter
Mode (GCM) as specified in the U.S. National Security Agency Suite B extension for SSH and approved by the National
Institute of Standards and Technology (NIST) FIPS-140-2 standards for cryptographic systems
Example: Administrative functions can be segmented away from common operator functions, or engineering type access,
all of which are defined by separate roles (see figure) so that access of UR devices by multiple personnel within a
substation is allowed. Permissions for each role are outlined in the next section.

CHAPTER 2: PRODUCT DESCRIPTION SECURITY
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL 2-5
2
Figure 2-2: CyberSentry user roles
The following types of authentication are supported by CyberSentry to access the UR device:
• Device Authentication (local UR device authenticates)
• Server Authentication (RADIUS server authenticates)
The EnerVista software allows access to functionality that is determined by the user role, which comes either from the local
UR device or the RADIUS server.
The EnerVista software has a device authentication option on the login screen for accessing the UR device. When the
"Device" button is selected, the UR uses its local authentication database and not the RADIUS server to authenticate the
user. In this case, it uses its built-in roles (Administrator, Engineer, Supervisor, Observer, Operator) as login names and the
associated passwords are stored on the UR device. As such, when using the local accounts, access is not user-attributable.
In cases where user-attributable access is required especially to facilitate auditable processes for compliance reasons, use
RADIUS authentication only.
When the "Server" Authentication Type option is selected, the UR uses the RADIUS server and not its local authentication
database to authenticate the user.
No password or security information is displayed in plain text by the EnerVista software or UR device, nor is such
information ever transmitted without cryptographic protection.
CyberSentry user roles
CyberSentry user roles (Administrator, Engineer, Operator, Supervisor, Observer) limit the levels of access to various UR
device functions. This means that the EnerVista software allows for access to functionality based on the user’s logged in
role.
Example: Observer cannot write any settings.
The table lists user roles and their corresponding capabilities.
Table 2-3: Permissions by user role for CyberSentry
Roles Administrator Engineer Operator Supervisor Observer
Complete access Complete access
except for
CyberSentry
Security
Command
menu Authorizes
writing Default role
Device Definition R R R R R
Settings
|---------- Product Setup
|--------------- Security
(CyberSentry) RW R R R R
|--------------- Supervisory See table notes R R See table
notes R
|--------------- Display Properties RW RW R R R
842838A2.CDR
Administrator
Engineer
Supervisor
Operator
Observer

2-6 C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
SECURITY CHAPTER 2: PRODUCT DESCRIPTION
2
|--------------- Clear Relay Records
(settings) RW RW R R R
|--------------- Communications RW RW R R R
|--------------- Modbus User Map RW RW R R R
|--------------- Real Time Clock RW RW R R R
|--------------- Oscillography RW RW R R R
|--------------- Data Logger RW RW R R R
|--------------- Demand RW RW R R R
|--------------- User-Programmable
LEDs RW RW R R R
|--------------- User-Programmable
Self Tests RW RW R R R
|--------------- Control Pushbuttons RW RW R R R
|--------------- User-Programmable
Pushbuttons RW RW R R R
|--------------- Flex state
Parameters RW RW R R R
|--------------- User-Definable
Displays RW RW R R R
|--------------- Direct I/O RW RW R R R
|--------------- Teleprotection RW RW R R R
|--------------- Installation RW RW R R R
|---------- System Setup RW RW R R R
|---------- FlexLogic RW RW R R R
|---------- Grouped Elements RW RW R R R
|---------- Control Elements RW RW R R R
|---------- Inputs / Outputs RW RW R R R
|--------------- Contact Inputs RW RW R R R
|--------------- Contact Input
threshold RW RW R R R
|--------------- Virtual Inputs RW RW R R R
|--------------- Contact Outputs RW RW R R R
|--------------- Virtual Outputs RW RW R R R
|--------------- Resetting RW RW R R R
|--------------- Direct Inputs RW RW R R R
|--------------- Direct Outputs RW RW R R R
|--------------- Teleprotection RW RW R R R
|--------------- Direct Analogs RW RW R R R
|--------------- Direct Integers RW RW R R R
|---------- Transducer I/O RW RW R R R
|---------- Testing RW RW R R R
|---------- Front Panel Labels Designer NA NA NA NA NA
|---------- Protection Summary NA NA NA NA NA
Commands RW RW RW R R
|---------- Virtual Inputs RW RW RW R R
|---------- Clear Records RW RW RW R R
|---------- Set Date and Time RW RW RW R R
User Displays R R R R R
Targets R R R R R
Roles Administrator Engineer Operator Supervisor Observer

CHAPTER 2: PRODUCT DESCRIPTION ORDER CODES
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL 2-7
2
Table Notes:
RW = read and write access
R = read access
Supervisor = RW (default), Administrator = R (default), Administrator = RW (only if Supervisor role is disabled)
NA = the permission is not enforced by CyberSentry security
CyberSentry server authentication
The UR has been designed to direct automatically the authentication requests based on user names. In this respect, local
account names on the UR are considered as reserved and not used on a RADIUS server.
The UR detects automatically whether an authentication request is to be handled remotely or locally. As there are five local
accounts possible on the UR, if the user ID credential does not match one of the five local accounts, the UR forwards
automatically the request to a RADIUS server when one is provided.
If a RADIUS server is provided, but is unreachable over the network, server authentication requests are denied. In this
situation, use local UR accounts to gain access to the UR system.
2.3 Order codes
The order code is on the product label and indicates the product options applicable.
The C70 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit and consists of the following
modules: power supply, CPU, CT/VT, contact input and output, transducer input and output, and inter-relay
communications. Module options are specified at the time of ordering.
Order codes are subject to change without notice. See the ordering page at
http://www.gedigitalenergy.com/multilin/order.htm for the latest options.
The order code depends on the mounting option (horizontal or vertical) and the type of CT/VT modules (enhanced
diagnostic CT/VT modules or HardFiberTM process bus modules). The HardFiber process bus module provides an interface
to HardFiber Bricks.
Actual Values R R R R R
|---------- Front panel labels designer R R R R R
|---------- Status R R R R R
|---------- Metering R R R R R
|---------- Transducer I/O R R R R R
|---------- Records R R R R R
|---------- Product Info R R R R R
Maintenance RW RW R R R
|---------- Modbus analyzer NA NA NA NA NA
|---------- Change front panel RW RW RW R R
|---------- Update firmware Yes No No No No
|---------- Retrieve file Yes No No No No
Roles Administrator Engineer Operator Supervisor Observer

2-8 C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
ORDER CODES CHAPTER 2: PRODUCT DESCRIPTION
2
2.3.1 Order codes with enhanced CT/VT modules
Table 2-4: C70 order codes for horizontal units
C70 - * ** - * * * - F ** - H ** - M ** - P ** - U ** -W/X ** Full Size Horizontal Mount
BASE UNIT C70 | | | | | | | | | | | Base Unit
CPU T | | | | | | | | | | RS485 with 3 100Base-FX Ethernet, multimode, SFP with LC
U | | | | | | | | | | RS485 with 1 100Base-TX Ethernet, SFP RJ-45 + 2 100Base-FX Ethernet, multimode,
SFP with LC
V | | | | | | | | | | RS485 with 3 100Base-TX Ethernet, SFP with RJ-45
SOFTWARE 00 | | | | | | | | | No software options
03 | | | | | | | | | IEC 61850
12 | | | | | | | | | Enhanced capacitor bank control (time and date, capacitor control supervision,
automatic voltage regulator)
13 | | | | | | | | | Enhanced capacitor bank control and IEC 61850
A0 | | | | | | | | | CyberSentry Lvl 1
A3 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850
AC | | | | | | | | | CyberSentry Lvl 1 and enhanced capacitor bank control
AD | | | | | | | | | CyberSentry Lvl 1, IEC 61850, and enhanced capacitor bank control
B0 | | | | | | | | | IEEE 1588
B3 | | | | | | | | | IEEE 1588 and IEC 61850
BC | | | | | | | | | IEEE 1588 and enhanced capacitor bank control
BD | | | | | | | | | IEEE 1588, IEC 61850, and enhanced capacitor bank control
C0 | | | | | | | | | Parallel Redundancy Protocol (PRP)
C3 | | | | | | | | | PRP and IEC 61850
CC | | | | | | | | | PRP and Enhanced Capacitor Bank Control
CD | | | | | | | | | PRP, IEC 61850, and Enhanced Capacitor Bank Control
D0 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1
D3 | | | | | | | | | IEEE 1588, CyberSentry Lvl 1, and IEC 61850
DC | | | | | | | | | IEEE 1588, CyberSentry Lvl 1, and enhanced capacitor bank control
DD | | | | | | | | | IEEE 1588, CyberSentry Lvl 1, IEC 61850, and enhanced capacitor bank control
E0 | | | | | | | | | IEEE 1588 and PRP
E3 | | | | | | | | | IEEE 1588, PRP, and IEC 61850
EC | | | | | | | | | IEEE 1588, PRP, enhanced capacitor bank control
ED | | | | | | | | | IEEE 1588, PRP, IEC 61850, and enhanced capacitor bank control
F0 | | | | | | | | | PRP and CyberSentry Lvl 1
F3 | | | | | | | | | PRP, CyberSentry Lvl 1, and IEC 61850
FC | | | | | | | | | PRP, CyberSentry Lvl 1, and enhanced capacitor bank control
FD | | | | | | | | | PRP, CyberSentry Lvl 1, IEC 61850, and enhanced capacitor bank control
G0 | | | | | | | | | IEEE 1588, PRP, and CyberSentry Lvl 1
G3 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
GC | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and enhanced capacitor bank control
GD | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, and enhanced capacitor bank control
J0 | | | | | | | | | IEC 60870-5-103
J3 | | | | | | | | | IEC 60870-5-103 and IEC 61850
JC | | | | | | | | | IEC 60870-5-103 and enhanced capacitor bank control
JD | | | | | | | | | IEC 60870-5-103, IEC 61850, and enhanced capacitor bank control
K0 | | | | | | | | | IEEE 1588, PRP, and IEC 60870-5-103
K3 | | | | | | | | | IEEE 1588, PRP, IEC 60870-5-103, and IEC 61850
KC | | | | | | | | | IEEE 1588, PRP, IEC 60870-5-103, and enhanced capacitor bank control
KD | | | | | | | | | IEEE 1588, PRP, IEC 60870-5-103, IEC 61850, and enhanced capacitor bank control
L0 | | | | | | | | | IEC 60870-5-103, IEEE 1588, PRP, and CyberSentry Lvl 1
L3 | | | | | | | | | IEC 60870-5-103, IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
LC | | | | | | | | | IEC 60870-5-103, IEEE 1588, PRP, CyberSentry Lvl 1, and enhanced capacitor bank
control
LD | | | | | | | | | IEC 60870-5-103, IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, and enhanced
capacitor bank control
MOUNT/
COATING
H | | | | | | | | Horizontal (19” rack)
A | | | | | | | | Horizontal (19” rack) with harsh-environment coating
FACEPLATE/ DISPLAY C | | | | | | | English display
P | | | | | | | English display with 4 small and 12 large programmable pushbuttons
D|||||| |Frenchdisplay
R|||||| |Russiandisplay
A|||||| |Chinesedisplay
K | | | | | | | Enhanced front panel with English display
M | | | | | | | Enhanced front panel with French display
Q | | | | | | | Enhanced front panel with Russian display
U | | | | | | | Enhanced front panel with Chinese display
L | | | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
W | | | | | | | Enhanced front panel with Turkish display
Y | | | | | | | Enhanced front panel with Turkish display and user-programmable pushbuttons
I | | | | | | | Enhanced front panel with German display
J | | | | | | | Enhanced front panel with German display and user-programmable pushbuttons

CHAPTER 2: PRODUCT DESCRIPTION ORDER CODES
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL 2-9
2
Table 2-5: C70 order codes for reduced-size vertical units
POWER
SUPPLY
H | | | | | | 125 / 250 V AC/DC power supply
L | | | | | | 24 to 48 V (DC only) power supply
ENHANCED DIAGNOSTICS CT/VT DSP
(requires all DSP to be enhanced
diagnostic)
||XX|XX |None
8L | 8L | 8L | Standard 4CT/4VT with enhanced diagnostics
8N | 8N | 8N | Standard 8CT with enhanced diagnostics
8V | 8V | 8V | Standard 8VT with enhanced diagnostics
CONTACT INPUTS/
OUTPUTS
XX XX XX XX XX None
4C 4C 4C 4C 4C 4 Solid-state (current with optional voltage) MOSFET outputs
6A 6A 6A 6A 6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
6B 6B 6B 6B 6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
6C 6C 6C 6C 6C 8 Form-C outputs
6D 6D 6D 6D 6D 16 Contact inputs
6E 6E 6E 6E 6E 4 Form-C outputs, 8 contact inputs
6F 6F 6F 6F 6F 8 Fast Form-C outputs
6G 6G 6G 6G 6G 4 Form-A (voltage with optional current) outputs, 8 contact inputs
6H 6H 6H 6H 6H 6 Form-A (voltage with optional current) outputs, 4 contact inputs
6K 6K 6K 6K 6K 4 Form-C and 4 Fast Form-C outputs
6L 6L 6L 6L 6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
6M 6M 6M 6M 6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
6N 6N 6N 6N 6N 4 Form-A (current with optional voltage) outputs, 8 contact inputs
6P 6P 6P 6P 6P 6 Form-A (current with optional voltage) outputs, 4 contact inputs
6R 6R 6R 6R 6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
6S 6S 6S 6S 6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
6T 6T 6T 6T 6T 4 Form-A (no monitoring) outputs, 8 contact inputs
6U 6U 6U 6U 6U 6 Form-A (no monitoring) outputs, 4 contact inputs
6V 6V 6V 6V 6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8
contact inputs
TRANSDUCER INPUTS/OUTPUTS (maximum of 3 per unit) 5A 5A 5A 5A 5A 4 DCmA inputs, 4 DCmA outputs (only one 5A module is allowed)
INTER-RELAY
COMMUNICATIONS
(select a maximum of 1 per unit)
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
2I Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1300 nm, single-mode, Laser
2J Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1550 nm, single-mode, Laser
77 IEEE C37.94, 820 nm, multimode, LED, 2 Channels
7H 820 nm, multi-mode, LED, 2 Channels
7I 1300 nm, multi-mode, LED, 2 Channels
7S G.703, 2 Channels
7W RS422, 2 Channels
C70 - * ** - * * * - F ** - H ** - M ** -P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
BASE UNIT C70 | | | | | | | | | Base Unit
CPU T | | | | | | | | RS485 with 3 100Base-FX Ethernet, multimode, SFP with LC
U | | | | | | | | RS485 with 1 100Base-TX Ethernet, SFP RJ-45 + 2 100Base-FX Ethernet, multimode, SFP with
LC
V | | | | | | | | RS485 with 3 100Base-TX Ethernet, SFP with RJ-45
SOFTWARE 00 | | | | | | | No software options
03 | | | | | | | IEC 61850
12 | | | | | | | Enhanced capacitor bank control (time and date, capacitor control supervision, automatic
voltage regulator)
13 | | | | | | | Enhanced capacitor bank control and IEC 61850
A0 | | | | | | | CyberSentry Lvl 1
A3 | | | | | | | CyberSentry Lvl 1 and IEC 61850
AC | | | | | | | CyberSentry Lvl 1 and enhanced capacitor bank control
AD | | | | | | | CyberSentry Lvl 1, IEC 61850, and enhanced capacitor bank control
B0 | | | | | | | IEEE 1588
B3 | | | | | | | IEEE 1588 and IEC 61850
BC | | | | | | | IEEE 1588 and enhanced capacitor bank control
BD | | | | | | | IEEE 1588, IEC 61850, and enhanced capacitor bank control
C0 | | | | | | | Parallel Redundancy Protocol (PRP)
C3 | | | | | | | PRP and IEC 61850
CC | | | | | | | PRP and enhanced capacitor bank control
CD | | | | | | | PRP, IEC 61850, and enhanced capacitor bank control
D0 | | | | | | | IEEE 1588 and CyberSentry Lvl 1
D3 | | | | | | | IEEE 1588, CyberSentry Lvl 1, and IEC 61850
DC | | | | | | | IEEE 1588, CyberSentry Lvl 1, and enhanced capacitor bank control
DD | | | | | | | IEEE 1588, CyberSentry Lvl 1, IEC 61850, and enhanced capacitor bank control
E0 | | | | | | | IEEE 1588 and PRP
E3 | | | | | | | IEEE 1588, PRP, and IEC 61850
EC | | | | | | | IEEE 1588, PRP, enhanced capacitor bank control
ED | | | | | | | IEEE 1588, PRP, IEC 61850, and enhanced capacitor bank control
F0 | | | | | | | PRP and CyberSentry Lvl 1
F3 | | | | | | | PRP, CyberSentry Lvl 1, and IEC 61850
FC | | | | | | | PRP, CyberSentry Lvl 1, and enhanced capacitor bank control
FD | | | | | | | PRP, CyberSentry Lvl 1, IEC 61850, and enhanced capacitor bank control
G0 | | | | | | | IEEE 1588, PRP, and CyberSentry Lvl 1
G3 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
GC | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and enhanced capacitor bank control
GD | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, and enhanced capacitor bank control
J0 | | | | | | | IEC 60870-5-103
J3 | | | | | | | IEC 60870-5-103 and IEC 61850
JC | | | | | | | IEC 60870-5-103 and enhanced capacitor bank control
JD | | | | | | | IEC 60870-5-103, IEC 61850, and enhanced capacitor bank control
K0 | | | | | | | IEEE 1588, PRP, and IEC 60870-5-103
K3 | | | | | | | IEEE 1588, PRP, IEC 60870-5-103, and IEC 61850
KC | | | | | | | IEEE 1588, PRP, IEC 60870-5-103, and enhanced capacitor bank control
KD | | | | | | | IEEE 1588, PRP, IEC 60870-5-103, IEC 61850, and enhanced capacitor bank control
L0 | | | | | | | IEC 60870-5-103, IEEE 1588, PRP, and CyberSentry Lvl 1
L3 | | | | | | | IEC 60870-5-103, IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
LC | | | | | | | IEC 60870-5-103, IEEE 1588, PRP, CyberSentry Lvl 1, and enhanced capacitor bank control
LD | | | | | | | IEC 60870-5-103, IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, and enhanced capacitor bank
control
MOUNT/
COATING
V | | | | | | Vertical (3/4 rack)
B | | | | | | Vertical (3/4 rack) with harsh-environment coating
FACEPLATE/ DISPLAY F | | | | | English display
D | | | | | French display
R | | | | | Russian display
A | | | | | Chinese display
K | | | | | Enhanced front panel with English display
M | | | | | Enhanced front panel with French display
Q | | | | | Enhanced front panel with Russian display
U | | | | | Enhanced front panel with Chinese display
C70 - * ** - * * * - F ** - H ** - M ** - P ** - U ** -W/X ** Full Size Horizontal Mount

2-10 C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
ORDER CODES CHAPTER 2: PRODUCT DESCRIPTION
2
2.3.2 Order codes with process bus modules
Table 2-6: C70 order codes for horizontal units with process bus
L | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
W | | | | | Enhanced front panel with Turkish display
Y | | | | | Enhanced front panel with Turkish display and user-programmable pushbuttons
I | | | | | Enhanced front panel with German display
J | | | | | Enhanced front panel with German display and user-programmable pushbuttons
POWER
SUPPLY
H | | | | 125 / 250 V AC/DC power supply
L | | | | 24 to 48 V (DC only) power supply
ENHANCED DIAGNOSTICS CT/VT
DSP
(requires all DSP to be enhanced
diagnostic)
XX | XX | None
8L | 8L | Standard 4CT/4VT with enhanced diagnostics
8N | 8N | Standard 8CT with enhanced diagnostics
8V | 8V | Standard 8VT with enhanced diagnostics
CONTACT INPUTS/OUTPUTS XX XX XX None
4C 4C 4C 4 Solid-state (current with optional voltage) MOSFET outputs
6A 6A 6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
6B 6B 6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
6C 6C 6C 8 Form-C outputs
6D 6D 6D 16 Contact inputs
6E 6E 6E 4 Form-C outputs, 8 contact inputs
6F 6F 6F 8 Fast Form-C outputs
6G 6G 6G 4 Form-A (voltage with optional current) outputs, 8 contact inputs
6H 6H 6H 6 Form-A (voltage with optional current) outputs, 4 contact inputs
6K 6K 6K 4 Form-C and 4 Fast Form-C outputs
6L 6L 6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
6M 6M 6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
6N 6N 6N 4 Form-A (current with optional voltage) outputs, 8 contact inputs
6P 6P 6P 6 Form-A (current with optional voltage) outputs, 4 contact inputs
6R 6R 6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
6S 6S 6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
6T 6T 6T 4 Form-A (no monitoring) outputs, 8 contact inputs
6U 6U 6U 6 Form-A (no monitoring) outputs, 4 contact inputs
6V 6V 6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 contact
inputs
TRANSDUCER INPUTS/OUTPUTS (maximum of 3 per
unit)
5A 5A 5A 4 DCmA inputs, 4 DCmA outputs (only one 5A module is allowed)
INTER-RELAY
COMMUNICATIONS
(select a maximum of 1 per unit)
For the last module, slot P is used for digital
input/output modules; slot R is used for inter-relay
communications modules.
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
2i Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1300 nm, single-mode, Laser
2J Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1300 nm, single-mode, Laser
77 IEEE C37.94, 820 nm, multimode, LED, 2 Channels
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels
7S G.703, 2 Channels
7W RS422, 2 Channels
C70 - * ** - * * * - F ** - H ** - M ** - P ** - U ** -W/X ** Full Size Horizontal Mount
BASE UNIT C70 | | | | | | | | | | | Base Unit
CPU T | | | | | | | | | | RS485 with 3 100Base-FX Ethernet, multimode, SFP with LC
U | | | | | | | | | | RS485 with 1 100Base-TX Ethernet, SFP RJ-45 + 2 100Base-FX Ethernet, multimode,
SFP with LC
V | | | | | | | | | | RS485 with 3 100Base-TX Ethernet, SFP with RJ-45
SOFTWARE 00 | | | | | | | | | No software options
03 | | | | | | | | | IEC 61850
12 | | | | | | | | | Enhanced capacitor bank control (time and date, capacitor control supervision,
automatic voltage regulator)
13 | | | | | | | | | Enhanced capacitor bank control and IEC 61850
A0 | | | | | | | | | CyberSentry Lvl 1
A3 | | | | | | | | | CyberSentry Lvl 1 and IEC 61850
AC | | | | | | | | | CyberSentry Lvl 1 and enhanced capacitor bank control
AD | | | | | | | | | CyberSentry Lvl 1, IEC 61850, and enhanced capacitor bank control
B0 | | | | | | | | | IEEE 1588
B3 | | | | | | | | | IEEE 1588 and IEC 61850
BC | | | | | | | | | IEEE 1588 and enhanced capacitor bank control
BD | | | | | | | | | IEEE 1588, IEC 61850, and enhanced capacitor bank control
C0 | | | | | | | | | Parallel Redundancy Protocol (PRP)
C3 | | | | | | | | | PRP and IEC 61850
CC | | | | | | | | | PRP and enhanced capacitor bank control
CD | | | | | | | | | PRP, IEC 61850, and enhanced capacitor bank control
D0 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1
D3 | | | | | | | | | IEEE 1588, CyberSentry Lvl 1, and IEC 61850
DC | | | | | | | | | IEEE 1588, CyberSentry Lvl 1, and enhanced capacitor bank control
DD | | | | | | | | | IEEE 1588, CyberSentry Lvl 1, IEC 61850, and enhanced capacitor bank control
E0 | | | | | | | | | IEEE 1588 and PRP
E3 | | | | | | | | | IEEE 1588, PRP, and IEC 61850
EC | | | | | | | | | IEEE 1588, PRP, enhanced capacitor bank control
ED | | | | | | | | | IEEE 1588, PRP, IEC 61850, and enhanced capacitor bank control
F0 | | | | | | | | | PRP and CyberSentry Lvl 1
F3 | | | | | | | | | PRP, CyberSentry Lvl 1, and IEC 61850
FC | | | | | | | | | PRP, CyberSentry Lvl 1, and enhanced capacitor bank control
FD | | | | | | | | | PRP, CyberSentry Lvl 1, IEC 61850, and enhanced capacitor bank control
G0 | | | | | | | | | IEEE 1588, PRP, and CyberSentry Lvl 1
G3 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
GC | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and enhanced capacitor bank control
GD | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, IEC 61850, and enhanced capacitor bank control
J0 | | | | | | | | | IEC 60870-5-103
J3 | | | | | | | | | IEC 60870-5-103 and IEC 61850
JC | | | | | | | | | IEC 60870-5-103 and enhanced capacitor bank control
JD | | | | | | | | | IEC 60870-5-103, IEC 61850, and enhanced capacitor bank control
K0 | | | | | | | | | IEEE 1588, PRP, and IEC 60870-5-103
K3 | | | | | | | | | IEEE 1588, PRP, IEC 60870-5-103, and IEC 61850
KC | | | | | | | | | IEEE 1588, PRP, IEC 60870-5-103, and enhanced capacitor bank control
KD | | | | | | | | | IEEE 1588, PRP, IEC 60870-5-103, IEC 61850, and enhanced capacitor bank control
C70 - * ** - * * * - F ** - H ** - M ** -P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
Other manuals for C70
4
Table of contents
Other GE Control System manuals

GE
GE SPEEDTRONIC Mark V User manual

GE
GE Multilin GEK-113328A User manual

GE
GE Multilin MM300 Operating instructions

GE
GE Multilin DGT Series User manual

GE
GE Mark VIe Parts list manual

GE
GE TRANSFORMER MANAGEMENT RELAY 745 User manual

GE
GE WH12X10457 Configuration guide

GE
GE PACSystems RX7i User manual

GE
GE Mark VIe Manual

GE
GE Multilin MM300 User manual