Alarm 1 SPEEDTRONICMark V Annunciator Troubleshooting Chart
10
ÁÁ
ÁÁ
ÁÁ
187
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
L86S
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Auto Synchronizing
Lockout
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Auto synchronizing self—
checking system has de-
tected a synchronizing
equipment abnormality.
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
Investigate synchronization system to deter-
mine exact cause of problem.
ÁÁ
188
ÁÁÁÁ
L27BN_ALM
ÁÁÁÁÁÁ
Bus Undervoltage –
No Auto Synch
ÁÁÁÁÁÁ
Bus synchronizing poten-
tial not available.
ÁÁÁÁÁÁÁÁÁÁ
Check bus PT fuses and wiring. Do not use
auto synchronizing or manual synchroniz-
ing until problem is resolved.
ÁÁ
ÁÁ
ÁÁ
189
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
L3Z
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Failure to Synchronize
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Unit did not synchronize
and close generator break-
er within the normal ex-
pected time (15 seconds).
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
Check all signals going making up the L4
logic signal to determine which caused the
problem or determine the cause of lack of
flame establishment.
ÁÁ
ÁÁ
190
ÁÁÁÁ
ÁÁÁÁ
L94EK
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Exciter Rect Cooling
Trouble — Trip 52G
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Breaker has tripped and
machine is at FSNL be-
cause of problem with ex-
citer rectifier cooling.
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
Investigate exciter rectifier cooling system.
ÁÁ
191
ÁÁÁÁ
L30EK
ÁÁÁÁÁÁ
Prim Exciter Rect Cooling
Fan Trouble
ÁÁÁÁÁÁ
Problem with primary ex-
citer rectifier cooling fan.
ÁÁÁÁÁÁÁÁÁÁ
Determine and correct problem with prima-
ry exciter rectifier cooling fan.
ÁÁ
192
ÁÁÁÁ
L30EKR
ÁÁÁÁÁÁ
Stby Exciter Rect Cooling
Fan Running
ÁÁÁÁÁÁ
Problem with primary ex-
citer rectifier cooling fan.
ÁÁÁÁÁÁÁÁÁÁ
Determine and correct problem with prima-
ry exciter rectifier cooling fan.
ÁÁ
193
ÁÁÁÁ
L26SFH_ALM
ÁÁÁÁÁÁ
Exciter Rectifier Bridge
Temp High
ÁÁÁÁÁÁ
Possible cooling system
problem.
ÁÁÁÁÁÁÁÁÁÁ
Check exciter rectifier cooling system.
194
L59E_ALM
Exciter Overvoltage
Excessive field volts have
been detected.
Check exciter.
ÁÁ
ÁÁ
ÁÁ
195
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
L49GH_ALM
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Generator Stator Temp
High
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Generator stator tempera-
ture is excessive caused by
lack of cooling or over-
load.
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
The generator should not be operated when
the stator temperature is excessive. Check
cooling system, reduce overload on genera-
tor.
ÁÁ
ÁÁ
196
ÁÁÁÁ
ÁÁÁÁ
L86TGT_ALM
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Generator Differential Trip
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
A generator panel protec-
tive device has tripped the
86G lockout relay.
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
Determine which protective device tripped
the 86G and correct the abnormality that
precipitated the trip.
ÁÁ
ÁÁ
ÁÁ
ÁÁ
197
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
L52G_ALM
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Generator Breaker Tripped
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Generator breaker has
been tripped by an auto-
matic protective device or
manually.
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
Determine device that tripped the breaker.
ÁÁ
ÁÁ
ÁÁ
198
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
L64F_ALM
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Generator Field Ground
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
A ground on the generator
field has been detected.
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
Operation of the generator with the field
grounded is not recommended as a second
ground could result in excessive damage to
the generator field.
ÁÁ
199
ÁÁÁÁ
L71WG_ALM
ÁÁÁÁÁÁ
Liquid Detected in Genera-
tor
ÁÁÁÁÁÁ
Excessive liquid in bottom
of generator.
ÁÁÁÁÁÁÁÁÁÁ
Remove liquid and take corrective action to
prevent recurrence of problem.
ÁÁ
ÁÁ
ÁÁ
200
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
L63BQL_ALM
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Generator Bearing Vacuum
Low
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Generator bearings are
sealed by vacuum. This
alarm indicates a potential
problem with the sealing
system.
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
Investigate generator bearing sealing sys-
tem.