GE 869 Use and care manual

GE
Digital Energy
Communications Guide
Product version: 1.4x
GE publication code: 1601-0451-A2 (GEK-119650A)
869
Motor Protection System
Motor Protection, Control and Management
1601-0451-A2

Copyright © 2015 GE Multilin Inc. All rights reserved.
869 Motor Protection System Instruction Manual for version 1.4x.
869 Motor Protection System, EnerVista, EnerVista Launchpad, EnerVista 8 Series Setup,
FlexLogic, FlexCurve, Digital Energy, Multilin, and GE Multilin are trademarks or registered
trademarks of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin. The content of this manual is for informational use only and is subject to
change without notice.
Part number: 1601-0451-A2 (July 2015)

869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
Table of Contents
1.INTRODUCTION 1 - 1
Communications.............................................................................................................................. 1 - 1
For Further Assistance ............................................................................................................................1 - 1
2.COMMUNICATION PORTS 2 - 1
RS485 Port........................................................................................................................................... 2 - 1
RS485 ..............................................................................................................................................................2 - 1
WiFi ......................................................................................................................................................... 2 - 2
WiFi Quick Start Procedure...................................................................................................................2 - 4
USB.......................................................................................................................................................... 2 - 5
Using the Quick Connect Feature via the USB Port...................................................................2 - 6
Ethernet Ports.................................................................................................................................... 2 - 6
Network Settings Menu ..........................................................................................................................2 - 7
Routing...........................................................................................................................................................2 - 8
3.TIME PROTOCOLS 3 - 1
Real-time Clock................................................................................................................................. 3 - 1
IEEE 1588 Precision Time Protocol (PTP) .........................................................................................3 - 1
PTP Status......................................................................................................................................................3 - 1
PTP Configuration......................................................................................................................................3 - 3
Clock................................................................................................................................................................3 - 5
IRIG-B...............................................................................................................................................................3 - 6
4.DNP 3 4 - 1
DNP communication ...................................................................................................................... 4 - 1
DNP device profile ........................................................................................................................... 4 - 5
DNP implementation...................................................................................................................... 4 - 8
5.DNP / IEC104 POINT LISTS 5 - 1
6.IEC 60870-5-104 6 - 1
Interoperability.................................................................................................................................. 6 - 3
7.IEC 60870-5-103 7 - 1
Cause of Transmission .................................................................................................................. 7 - 1
Communications Menus............................................................................................................... 7 - 2
Interoperability.................................................................................................................................. 7 - 4
Physical layer...............................................................................................................................................7 - 4
Electrical interface.....................................................................................................................................7 - 4
Optical interface.........................................................................................................................................7 - 4
Transmission speed..................................................................................................................................7 - 4
Link layer .......................................................................................................................................................7 - 4
Application layer ........................................................................................................................................7 - 5
Transmission mode for application data........................................................................................7 - 5
Common address of ASDU....................................................................................................................7 - 5
Selection of standard information numbers in monitor direction......................................7 - 5
Selection of standard information numbers in control direction........................................7 - 7

TOC-2 869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
Basic application functions.................................................................................................................. 7 - 8
Miscellaneous............................................................................................................................................. 7 - 8
8.IEC 61850 8 - 1
General ..................................................................................................................................................8 - 1
Functionality........................................................................................................................................8 - 4
The IEC 61850 Configurator.........................................................................................................8 - 4
Online and Offline Setup........................................................................................................................ 8 - 4
IEC 61850 Configurator Details.......................................................................................................... 8 - 6
ICD/CID........................................................................................................................................................... 8 - 7
Settings.......................................................................................................................................................... 8 - 9
Reports.........................................................................................................................................................8 - 12
Goose Transmission ..............................................................................................................................8 - 18
Goose Reception .....................................................................................................................................8 - 22
9.FILE TRANSFER PROTOCOLS 9 - 1
10.MODBUS PROTOCOL 10 - 1
Modbus Protocol............................................................................................................................10 - 2
Administrator Login and Commands via Modbus for 8 Series Relays...........................10 - 7
11.MODBUS MEMORY MAP 11 - 1
Reading the Event Recorder.....................................................................................................11 - 1
Reading Transient Recorder.....................................................................................................11 - 1
Reading Fault Reports................................................................................................................. 11 - 2
Accessing Data via the User Map ..........................................................................................11 - 2
Memory Map Organization .......................................................................................................11 - 3
MODBUS memory map...............................................................................................................11-3
Format Codes.............................................................................................................................11 - 146
Modbus Commands................................................................................................................11 - 339
12.APPENDIX A 12 - 1
Warranty............................................................................................................................................12 - 1
Revision history...............................................................................................................................12 - 1
Major Updates..........................................................................................................................................12 - 1

869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE 1-1
869 Motor Protection System
Chapter 1: Introduction
GE
Digital Energy
Introduction
The 869 Motor Protection, Control and Management System is a microprocessor-based
unit intended for the management and primary protection of medium and large sized
motors. Base relay models provide thermal overload and overcurrent protection plus a
number of current and voltage based backup functions.
Communications
The 869 has a two-stage communications capability. The base CPU supports Modbus
protocol through the Ethernet, USB, serial and WiFi port. In addition, the base CPU also
supports IEC 103, DNP serial, and TFTP protocol. Once the communications module option
is added to the base, the base Ethernet port becomes disabled but the two Ethernet ports
on the communications module have enhanced communications capabilities such as
IEC61850, IEC62439 parallel redundancy protocol and IEEE 1588 Precision Time Protocol.
The communications CPU also supports Modbus TCP, IEC 104, DNP TCP, TFTP, SFTP, and
SNTP protocol.
For Further Assistance
For product support, contact the information and call center as follows:
GE Digital Energy
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Worldwide telephone: +1 905 927 7070
Europe/Middle East/Africa telephone: +34 94 485 88 54
North America toll-free: 1 800 547 8629
Fax: +1 905 927 5098
Website: http://www.gedigitalenergy.com/multilin/

1-2 869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
COMMUNICATIONS CHAPTER 1: INTRODUCTION

869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE 2-1
869 Motor Protection System
Chapter 2: Communication Ports
GE
Digital Energy
Communicatio n Ports
The 869 has four communications ports: RS485, WiFi, USB, and Ethernet.
RS485 Port
SERIAL
RS485 port: ............................................................Isolated
Baud rates:.............................................................Supports 9600, 19200, 38400, 57600, and 115200 kbps
Response time:.....................................................10 ms typical
Parity:........................................................................None, Odd, Even
Protocol: ..................................................................Modbus RTU, DNP 3.0, IEC 60870-5-103
Maximum distance: ...........................................1200 m (4000 feet)
Isolation:..................................................................2 kV
RS485
On the rear card the 869 is equipped with one RS485 serial communication port and one
10/100 Mbps Ethernet port. The RS485 port has settings for baud rate and parity. It is
important that these parameters agree with the settings used on the computer or other
equipment connected to this port. A maximum of 32 relays can be daisy-chained and
connected to a DCS, PLC or a PC using the RS485 port.
Path: Setpoints > Device > Communications > RS485
BAUD RATE
Range: 9600, 19200, 38400, 57600, 115200
Default: 115200
PARITY
Range: None, Odd, Even
Default: None
PORT PROTOCOL
Range: Modbus, DNP 3.0, IEC 60870-5-103
Default: Modbus

2-2 869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
WIFI CHAPTER 2: COMMUNICATION PORTS
WiFi
WiFi refers to Wireless Local Area Networks (WLANs) that are based on the 802.11 set of
standards. WLANs are essentially providing Local Area Network (LAN) type of connectivity
but without the need of cables, which makes them more convenient for use in limited
spaces. WiFi works on top of the TCP/IP stack, the same as Ethernet. The signal strength
and its range is determined by the wireless device’s antenna technology and standard, the
best being IEEE 802.11n.
WiFi defines two modes of operation, namely ad-hoc, used for small deployments, and
infrastructure mode, which supports more robust types of security and better capabilities
for centralized management. The infrastructure mode requires an access point (AP).
Devices operating in this mode pass all data through the AP.
The WiFi module integrated on the 8-Series products conforms to IEEE 802.11b/g/n
standards. The 8-Series devices operate in infrastructure mode. Security is optional, but
enabled by default and it is advisable that it is left on, as wireless traffic is very susceptible
to cyber-attacks.
The security technology used is WPA2 (Wireless Protected Access version 2), based on the
IEEE 802.11i standard for data encryption. WPA2 is a second version of WPA technology,
designed to solve known security limitations found in one of the encryption algorithms
used by WPA, namely TKIP (Temporal Key Integrity Protocol). WPA2 uses CCMP (Counter
Mode with Cipher Block Chaining Message Authentication Code Protocol), which provides
an enhanced data cryptographic encapsulation mechanism based on AES (Advanced
Encryption Standard). CCMP makes WPA2 much stronger and secure than its predecessors,
WPA and WEP.
Several forms of WPA2 security keys exist. The 8-Series supports WPA2 PSK (Pre-Shared
Key), which utilizes 64 hexadecimal digits. The key may actually be entered as a string of 64
hexadecimal digits or as a passphrase of 8 to 32 printable ASCII characters. For user
convenience, the settings accept the key in the form of a passphrase. Internally the ASCII
passphrase is used for deriving a 256-bit key.
WiFi Settings
The following are the WiFi network settings for the 8-Series product. Only an Administrator
has the rights to change them.
Path: Setpoints > Device > Communications > WiFi

CHAPTER 2: COMMUNICATION PORTS WIFI
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE 2-3
WiFi Enable
This setting switches WiFi functionality on/off. By default WiFi is enabled in the basic
offering, but it is disabled in software options that offer CyberSentry.
WiFi IP Address / Subnet Mask
The default IP address is 192.168.0.x, where x is calculated as:
X = (modulo 242 of the last 3 digits of the serial number) + 12
This is to ensure uniqueness of the default IP address for all 8 Series devices present on one
wireless network and it creates a usable address space from 192.168.0.12 to
192.168.0.253 for 8 Series devices.
NOTE
NOTE: From the remaining range of unicast addresses 192.168.0.1 to 192.168.0.11, at least two
are going to be used for the AP and a laptop installed with the EnerVista software, which
will be used to configure the 8 Series devices. The AP should be configured with the
address 192.168.0.1 and mask 255.255.255.0 and have DHCP enabled with a DHCP range
from 192.168.0.2 to 192.168.0.11. This allows laptops, iPads and any other devices
(Android, iPhone) to connect to the local network without the need to statically configure
their own IP address and mask.
WiFi GWY IP Address
The setting specifies the address of the access point AP which the 8 Series device uses for
communicating over WiFi.
WiFi Security
The setting enables WiFi security. If set to “None”, there is no security and all traffic is open.
By default WiFi Security is set to WPA2-PSK.
WiFi SSID
The SSID is the public name of a wireless network. All of the wireless devices on a WLAN
must use the same SSID in order to communicate with each other. The default for the SSID
is provided by the vendor with the shipment of any new 8-Series device. It is recommended
that the customer modifies this name as needed after initial startup, to ensure unique
SSIDs if several WLANs are configured.
WiFi Enable:
Enabled
WiFi IP Address:
192.168.0.x
WiFi Subnet Mask:
255.255.255.0
WiFi GWY IP Address:
0.0.0.0
WiFi Security:
WPA2-PSK
WiFi SSID:
XXXXXXXX
Message
Message
Message
Message
Message
n
WiFi
n
Range: Enabled, Dis
Default: Enabled
abled
Range: Standard IPV4 address format
Default: 192.168.0.x
Range: Standard IPV4 mask format
Default: 255.255.255.0
Range: None, WPA2-PSK
Default: WPA2-PSK
Any name using up to 14 characters
Default: provided by vendor
WiFi WPA2 passphrase:
**********
Up to any 14 ASCII characters
Default: Provided by vendor
Message
Range: Standard IPV4 address format
Default: 0.0.0.0

2-4 869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
WIFI CHAPTER 2: COMMUNICATION PORTS
NOTE
NOTE: SSID broadcast should be disabled on AP. This provides some extra protection by requiring
a user to know an SSID before the user can connect to the device and making it harder for
casual outsiders looking for wireless networks to find the device and attempt to connect.
WiFi WPA2 Passphrase
The WPA2 Passphrase is used for generating the encryption key. The same passphrase
must be set on AP and on all devices communicating on the same WLAN. The 8-Series
device supports a string of up to 14 printable ASCII characters. Internally a 256-bit key is
calculated by applying the PBKDF2 key derivation function to this passphrase, using the
SSID as the salt and 4096 iterations of HMAC-SHA1.
The 8-Series devices are configured with a default passphrase, which is provided by the
vendor with the shipment of any new 8-Series device.
When choosing a new passphrase, the password complexity rules of CyberSentry must be
used (see CyberSentry details in the 869 Instruction manual).
This field is visible only if the security is set to WPA2-PSK.
NOTE
NOTE: Ideally the passphrase should be set through EnerVista and not directly from the Keypad,
where there are limitations in terms of space and types of characters supported. However,
for convenience, the key setting is available from the Keypad as well.
WiFi Status
A WiFi symbol is displayed in the caption area of the 8-Series product front panel. The
following table lists all possibilities for this icon:
WiFi Events
NOTE
NOTE: If the relay is in service mode and the settings are default a minor error is triggered.
WiFi Quick Start Procedure
The following provides the settings information and instructions to quickly setup WiFi.
Required Equipment
• 8-Series Relay with WiFi functionality
•PCwithWiFi
•AccessPoint
Quick Start Procedure
1. The PC WiFi Network Settings are as follows:
Passphrase: provided with the 8-Series relay
2. The Access Point Settings are given below:
WiFi State WiFi Icon Color
Disabled Icon is grey and crossed by a red line
Disconnected Grey
Connecting Yellow
Connected Green
Event Description
WiFi Connected This event is recorded to indicate a network connect.
WiFi Disconnected This event is recorded to indicate a network
disconnect.

CHAPTER 2: COMMUNICATION PORTS USB
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE 2-5
3. If the 8-Series relay(s) are in range, they automatically connect to the configured
Access Point.
4. Start EnerVista on a PC and use the Discover function, all relays within range appear
and are populated in Enervista for initial configuration and commissioning.
5. Once the relay is configured, change the 8-Series relay default WiFi SSID and
Passphrase settings before the relay goes into service.
Figure 2-1: Example of WiFi Deployment
USB
The USB parameters are as follows:
IP Address: 172.16.0.2
IP Mask: 255.255.255.0
IP Gateway: 172.16.0.1
FASTPATH: Whenever the device is rebooted, the USB cable needs to be unplugged and plugged in
again for proper communication to be established over USB.
FASTPATH: Connecting multiple 869 relays over USB to a single PC is not possible because in the case
of USB, the IP address of the device 172.16.0.2 is constant.
IP address: 192.168.0.1
Subnet Mask: 255.255.255.0
SSID: same as entered on the PC (SSID provided with the 8-Series relay)
Broadcast disabled
Security type: WPA2-PSK (WPA2-Personal)
Encryption: AES
Passphrase: same as entered on the PC (Passphrase provided with the 8-Series relay)
DHCP enabled range of 192.168.0.2 to 192.168.0.11

2-6 869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
ETHERNET PORTS CHAPTER 2: COMMUNICATION PORTS
Using the Quick Connect Feature via the USB Port
From the EnerVista 8 Series Setup software the Quick Connect button can be used to
establish a fast connection through the front panel USB port of an 869 relay.
Before starting, verify that the standard USB cable is properly connected from the laptop
computer to the front panel USB port.
1. Verify that the latest version of the EnerVista 8 Series Setup software is installed
(available from the GE EnerVista CD or online from http://www.gedigitalenergy.com/
multilin). See the software installation section in the 869 Motor Management
System instruction manual for installation details.
2. Open the 8-Series Setup.
3. Select the 869 device to start EnerVista 8 Series Setup.
4. Click the Quick Connect button to open the Quick Connect dialog box.
5. Set the Interface to USB, then click Connect.
6. The EnerVista 8 Series Setup software creates a site named “Quick Connect” with a
corresponding device also named “Quick Connect” and displays them on the upper-
left corner of the screen. Expand the sections to view data directly from the
869 device.
Ethernet Ports
The following communication offerings are available.
Base Offering
Modes: 10/100 Mbps
One Port: RJ45
Protocol: Modbus TCP, TFTP
Communications Card Option
Modes: 100 MB
Two Ports: ST (with this option both enabled ports are on the communications card; the
Ethernet port located on the base CPU is disabled)
Protocols: Modbus TCP, DNP 3.0 TCP, IEC 60870-5-104, IEC 61850 MMS Server/GOOSE,
IEEE 1588, SNTP, IEC 62439-3 clause 4 (PRP), TFTP, SFTP

CHAPTER 2: COMMUNICATION PORTS ETHERNET PORTS
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE 2-7
Network Settings Menu
The following are the network settings menu of the 869 to accommodate the features of
the 869 product. If the communications card is installed network port 1 is no longer
available. When using more than one Ethernet port, configure each to belong to a different
network or subnet using the IP addresses and mask, else communication becomes
unpredictable when more than one port is configured to the same subnet.
NOTE
NOTE: The softkeys and Down/Up key can be used to enter an IP address. When entering an IP
address you must press the “Back” key first to switch between softkey mode and the
Down/Up key mode.
NETWORK 1, 4, 5, PRT1(4,5) IP ADDRESS
Range: Standard IPV4 Address format
Default: 169.254.3.3 (Port 1)
Default: 127.0.0.1 (Port 4, 5)
The setting sets the port’s IPV4 address in standard IPV4 format.
NOTE
NOTE: The setting is valid on port 1 if the optional communications card is not present.
The setting is valid on port 5 if port 4’s OPERATION is set to INDEPENDENT.
PRT1(4,5) SUBNET IP MASK
Range: Standard IPV4 mask format
Default: 255.255.255.0 (Port 1)
Default: 0.0.0.0 (Port 4, 5)
This setting specifies the IPv4 mask associated with the corresponding port IP address.
PRT1 GWY ADDRESS
This setting sets the ports IPv4 GATEWAY address in standard IPv4 format.
This setting is only valid on port 1.
This setting is not present on port 4 and 5, which are available on the communications
card.
NOTE
NOTE: The communications card comes with the capability of setting a number of static routes
and one default route, which is used instead of default gateways.
Notes:
• The fiber optic ports support only 100 Mbps.
• Changes to the Ethernet communications settings take effect only after rebooting the
relay.
• All Ethernet ports have flex operands associated with them. A failure of one of the
Ethernet ports will trigger an event, a target message and the corresponding operand
set.

2-8 869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
ETHERNET PORTS CHAPTER 2: COMMUNICATION PORTS
PRT4 OPERATION
Range: Independent, LLA, PRP
Default: Independent
This setting determines the mode of operation for ports 4 and 5: INDEPENDENT, LLA or
PRP.
INDEPENDENT operation: ports 4 and 5 operate independently with their own MAC and
IP address.
LLA operation: the operation of ports 4 and 5 are as follows:
Ports 4 and 5 use port 4’s MAC and IP address settings while port 5 is in standby mode in
that it does not actively communicate on the Ethernet network but monitors its link. If
Port 4 is active and the link loss problem is detected, communications is switched to Port
5 immediately. Port 5 is, in effect, acting as a redundant or backup link to the network for
port 4.
LLA (Link Loss Alert) is a proprietary feature supported by the 8 Series relay fiber optic
ports. When enabled on an 8 Series fiber optic port, this feature is able to detect a failure
of the fiber link. If port 4’s OPERATION is set to LLA, the detection of a link failure by this
feature triggers the transfer of communications from port 4 to port 5. If LLA is enabled
on a port with a non-fiber SFP, the target message “LLA not supported by Prt (4 or 5)” is
displayed on the keypad and an event is logged.
PRP (Parallel Redundancy Protocol): ports 4 and 5 use the same MAC address and
combine information at the link layer. It is intended to only be used if the two ports are
connected to separate parallel LAN’s. In this mode of operation both ports cannot be
connected to the same LAN. The receiving devices (SR relays) process the first frame
received and discard the duplicate through a link redundancy entity (LRE) or similar
service that operates below layer 2. Aside from LRE, PRP uses conventional Ethernet
hardware but both ports must know they are in PRP. Ports of PRP devices operating with
the same Internet Protocol (IP) addresses for traffic that uses IP Management protocols
such as Address Resolution Protocol (ARP) must operate correctly.
Duplicate Discard mode (only mode supported by the 8 Series). This is the normal
setting for PRP operation and once set it allows the sender LRE to append a six-octet
field that contains a sequence number, the Redundancy Control Trailer (RCT) to both
frames it sends. The receiver LRE uses the sequence number of the RCT and the source
MAC address to detect duplicates. It forwards only the first frame of a pair to its upper
layers.
Routing
When the configuration card is present, a default route and a maximum number of 6 static
routes can be configured. The default route is used as the last choice, if no other route
towards a given destination is found.

CHAPTER 2: COMMUNICATION PORTS ETHERNET PORTS
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE 2-9
Figure 2-2: Device Display for Routing Hierarchy
SETTINGS
DEFAULT ROUTE:
Gateway Address
Range: Standard IPV4 unicast address format (0.0.0.1 to 223.255.255.254)
Default: 127.0.0.1
This setting sets the gateway of the default route to be used by IP traffic sent from the
relay, if no other route towards a given IP destination is found.
This setting is available only if the communications card is present.
STATIC ROUTE 1 to 6:
Rt1 (2,3,4,5,6) Destination
Range: Standard IPV4 network address format (0.0.0.1 to 223.255.255.254)
Default: 127.0.0.1
This setting sets the destination IPv4 route. This setting is available only if the
communications card is present.
Rt1 (2,3,4,5,6) Mask
Range: Standard IPV4 network mask format
Default: 255.0.0.0
This setting sets the IP mask associated with the route. This setting is available only if the
communications card is present.
Rt1 (2,3,4,5,6) Gateway
Range: Standard IPV4 unicast address format (0.0.0.1 to 223.255.255.254)
Default: 127.0.0.1
This setting sets the destination IP route. This setting is available only if the
communications card is present.
ADDING AND DELETING STATIC ROUTES
Defaults:
Rule #1.
By default, the value of the destination field is 127.0.0.1 for all static routes (1 to 6). This
is equivalent to saying that the static routes are not configured. When the destination
address is 127.0.0.1, the mask and gateway must also be kept as default values.Rule #2.
By default, the value of the default route gateway address is 127.0.0.1. This means the
default route is not configured.
Setpoints
Level 1 Level 2 Level 3 Level 4
Device
Communications Ethernet
Level 5
Default Route
Static RT1
Routing
Gateway Address
Rt1 Destination
Rt1 Net Mask
Level 6
Static RT6
Rt1 Gateway
Rt6 Destination
Rt6 Net Mask
Rt6 Gateway

2-10 869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
ETHERNET PORTS CHAPTER 2: COMMUNICATION PORTS
Adding a route:
Rule #3.
Use any of the static network route entries numbered 1 to 6 to configure a static
network route. Once a route destination is configured for any of the entries 1 to 6, that
entry becomes a static route and it must meet all the rules listed in the following section
under “Important Notes”.
Rule #4.
To configure the default route, enter a default gateway address. A default gateway
address configured must be validated against Rule #5, the next rule.
Deleting a route:
Rule #5.
Routes are deleted by replacing the route destination with the default address
(127.0.0.1). When deleting a route, the mask and gateway must also be put back to their
default values.
Rule #6.
The default route is deleted by replacing the default gateway with the default value
127.0.0.1.
Important Notes:
1. Host routes are not supported at present.
2. The route mask has IPv4 mask format. In binary this is a set of contiguous bits of 1
from left to right, followed by one or more contiguous bits of 0.
3. The route destination and mask must match.
4. Item #3, above, can be verified by checking that RtDestination & RtMask ==
RtDestination
5. This is an example of a good configuration: RtDestination= 10.1.1.0; Rt Mask=
255.255.255.0
6. This is an example of a bad configuration: RtDestination = 10.1.1.1; Rt Mask=
255.255.255.0
7. The route destination must not be a connected network.
8. The route gateway must be on a connected network. This rule applies to the gateway
address of the default route as well.
9. Item #8, above, can be verified by checking that:
RtGwy & Prt4Mask) == (Prt4IP & Prt4Mask) || (RtGwy & Prt5Mask) == (Prt5IP & Prt5Mask)
TARGETS
WRONG ROUTE CONFIG
Description: A route with mismatched destination and mask has been configured.
Message: “Wrong route configuration.
”What to do: Rectify the IP address and mask of the mis-configured route.
TOPOLOGY EXAMPLE

CHAPTER 2: COMMUNICATION PORTS ETHERNET PORTS
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE 2-11
Figure 2-3: Topology Example
In the above figure: Topology Example, the 8 Series device is connected through the two
Ethernet ports available on the communications card.
• Port 4 (IP address 10.1.1.2) connects to LAN 10.1.1.0/24 and to the Internet through
Router1. Router 1 has an interface on 10.1.1.0/24 and the IP address of this interface
is 10.1.1.1.
• Port 5 (IP address 10.1.2.2) connects to LAN 10.1.2.0/24 and to EnerVista setup
program through Router 2. Router 2 has an interface on 10.1.2.0/24 and the IP
address of this interface is 10.1.2.1.
Configuration
Network addresses:
PRT54IP ADDRESS = 10.1.1.2PRT4 SUBNET IP MASK = 255.255.255.0PRT5 IP ADDRESS =
10.1.2.2PRT5 SUBNET IP MASK = 255.255.255.0
Routing Settings:
IPV4 DEFAULT ROUTE: GATEWAY ADDRESS = 10.1.1.1
STATIC NETWORK ROUTE 1:
– RT1 DESTINATION = 10.1.3.0/24RT1 NET MASK = 255.255.255.0RT1 GATEWAY =
10.1.2.1
Behavior: One static network route was added to the destination 10.1.3.0/24, where a
laptop running EnerVista is located. This static route uses a different gateway (10.1.2.1)
than the default route. This gateway is the address of Router 2, which is “aware” of
destination 10.1.3.0 and is able to route packets coming from the 8 Series device and
destined to EnerVista.

2-12 869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
ETHERNET PORTS CHAPTER 2: COMMUNICATION PORTS

869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE 3-1
869 Motor Protection System
Chapter 3: Time Protocols
GE
Digital Energy
Time Protocols
Real-time Clock
Path:Setpoints > Device > Real Time Clock
The 869 is capable of receiving a time reference from several time sources in addition to its
own internal clock for the purpose of time-stamping events, transient recorders and other
occurrences within the relay. The accuracy of the time stamp is based on the time
reference that is used. The 869 supports an internal clock, SNTP, IRIG-B, and PTP IEEE 1588
as potential time references.
If two or more time sources are available, the time source with the higher priority shown in
Time Sources table is used where 1 is considered to be the highest priority. Please note
that the time source priority of PTP and IRIG-B can be swapped. If both PTP and IRIG-B are
available to the 869, by default the 869 clock syncs to PTP over IRIG-B. If PTP is not
available the 869 CPU syncs the internal clock to IRIG-B.
Table 3-1: Time Sources
* The priority of IRIG-B and PTP can be swapped.
FASTPATH: Synchronization by IEC103, DNP, Modbus and IEC104 is not going to be issued if there is a
sync source from IRIG-B, SNTP or PTP.
IEEE 1588 Precision Time Protocol (PTP)
PTP Status The present values of the PTP protocol are displayed here.
Time Source Priority
PTP (IEEE1588) 1*
IRIG-B 2*
SNTP 3
Internal Clock 4

3-2 869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
REAL-TIME CLOCK CHAPTER 3: TIME PROTOCOLS
Path:Status > PTP
The RTC Sync Source actual value is the time synchronizing source the relay is using at
present. Possible sources are: Port 4 PTP Clock, Port 5 PTP Clock, IRIG-B, SNTP and None.
Grandmaster ID is the grandmaster Identity code being received from the present PTP
grandmaster, if any. When the relay is not using any PTP grandmaster, this actual value is
zero. The grandmaster Identity code is specified by PTP to be globally unique, so one can
always know which clock is grandmaster in a system with multiple grandmaster-capable
clocks.
RTC Accuracy is the estimated maximum time difference at present in the Real Time Clock
(RTC), considering the quality information imbedded in the received time signal, how long
the relay has had to lock to the time source, and in the case of time signal interruptions,
the length of the interruption. The value 999,999,999 indicates that the magnitude of the
estimated difference is one second or more, or that the difference cannot be estimated.
Port 4 (5) PTP State is the present state of the port’s PTP clock. The PTP clock state is:
•DISABLED
If the port’s function setting is Disabled
•NOSIGNAL
If enabled but no signal from an active master has been found and selected
•CALIBRATING
If an active master has been selected but lock is not at present established
•SYNCH’D(NOPDELAY)
If the port is synchronized, but the peer delay mechanism is non-operational
•SYNCHRONIZED
If the port is synchronized
Other manuals for 869
1
Table of contents
Other GE Protection Device manuals
Popular Protection Device manuals by other brands

Guardian
Guardian 00516 instruction manual

NEUTRIK
NEUTRIK etherCON NE8FDPS-TOP product manual

Vega
Vega B 61-300 operating instructions

Scorpion Power System
Scorpion Power System Scorpion Backup Guard II user manual

Engelbert Strauss
Engelbert Strauss 75.76.461 Instructions for use

Infineon
Infineon ESD0P2RF-02LS manual