GE 339 User manual

GE Multilin's Quality
Management System is
registered to ISO9001:2000
QMI # 005094
GE Digital Energy
Multilin
GE Multilin
215 Anderson Avenue, Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222 Fax: (905) 201-2098
Internet: http://www.GEmultilin.com
Instruction manual
339 revision: 1.40
Manual P/N: 1601-9103-A3
GE publication code: GEK-113562B
Copyright © 2010 GE Multilin
*1601-9103-A3*
339
Motor Protection System
Motor protection and control

© 2010 GE Multilin Incorporated. All rights reserved.
GE Multilin 339 Motor Protection System instruction manual for revision 1.40.
339 Motor Protection System, EnerVista, EnerVista Launchpad, and EnerVista SR3 Setup
are registered trademarks of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin. The content of this manual is for informational use only and is subject to
change without notice.
Part number: 1601-9103-A3 (September 2010)

339C MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL TOC–1
Table of Contents
1.INTRODUCTION Overview ................................................................................................................................1 - 1
Cautions and warnings ...................................................................................................1 - 2
Description of the 339 Motor Protection System................................................1 - 3
339 order codes..................................................................................................................1 - 6
Specifications.......................................................................................................................1 - 7
Password security....................................................................................................................1 - 7
Protection.....................................................................................................................................1 - 7
Metering........................................................................................................................................1 - 10
Data capture ..............................................................................................................................1 - 11
Control...........................................................................................................................................1 - 12
Inputs .............................................................................................................................................1 - 13
Outputs..........................................................................................................................................1 - 14
Power supply..............................................................................................................................1 - 14
Communications ......................................................................................................................1 - 15
Testing and certification .......................................................................................................1 - 15
Physical .........................................................................................................................................1 - 16
Environmental............................................................................................................................1 - 16
2.INSTALLATION Mechanical installation ...................................................................................................2 - 1
Dimensions..................................................................................................................................2 - 2
Product identification .............................................................................................................2 - 2
Mounting ......................................................................................................................................2 - 3
Unit withdrawal and insertion............................................................................................2 - 7
Electrical installation ........................................................................................................2 - 8
339 terminal identification...................................................................................................2 - 9
RMIO module installation......................................................................................................2 - 11
Phase sequence and transformer polarity...................................................................2 - 13
Phase current inputs...............................................................................................................2 - 13
Ground and CBCT inputs.......................................................................................................2 - 13
Zero sequence CBCT installation ......................................................................................2 - 14
Voltage inputs............................................................................................................................2 - 15
Control power ............................................................................................................................2 - 15
Contact inputs ...........................................................................................................................2 - 16
Trip and Close output relays ...............................................................................................2 - 16
Serial communications..........................................................................................................2 - 19
IRIG-B .............................................................................................................................................2 - 20
3.INTERFACES Front control panel interface........................................................................................3 - 2
Description ..................................................................................................................................3 - 2
Display ...........................................................................................................................................3 - 3
Working with the Keypad....................................................................................................3 - 3
LED status indicators..............................................................................................................3 - 4
Relay messages ........................................................................................................................3 - 6
Default message.....................................................................................................................3 - 6
Target messages.....................................................................................................................3 - 6
Self-test errors..........................................................................................................................3 - 7
Flash messages.......................................................................................................................3 - 9
Software setup....................................................................................................................3 - 10
Quick setup - Software interface ......................................................................................3 - 10
EnerVista SR3 Setup Software............................................................................................3 - 10

TOC–2 339C MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Hardware and software requirements.........................................................................3 - 11
Installing the EnerVista SR3 Setup software..............................................................3 - 11
Connecting EnerVista SR3 Setup to the relay ............................................................3 - 14
Configuring serial communications...............................................................................3 - 14
Using the Quick Connect feature ....................................................................................3 - 15
Configuring Ethernet communications ........................................................................3 - 16
Connecting to the relay........................................................................................................3 - 17
Working with setpoints and setpoint files....................................................................3 - 18
Engaging a device..................................................................................................................3 - 18
Entering setpoints...................................................................................................................3 - 18
File support ................................................................................................................................3 - 20
Using setpoints files...............................................................................................................3 - 20
Downloading and saving setpoints files......................................................................3 - 20
Adding setpoints files to the environment..................................................................3 - 20
Creating a new setpoint file...............................................................................................3 - 21
Upgrading setpoint files to a new revision .................................................................3 - 22
Printing setpoints and actual values .............................................................................3 - 23
Printing actual values from a connected device .....................................................3 - 24
Loading setpoints from a file.............................................................................................3 - 25
Upgrading relay firmware ...................................................................................................3 - 25
Loading new relay firmware..............................................................................................3 - 25
Advanced EnerVista SR3 Setup features ...................................................................... 3 - 27
Data logger................................................................................................................................3 - 27
Motor start data logger........................................................................................................3 - 28
Transient recorder (Waveform capture).......................................................................3 - 30
Protection summary..............................................................................................................3 - 33
Password security ..................................................................................................................3 - 34
4.ACTUAL VALUES Actual values overview ...................................................................................................4 - 1
A1 Status................................................................................................................................4 - 3
Motor status ...............................................................................................................................4 - 4
Clock...............................................................................................................................................4 - 6
Contact inputs...........................................................................................................................4 - 6
Output relays ............................................................................................................................. 4 - 6
Output relays - Breaker........................................................................................................4 - 6
Output relays - Contactor...................................................................................................4 - 7
Logic elements ..........................................................................................................................4 - 7
Virtual inputs ..............................................................................................................................4 - 7
Remote inputs ...........................................................................................................................4 - 7
Remote outputs ........................................................................................................................4 - 8
Contact inputs summary......................................................................................................4 - 8
Output relays summary........................................................................................................4 - 8
Logic elements summary.....................................................................................................4 - 8
GOOSE status.............................................................................................................................4 - 9
GOOSE HDR status ..................................................................................................................4 - 9
RTD temp summary................................................................................................................4 - 9
A2 Metering ..........................................................................................................................4 - 10
Current..........................................................................................................................................4 - 10
Voltage..........................................................................................................................................4 - 11
Power.............................................................................................................................................4 - 11
Energy ...........................................................................................................................................4 - 12
RTD temperature......................................................................................................................4 - 12
Clear energy ...............................................................................................................................4 - 12
A3 Records............................................................................................................................4 - 13
Datalogger ..................................................................................................................................4 - 13
Motor start data logger.........................................................................................................4 - 13

339C MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL TOC–3
Event records .............................................................................................................................4 - 13
Transient records .....................................................................................................................4 - 30
Learned data..............................................................................................................................4 - 30
Learned data recorder...........................................................................................................4 - 32
Clear learned data ...................................................................................................................4 - 32
Clear transient record ............................................................................................................4 - 32
Clear event record ...................................................................................................................4 - 32
A4 Target messages.........................................................................................................4 - 33
5.QUICK SETUP -
FRONT CONTROL
PANEL
Quick Setup settings.........................................................................................................5 - 3
6.SETPOINTS Setpoints ................................................................................................................................6 - 1
Setpoint entry methods.........................................................................................................6 - 2
Common setpoints ..................................................................................................................6 - 3
Logic diagrams..........................................................................................................................6 - 3
Settings text abbreviations..................................................................................................6 - 4
S1 Relay setup .....................................................................................................................6 - 6
Clock...............................................................................................................................................6 - 7
Password security....................................................................................................................6 - 9
Access passwords..................................................................................................................6 - 10
Communications ......................................................................................................................6 - 12
RS485 interface .......................................................................................................................6 - 13
Ethernet.......................................................................................................................................6 - 13
Modbus........................................................................................................................................6 - 14
IEC60870-5-103 serial communication settings .....................................................6 - 15
IEC60870-5-104 protocol....................................................................................................6 - 29
DNP communication.............................................................................................................6 - 30
IEC 61850 GOOSE configuration......................................................................................6 - 43
Event recorder ...........................................................................................................................6 - 44
Transient recorder ...................................................................................................................6 - 45
Datalogger...................................................................................................................................6 - 47
Front panel ..................................................................................................................................6 - 47
Installation...................................................................................................................................6 - 48
Preset statistics .........................................................................................................................6 - 49
S2 System Setup.................................................................................................................6 - 50
Current sensing.........................................................................................................................6 - 50
Voltage sensing.........................................................................................................................6 - 52
Power system.............................................................................................................................6 - 53
Motor..............................................................................................................................................6 - 53
Switching device.......................................................................................................................6 - 54
S3 Protection........................................................................................................................6 - 55
Thermal Model...........................................................................................................................6 - 58
Total Capacity Used register (TCU) .................................................................................6 - 58
Start protection........................................................................................................................6 - 59
Thermal overload curves ....................................................................................................6 - 59
Thermal protection setpoints............................................................................................6 - 67
Short circuit.................................................................................................................................6 - 72
Mechanical Jam........................................................................................................................6 - 75
Undercurrent..............................................................................................................................6 - 78
Current unbalance...................................................................................................................6 - 81
Load increase alarm ...............................................................................................................6 - 84
Ground fault................................................................................................................................6 - 85

TOC–4 339C MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Neutral instantaneous overcurrent.................................................................................6 - 88
Phase undervoltage................................................................................................................6 - 90
Phase overvoltage...................................................................................................................6 - 93
Underfrequency........................................................................................................................6 - 96
Overfrequency...........................................................................................................................6 - 99
Underpower................................................................................................................................6 - 102
Negative sequence overvoltage.......................................................................................6 - 105
Phase reversal........................................................................................................................... 6 - 107
VT fuse fail ................................................................................................................................... 6 - 107
Acceleration protection ........................................................................................................ 6 - 108
RTD protection...........................................................................................................................6 - 110
Two-speed motor ....................................................................................................................6 - 116
Two-speed motor setup ......................................................................................................6 - 117
High speed thermal protection ........................................................................................6 - 118
High speed short circuit settings.....................................................................................6 - 118
High speed acceleration......................................................................................................6 - 121
High speed undercurrent....................................................................................................6 - 121
S4 Control..............................................................................................................................6 - 124
Virtual inputs ..............................................................................................................................6 - 125
Logic elements ..........................................................................................................................6 - 126
Breaker failure / Welded contactor................................................................................. 6 - 142
Start inhibit..................................................................................................................................6 - 145
Emergency restart...................................................................................................................6 - 148
Lockout reset .............................................................................................................................6 - 148
Reset .............................................................................................................................................. 6 - 148
Breaker control .........................................................................................................................6 - 148
S5 Inputs/Outputs .............................................................................................................6 - 150
Contact inputs...........................................................................................................................6 - 151
Output relays ............................................................................................................................. 6 - 152
Output Relays - Breaker.......................................................................................................6 - 153
Output Relays - Contactor..................................................................................................6 - 161
Virtual inputs ..............................................................................................................................6 - 164
7.MAINTENANCE M1 Relay information.......................................................................................................7 - 4
M2 Motor maintenance ..................................................................................................7 - 6
M3 Breaker maintenance ..............................................................................................7 - 7
Trip coil..........................................................................................................................................7 - 7
Close coil ......................................................................................................................................7 - 10
Breaker trip counter................................................................................................................ 7 - 13
Reset counters ..........................................................................................................................7 - 15
M4 Breaker monitor..........................................................................................................7 - 16
M5 Relay maintenance ...................................................................................................7 - 17
Ambient temperature ............................................................................................................ 7 - 17
M6 Factory service............................................................................................................7 - 20
APPENDIX Change notes ...................................................................................................................Appendix - 1
Manual Revision history.................................................................................................... Appendix - 1

339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 1–1
339 Motor Protection System
Chapter 1: Introduction
Digital Energy
Multilin
Introduction
Overview
The 339 Motor Protection System is a microprocessor based relay providing suitable
protection of medium voltage motors. The small footprint and the withdrawable option
make the relay ideal for panel mounting on either new or retrofit installations. The
combination of proven hardware, a variety of protection and control features, and
communications, makes the relay ideal for total motor protection and control. Equipped
with serial (RS485), USB, and Ethernet ports, and a wide selection of protocols such as
Modbus, DNP3.0, IEC 60870-5-103, 60870-5-104, GOOSE, the relay is the best-in-class for
MCCs, SCADA and inter-relay communications. The relay provides excellent transparency
with respect to power system conditions and events, through its four-line 20-character
display, as well as the EnerVista SR3 Setup program. Conveniently located LEDs provide
indication of overall relay operation, as well as alarm, pickup, and motor status.
The relay provides the following key benefits:
• Withdrawable small footprint – saves on rewiring and space.
• Fast setup (Quick Setup) menu provided, to guide users through a wide range of motor
management applications.
• Large four-line LCD display, LEDs, and an easy-to-navigate keypad.
• Multiple communication protocols for simultaneous access when integrated into
monitoring and control systems.

1–2 339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CAUTIONS AND WARNINGS CHAPTER 1: INTRODUCTION
Cautions and warnings
Before attempting to install or use this device, it is imperative that all caution and danger
indicators in this manual are reviewed to help prevent personal injury, equipment damage,
or downtime. The following icons are used to indicate notes, cautions, and dangers.
Figure 1: Note icons used in the documentation
The standard note icon emphasizes a specific point or indicates minor problems that may
occur if instructions are not properly followed.
The caution icon indicates that possible damage to equipment or data may occur if
instructions are not properly followed.
The danger icon provides users with a warning about the possibility of serious or fatal
injury to themselves or others.
NOTE
CAUTION
DANGER

CHAPTER 1: INTRODUCTION DESCRIPTION OF THE 339 MOTOR PROTECTION SYSTEM
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 1–3
Description of the 339 Motor Protection System
CPU
Relay functions are controlled by two processors: a Freescale MPC5554 32-bit
microprocessor measures all analog signals and digital inputs and controls all output
relays; a Freescale MPC520B 32-bit microprocessor controls all the Ethernet
communication protocols.
Analog Input Waveform Capture
Magnetic transformers are used to scale-down the incoming analog signals from the
source instrument transformers. The analog signals are then passed through a 960 Hz low
pass anti-aliasing filter. All signals are then simultaneously captured by sample and hold
buffers to ensure there are no phase shifts. The signals are converted to digital values by a
12-bit A/D converter before finally being passed on to the CPU for analysis.
Both current and voltage are sampled thirty-two times per power frequency cycle. These
‘raw’ samples are scaled in software, then placed into the waveform capture buffer, thus
emulating a fault recorder. The waveforms can be retrieved from the relay via the EnerVista
SR3 Setup software for display and diagnostics.
Frequency
Frequency measurement is accomplished by measuring the time between zero crossings
of the Bus VT phase A voltage . The signals are passed through a low pass filter to prevent
false zero crossings. Sampling is synchronized to the Va-x voltage zero crossing which
results in better co-ordination for multiple relays on the same bus.
Phasors, Transients, and Harmonics
Current waveforms are processed twice every cycle with a DC Offset Filter and a Discrete
Fourier Transform (DFT). The resulting phasors have fault current transients and all
harmonics removed. This results in a motor that is extremely secure and reliable; one that
will not overreach.
Processing of AC Current Inputs
The DC Offset Filter is an infinite impulse response (IIR) digital filter, which removes the DC
component from the asymmetrical current present at the moment a fault occurs. This is
done for all current signals used for overcurrent protection; voltage signals bypass the DC
Offset Filter. This filter ensures no overreach of the overcurrent protection.
The Discrete Fourier Transform (DFT) uses exactly one sample cycle to calculate a phasor
quantity which represents the signal at the fundamental frequency; all harmonic
components are removed. All subsequent calculations (e.g. RMS, power, etc.) are based
upon the current and voltage phasors, such that the resulting values have no harmonic
components.
Protection Elements
All protection elements are processed twice every cycle to determine if a pickup has
occurred or a timer has expired. The protection elements use RMS current/voltage, based
on the magnitude of the phasor. Hence, protection is impervious to both harmonics and DC
transients.

1–4 339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
DESCRIPTION OF THE 339 MOTOR PROTECTION SYSTEM CHAPTER 1: INTRODUCTION
Figure 2: Line Diagram
Table 1: Protection functions
896814.CDR
52
37 46 49 50P
50BF
50G
49
MOTOR
LOAD
Stator RTDs
Bearing RTDs
Phase CT 3
Ground CT 1
BUS
339
MOTOR PROTECTIONSYSTEM
Ambient air
RTD
38
Optional Remote RTD
51
86
START
50N
TRIP
CLOSE
START INHIBIT
27P 59P 47 59_2 81O 81U
59_2
ANSI device Description
27P Phase UV
37 Undercurrent
Underpower
38 Bearing RTD
Stator/Ambient/Other
RTD Trouble Alarm
46 Current Unbalance
47 Voltage Phase Reversal
48 Acceleration Time
49 Thermal Protection/Stall Protection
50BF Breaker Failure / Welded Contactor
50G Ground Fault
50P Short Circuit
51P Mechanical Jam
50N Neutral Instantaneous Overcurrent
59_2 Negative Sequence OV
59P Phase OV
66 Starts per Hour & Time Between Starts
Restart Block
Thermal Inhibit
81O Overfrequency
81U Underfrequency
86 Lockout
VTFF VT Fuse Failure

CHAPTER 1: INTRODUCTION DESCRIPTION OF THE 339 MOTOR PROTECTION SYSTEM
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 1–5
Figure 3: Main Menu structure
ACTUAL VALUES
QUICK SETUP
SETPOINTS
MAINTENANCE
ACTUAL VALUES
A1 STATUS
A2 METERING
A3 RECORDS
A4 TARGET MESSAGES
▼
QUICK SETUP
RELAY STATUS
NOMINAL FREQUENCY
GROUND CT TYPE
VT CONNECTION
VT SECONDARY
VT RATIO
MOTOR FLA
THERMAL O/L FUNC
S/C FUNC
MECH JAM FUNC
U/CURR TRIP FUNC
GND TRIP FUNC
PH UV FUNC
PHASE CT PRIMARY
SWITCHING DEVICE
52a CONTACT
52b CONTACT
▼
SETPOINTS
S1 RELAY SETUP
S2 SYSTEM SETUP
S3 PROTECTION
S4 CONTROLS
S5 INPUTS/OUTPUTS
▼
MAINTENANCE
M1 RELAY INFO
M2 MOTOR MAINTEN
M3 BKR MAINTENANCE
M4 BKR MONITOR
M6 FACTORY SERVICE
▼
896756.cdr
THERMAL PROTECTION
START PROTECTION
SAFE STALL T COLD
THERMAL O/L PKP
UNBALANCE K FACTOR
COOL TIME RUNNING
COOL TIME STOPPED
HOT/COLD RATIO
LOCKED ROTOR CURR
▼
SHORT CIRCUIT
S/C PKP
S/C DELAY
▼
MECHANICAL JAM
MECH JAM PKP
MECH JAM DELAY
▼
UNDERCURRENT
U/CURR TRIP PKP
UCURR TRIP DELAY
▼
GROUND FAULT
GND TRIP PKP
GND TRIP ON RUN
GND TRIP ON START
▼
PHASE UV
PH UV PKP
PH UV DELAY
▼

1–6 339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
339 ORDER CODES CHAPTER 1: INTRODUCTION
339 order codes
The information to specify a 339 relay is provided in the following order code table.
Figure 4: Order Codes

CHAPTER 1: INTRODUCTION SPECIFICATIONS
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 1–7
Specifications
NOTE
NOTE: Specifications are subject to change without notice.
Password security
PASSWORD SECURITY
Master Reset Password: ..................................8 to 10 alpha-numeric characters
Settings Password:.............................................3 to 10 alpha-numeric characters for local and remote
access
Control Password:...............................................3 to 10 alpha-numeric characters for local and remote
access
Protection
NEUTRAL INSTANTANEOUS OVERCURRENT
Pickup Level:..........................................................0.05 to 20 x CT in steps of 0.01 x CT
Dropout Level: ......................................................96 to 99% of Pickup @ I > 1 x CT
Pickup - 0.02 x CT @ I <1 x CT
Time Delay:............................................................0.00 to 300.00 sec in steps of 0.01
Operate Time:.......................................................<30 ms @ 60Hz (I > 2.0 x PKP), 0 ms time delay
<35 ms @ 50Hz (I > 2.0 x PKP), 0 ms time delay
Timer Accuracy:...................................................0 to 1 cycle
Level Accuracy:....................................................per CT input
Elements: ................................................................Trip or Alarm
NEUTRAL DIRECTIONAL OVERCURRENT
Directionality:........................................................Co-existing forward and reverse
Polarizing: ...............................................................Voltage, Current, Dual
Voltage can be:
- Calculated from VT phases (VTs must be connected in
"Wye")
- Measured by Vaux input (3V0provided by an external open
delta connection)
Polarizing Voltage:..............................................-V0
Polarizing Current:..............................................IG
MTA:...........................................................................From 0oto 359oin steps of 1o
Angle Accuracy:...................................................±2o
Operation Delay: .................................................20 to 30 ms
UNDERCURRENT
Pickup Level:..........................................................0.1 to 0.95 x FLA in steps of 0.01 x FLA
Dropout Level: ......................................................101 to 104% of Pickup
Time Delay:............................................................1.00 to 60.00 s in steps of 0.01 s
Block from Start:..................................................0 to 600 s in steps of 1 s
Pickup Accuracy:.................................................as per phase current inputs
Timing Accuracy: ................................................±0.5 s or ±0.5% of total time
Elements: ................................................................Trip and Alarm

1–8 339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS CHAPTER 1: INTRODUCTION
CURRENT UNBALANCE
Unbalance: ............................................................See table below
Unbalance Pickup Level: .................................4 to 40% in steps of 1%
Unbalance Time Delay:.................................... 1.00 to 60.00 s in steps of 0.01 s
Single Phasing Pickup Level: .........................unbalance level > 40% or when Iavg ≥25%FLA and current in
any phase is less than the cutoff current
Single Phasing Time Delay:............................2 sec
Dropout Level:......................................................96 to 99% of pickup
Pickup Accuracy:.................................................±2%
Timing Accuracy:................................................ ±0.5 s or ±0.5% of total time
Unbalance Elements:........................................ Trip and Alarm
Single Phasing Elements:................................Trip
Table 2: Current Unbalance equations
RTD
Pickup:......................................................................1 to 250oC in steps of 1oC
Pickup Hysteresis:............................................... 2oC
Time Delay:............................................................3 sec
Elements:................................................................Trip and Alarm
RTD TROUBLE ALARM
RTD Trouble Alarm: ............................................<-50oC or >250oC
LOAD INCREASE ALARM
Pickup Level: .........................................................50 to 150%FLA in steps of 1%FLA
Dropout Level:......................................................96 to 99% of Pickup
Alarm Time Delay:..............................................1.00 to 60.00 s in steps of 0.01 s
Pickup Accuracy:.................................................as per phase current inputs
Timing Accuracy:................................................±0.5 s or ±0.5% of total time
SHORT CIRCUIT
Pickup Level: ......................................................... 1.00 to 20.00 x CT in steps of 0.01 x CT
Dropout Level:......................................................96 to 99% of Pickup @ I > 1 x CT
Pickup - 0.02 x CT @ I < 1 x CT
Alarm Time Delay:..............................................0.00 to 60.00 s in steps of 0.01 s
Pickup Accuracy:.................................................as per phase current inputs
Operate Time: ...................................................... <30 ms @ 60Hz (I > 2.0 x PKP), 0 ms time delay
<35 ms @ 50Hz (I > 2.0 x PKP), 0 ms time delay
Timer Accuracy: .................................................. 0 to 1 cycle
Elements:................................................................Trip or Alarm
MECHANICAL JAM TRIP
Pickup Level: .........................................................1.01 to 4.50 x FLA in steps of 0.01 x FLA, blocked from start
Dropout Level:......................................................96 to 99% of Pickup
Trip Time Delay:...................................................0.10 to 30.00 s in steps of 0.01 s
Pickup Accuracy:.................................................as per phase current inputs
Timing Accuracy:................................................±0.5 s or ±0.5% of total time

CHAPTER 1: INTRODUCTION SPECIFICATIONS
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 1–9
GROUND FAULT
Pickup Level:..........................................................0.03 to 1.00 x CT in steps of 0.01 x CT
0.50 to 15.00 A in steps of 0.01 A (CBCT)
Dropout Level: ......................................................Pickup - 0.02 x CT
96 to 99% of Pickup (CBCT)
Alarm Time Delay on Run: ..............................0.00 to 60.00 s in steps of 0.01 s
Alarm Time Delay on Start:............................0.00 to 60.00 s in steps of 0.01 s
Trip Time Delay on Run:...................................0.00 to 5.00 s in steps of 0.01 s
Trip Time Delay on Start:.................................0.00 to 10.00 s in steps of 0.01 s
Pickup Accuracy:.................................................as per ground current inputs
Operate Time:.......................................................<30 ms @ 60Hz (I > 2.0 x PKP), 0 ms time delay
<35 ms @ 50Hz (I > 2.0 x PKP), 0 ms time delay
Timing Accuracy: ................................................0 to 1 cycle
Elements: ................................................................Trip and Alarm
THERMAL PROTECTION
Locked Rotor Current:.......................................2.0 to 11.0 x FLA in steps of 0.1 x FLA
Safe Stall Time:.....................................................1.0 to 600.0 s in steps of 0.1 s
Curve Multiplier:...................................................1 to 15 in steps of 1
Pickup Level:..........................................................1.01 to 1.25 x FLA in steps of 0.01 x FLA
Curve Biasing:.......................................................Phase unbalance
Hot/cold biasing
Stator RTD biasing
Exponential Running and Stopped Cooling Rates
TCU Update Rate: ...............................................3 cycles
Pickup Accuracy:.................................................per phase current inputs
Timing Accuracy: ................................................±200 ms or ±2% of total time
Elements: ................................................................Trip and Alarm
PHASE/AUXILIARY UNDERVOLTAGE
Minimum Voltage:...............................................Programmable from 0.00 to 1.25 x VT in steps of 0.01
Pickup Level:..........................................................0.00 to 1.25 x VT in steps of 0.01
Dropout Level: ......................................................101 to 104% of pickup
Curve: .......................................................................Definite Time, Inverse Time
Time Delay:............................................................0.1 to 600.0 s in steps of 0.1
Operate Time:.......................................................Time delay ±30 ms @ 60 Hz (V < 0.85 x PKP)
Time delay ±40 ms @ 50 Hz (V < 0.85 x PKP)
Time Delay Accuracy: .......................................±3% of expected time, or 1 cycle, whichever is greater
Level Accuracy:....................................................Per voltage input
UNDERPOWER
Pickup Level:..........................................................1 to 100% Hz MNR 1%
Dropout Level: ......................................................101% to 104% of Pickup
Time Delay:............................................................1.0 to 60.0 s in steps of 0.1
Pickup Accuracy:.................................................as per power monitoring specification
Timing Accuracy: ................................................±0.5 s or ±0.5% of total time
Elements: ................................................................Trip and Alarm
NEGATIVE SEQUENCE/PHASE OVERVOLTAGE
Pickup Level:..........................................................0.00 to 1.25 x VT in steps of 0.01
Dropout Level: ......................................................96 to 99% of pickup
Time Delay:............................................................0.1 to 600.0 s in steps of 0.1
Operate Time:.......................................................Time delay ±30 ms @ 60 Hz (V < 0.85 x PKP)
Time delay ±40 ms @ 50 Hz (V < 0.85 x PKP)
Timing Accuracy: ................................................±0.5 s or ±0.3% of total time
Level Accuracy:....................................................Per voltage input

1–10 339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS CHAPTER 1: INTRODUCTION
PHASE REVERSAL
Configuration: ......................................................ABC or ACB phase rotation
Time Delay:............................................................100 ms
Timing Accuracy:................................................±0.5 s
Elements:................................................................Trip or Alarm
UNDERFREQUENCY
Minimum Voltage: ..............................................0.00 to 1.25 x VT in steps of 0.01
Pickup Level: .........................................................40.00 to 70.00 Hz in steps of 0.01
Dropout Level:......................................................Pickup +0.03 Hz
Time Delay:............................................................0.1 to 600.0 s in steps of 0.1
Timing Accuracy:................................................±0.5 s or ±0.5% of total time
Level Accuracy:.................................................... ±0.01 Hz
Elements:................................................................Trip and Alarm
OVERFREQUENCY
Minimum Voltage: ..............................................0.3 x VT
Pickup Level: .........................................................40.00 to 70.00 Hz in steps of 0.01
Dropout Level:......................................................Pickup - 0.03 Hz
Time Delay:............................................................0.1 to 600.0 s in steps of 0.1
Timing Accuracy:................................................±0.5 s or ±0.5% of total time
Level Accuracy:.................................................... ±0.01 Hz
Elements:................................................................Trip and Alarm
FUSE FAIL
Time Delay:............................................................1 s
Timing Accuracy:................................................±0.5 s
Elements:................................................................Trip or Alarm
ACCELERATION TIME TRIP
Pickup Level: ......................................................... Motor start condition
Dropout Level:......................................................Motor run, trip, or stop condition
Timers for single-speed:..................................Stopped to running
Timers for two-speed:......................................Stopped to high speed, stopped to low speed, low to high
speed
Time Delay:............................................................1.0 to 250.0 s in steps of 0.1
Timing Accuracy:................................................±200 ms or ±1% of total time
Metering
NOTE
NOTE: Full scale for CT Input is 3 x CT
PARAMETER ACCURACY RESOLUTION RANGE
3-Phase Real Power (kW) ±1% of full scale 0.1 kW ±100000.0 kW
3-Phase Reactive Power (kvar) ±1% of full scale 0.1 kvar ±100000.0 kvar
3-Phase Apparent Power (kVA) ±1% of full scale 0.1 kVA 100000.0 kVA
3-Phase Positive Watthour (MWh) ±1% of full scale ±0.001 MWh 50000.0 MWh
3-Phase Negative Watthour (MWh) ±1% of full scale ±0.001 MWh 50000.0 MWh
3-Phase Positive Varhour (Mvarh) ±1% of full scale ±0.001 Mvarh 50000.0 Mvarh
3-Phase Negative Varhour (Mvarh) ±1% of full scale ±0.001 Mvarh 50000.0 Mvarh
Power Factor ±0.05 0.01 -0.99 to 1.00
Frequency ±0.05 Hz 0.01 Hz 40.00 to 70.00 Hz

CHAPTER 1: INTRODUCTION SPECIFICATIONS
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 1–11
Data capture
DATA LOGGER
Number of Channels: ........................................10
Parameters:...........................................................Any available analog actual value
Sampling Rate:.....................................................1 cycle, 1 second, 1 minute, 1 hour
Trigger Source:.....................................................All logic elements, Logic operand: Any Trip PKP/OP/DPO, Any
Alarm PKP/OP/DPO
Mode:........................................................................Continuous or triggered
MOTOR START DATA LOGGER
Length:.....................................................................6 buffers, containing a total of 30 seconds of motor starting
data
Trigger:.....................................................................Motor start status
Trigger Position:...................................................1-second pre-trigger duration
Logging Rate:........................................................1 sample/200 ms
TRANSIENT RECORDER
Buffer size:..............................................................3 s
No. of buffers:......................................................1x192 cycles, 3x64 cycles, 6x32 cycles
Sampling rate:......................................................32 samples per cycle
Triggers:...................................................................Manual Command
Contact Input
Virtual Input
Logic Element
Element Pickup/Trip/Dropout/Alarm
Data:..........................................................................AC input channels
Contact input state
Contact output state
Virtual input state
Logic element state
Data storage:........................................................RAM - battery backed-up
EVENT RECORDER
Number of events:..............................................256
Content:...................................................................event number, date of event, cause of event, per-phase
current, ground current, sensitive ground current, neutral
current, per-phase voltage (VTs connected in “Wye”), or
phase-phase voltages (VTs connected in “Delta”), system
frequency, power, power factor, thermal capacity, motor
load, current unbalance
Data Storage:........................................................Non-volatile memory
LEARNED DATA RECORDER
Number of events:..............................................250
Header: ....................................................................Date, number of records
Content:...................................................................learned acceleration time , learned starting current, learned
starting capacity, last starting current, last starting capacity,
last acceleration time , average motor load learned, average
run time after start (days), average run time after start
(minutes)
Data Storage:........................................................Non-volatile memory
CLOCK
Setup:........................................................................Date and time
Daylight Saving Time
RTC Accuracy: ± 1 min / month at 25°C
IRIG-B:.......................................................................Auto-detect (DC shift or Amplitude Modulated)
Amplitude modulated: 1 to 10 V pk-pk
DC shift: 1 to 10 V DC
Input impedance: 40 kOhm ± 10% at 25°C

1–12 339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS CHAPTER 1: INTRODUCTION
Control
LOGIC ELEMENTS
Number of logic elements:............................. 16
Trigger source inputs per element:............3
Block inputs per element: ...............................3
Supported operations: .....................................OR, AND, NOT, Pickup / Dropout timers
Pickup timer: .........................................................0 to 60000 ms in steps of 1 ms
Dropout timer:......................................................0 to 60000 ms in steps of 1 ms
BREAKER CONTROL
Operation: ..............................................................Asserted Contact Input, Logic Element, Virtual Input, Manual
Command, Remote Input
Function:.................................................................Opens/closes the motor breaker
START INHIBIT
Thermal Start Inhibit: ........................................Thermal Inhibit Margin: 0 to 25 % in steps of 1%
Starts per Hour Inhibit:.....................................Maximum: 1 to 5 starts in steps of 1
Time Between Starts Inhibit:.........................Time Between Starts: 1 to 3600 s in steps of 1 s
Restart Inhibit:......................................................Restart Inhibit Delay: 1 to 50000 s in steps of 1 s
BREAKER FAILURE/WELDED CONTACTOR
Current Supervision:..........................................Phase Current
Current Supervision Pickup:...........................0.05 to 20.00 x CT in steps of 0.01 x CT
Time Delay 1:........................................................ 0.03 to 1.00 s in steps of 0.01 s
Time Delay 2:........................................................ 0.00 to 1.00 s in steps of 0.01 s
Current Supervision Dropout: ....................... 97 to 98% of pickup
Current Supervision Accuracy:.....................per CT input
Timing Accuracy:................................................0 to 1 cycle (Timer 1, Timer 2)
BREAKER TRIP COUNTER
Trip Counter Limit (Pickup):.............................1 to 10000 in steps of 1
EMERGENCY RESTART
Function:.................................................................Defeats all motor start inhibit features, resets all trips and
alarms, and discharges the thermal capacity to zero so that
a hot motor can be restarted in the event of an emergency
Operation: ..............................................................Contact Input 1 to 10, Virtual Input 1 to 32, Logic Element 1
to 16, Remote Input 1 to 32
LOCKOUT RESET
Function:.................................................................Reset any lockout trips when this feature is configured.
Operation: ..............................................................Contact Input 1 to 10, Virtual Input 1 to 32, Logic Element 1
to 16, Remote Input 1 to 32
RESET
Function:.................................................................Resets any alarms and non-lockout trips when LOCKOUT
RESET is configured, or resets any alarms and trips (lockout
and non-lockout trips) when LOCKOUT RESET is not
configured.
Operation: ..............................................................Contact Input 1 to 10, Virtual Input 1 to 32, Logic Element 1
to 16, Remote Input 1 to 32
AMBIENT TEMPERATURE
High Temperature Pickup:.............................. 20°C to 80°C in steps of 1°C
Low Temperature Pickup:...............................-40°C to 20°C in steps of 1°C
Time Delay:............................................................ 1 to 60 min in steps of 1 mins
Temperature Dropout:......................................Configurable 90 to 98% of pickup
Temperature Accuracy: ................................... ±10°C
Timing Accuracy:................................................±1 second

CHAPTER 1: INTRODUCTION SPECIFICATIONS
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 1–13
Inputs
CONTACT INPUTS
Inputs:.......................................................................10
Selectable thresholds: ......................................17, 33, 84, 166 VDC
Recognition time:................................................1/2 cycle
Debounce time: ...................................................1 to 64 ms, selectable, in steps of 1 ms
Continuous current draw:...............................2 mA
Type:..........................................................................opto-isolated inputs
External switch: ...................................................wet contact
Maximum input voltage:..................................300 VDC
PHASE & GROUND CURRENT INPUTS
CT Primary:.............................................................30 to 1500 A
Range: ......................................................................0.05 to 20 × CT
Input type: ..............................................................1 A or 5 A (must be specified with order)
Nominal frequency: ...........................................50/60 Hz
Burden: ....................................................................<0.1 VA at rated load
Accuracy:................................................................±1% of reading at 1× CT
±3% of reading from 0.2 to 20 × CT
±20% of reading from 0.05 to 0.19 × CT
CT withstand: ........................................................1 second at 100 × rated current
2 seconds at 40 × rated current
continuous at 3 × rated current
CBCT INPUT (50:0.025)
Range: ......................................................................0.5 to 15.0 A
Nominal frequency: ...........................................50 or 60 Hz
Accuracy (CBCT):..................................................±0.1 A (0.5 to 3.99 A)
±0.2 A (4.0 A to 15 A)
FREQUENCY
Accuracy:................................................................±0.05 Hz
Resolution:..............................................................0.01 Hz
Range: ......................................................................40.00 to 70.00 Hz
PHASE VOLTAGE INPUTS
Source VT:...............................................................100 to 20000 V
VT secondary range: .........................................50 to 240 V
VT ratio:....................................................................1 to 300 in steps of 1
Nominal frequency: ...........................................50/60 Hz
Accuracy:................................................................±1.0% throughout range
Voltage withstand: .............................................260 VAC continuous
RMIO RTD INPUTS
RTD Type: ................................................................100 Ohm platinum (DIN.43760)
RTD Sensing Current:.........................................5 mA
Isolation:..................................................................2 kV from base unit
Distance: .................................................................250 m maximum
Range: ......................................................................-50 to +250oC
Accuracy:................................................................±2oC
Lead Resistance: .................................................25 Ohm max per lead

1–14 339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS CHAPTER 1: INTRODUCTION
Outputs
FORM-A RELAYS
Configuration: ......................................................2 (two) electromechanical
Contact material:................................................ silver-alloy
Operate time:........................................................<8 ms
Continuous current:...........................................10 A
Make and carry for 0.2s:..................................30 A per ANSI C37.90
Break (DC inductive, L/R=40 ms):.................24 V / 1 A
48 V / 0.5 A
125 V / 0.3 A
250 V / 0.2 A
Break (DC resistive): ...........................................24 V / 10 A
48 V / 6 A
125 V / 0.5 A
250 V / 0.3 A
Break (AC inductive):..........................................720 VA @ 250 VAC Pilot duty A300
Break (AC resistive):............................................277 VAC / 10 A
FORM-A VOLTAGE MONITOR
Applicable voltage: ............................................20 to 250 VDC
Trickle current: .....................................................1 to 2.5 mA
FORM-C RELAYS
Configuration: ......................................................5 (five) electromechanical
Contact material:................................................ silver-alloy
Operate time:........................................................<8 ms
Continuous current:...........................................10 A
Make and carry for 0.2s:..................................30 A per ANSI C37.90
Break (DC inductive, L/R=40 ms):.................24 V / 1 A
48 V / 0.5 A
125 V / 0.3 A
250 V / 0.2 A
Break (DC resistive): ...........................................24 V / 10 A
48 V / 6 A
125 V / 0.5 A
250 V / 0.3 A
Break (AC inductive):..........................................720 VA @ 250 VAC Pilot duty A300
Break (AC resistive):............................................277 VAC / 10 A
TRIP / CLOSE SEAL-IN
Relay 1 trip seal-in: ............................................0.00 to 9.99 s in steps of 0.01
Relay 2 close seal-in:......................................... 0.00 to 9.99 s in steps of 0.01
Power supply
HIGH RANGE POWER SUPPLY
Nominal:..................................................................120 to 240 VAC125 to 250 VDC
Range:......................................................................60 to 300 VAC (50 and 60 Hz)
84 to 250 VDC
Ride-through time:.............................................35 ms
LOW RANGE POWER SUPPLY
Nominal:..................................................................24 to 48 VDC
Range:......................................................................20 to 60 VDC
ALL RANGES
Voltage withstand:.............................................2 × highest nominal voltage for 10 ms
Power consumption: .........................................15 W nominal, 20 W maximum
20 VA nominal, 28 VA maximum
Other manuals for 339
1
Table of contents
Other GE Protection Device manuals
Popular Protection Device manuals by other brands

Schweitzer Engineering Laboratories
Schweitzer Engineering Laboratories SEL-311C instruction manual

Siemens
Siemens SIPROTEC 4 7VK61 manual

Cardigo
Cardigo 91951 Instructions for use

SENSTAR
SENSTAR FPS-3 Installation & operation guide

Max-Air Systems
Max-Air Systems CAPR Series User instructions

SMA
SMA DC SPD KIT7 T1T2 Quick reference guide