GE SG 225 User manual

GE Digital Energy
Power Quality
User Manual
Uninterruptible Power supply
SG Series 225 & 300
225 & 300 kVA / 480Vac UL / S2
GE Consumer & Industrial SA
General Electric Company
CH – 6595 Riazzino (Locarno)
Switzerland
T +41 (0)91 / 850 51 51
F +41 (0)91 / 850 52 52
www.gepowerquality.com
imagination at work

Model: SG Series 225 & 300 UL S2
Issued by Product Document Department – Riazzino - CH
Date of issue: 06/15/2010
File name: OPM_SGT_USG_M22_M30_2US_V010
Revision: 1.0
Identification No.:
Up-dating
Revision Concerns Date
COPYRIGHT © 2010 by GE Consumer & Industrial SA
All rights reserved.
The information contained in this publication is intended solely for the purposes indicated.
The present publication and any other documentation supplied with the UPS system is not to be
reproduced, either in part or in its entirety, without the prior written consent of GE.
The illustrations and plans describing the equipment are intended as general reference only and are not
necessarily complete in every detail.
The content of this publication may be subject to modification without prior notice.

Modifications reserved Page 3/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
Dear Customer,
We thank you for selecting our products and are
pleased to count you amongst our very valued
customers at GE.
We trust that the use of the SG Series 225 & 300
Uninterruptible Power Supply system, developed and
produced to the highest standards of quality, will give
you complete satisfaction.
Please read carefully the User Manual, which contains
all the necessary information and describes all you need
to know about the use of the UPS.
Thank you for choosing GE !
START UP AND COMMISSIONING
A GE Global Services Field Engineer must perform start-up and
commissioning of the UPS. Please Contact GE. Global Services at least two
weeks prior to schedule start-up and commissioning at 1-800-637-1738, or
Distributed in the USA by:
Your service contact:
g
GE Consumer & Industrial SA
General Electric Company
CH – 6595 Riazzino (Locarno)
Switzerland
www.gepowerquality.com
g
GE Digital Energy
Power Quality
2501 Pecan Street
Bonham, TX 75418
T: +1 800-637-1738
F: +1 903-640-0533
http://www.gedigitalenergy.com/ups

Modifications reserved Page 4/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
Preface
Congratulations on your choice of a SG Series Uninterruptible Power Supply (UPS). It will
help eliminate Load disturbances due to unexpected power problems.
This Manual describes the function of the UPS module, the purpose and location of the
switches, the meaning of the system events related to the front panel indication, and
provides procedures for starting and stopping the equipment.
Please refer to the accompanying Installations Guide, which describes how to prepare the
installation site, and it provides weight, dimensions and procedures for moving, installing
and connecting the UPS.
While every care has been taken to ensure the completeness and accuracy of this manual,
GE assumes no responsibility or liability for any losses or damages resulting from the use
of the information contained in this document.
WARNING!
SG Series 225 & 300 is a product that needs to be installed by a licensed and
knowledgeable contractor.
We recommend that this manual be kept next to the UPS for future references.
If any problems are encountered with the procedures contained in this manual, please
contact your Service Center before you proceed.
This document shall not be copied or reproduced without the permission of GE.
Some of the information contained in this manual may be changed without notice to
reflect technical improvements.
Safety instructions
Read the safety instructions contained on the following pages carefully before the
installation of the UPS, options and battery system.
Pay attention to the rectangular boxes included in the text:
They contain important information and warning concerning electrical connections and
personnel safety.
Parallel version secured with RPA
When included in the text, this symbol refers to operation needed
only for parallel system.

Modifications reserved Page 5/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
Table of contents Page
1IMPORTANT SAFETY INSTRUCTIONS ........................................................................................................... 7
2LAYOUT .......................................................................................................................................................... 10
2.1 LAYOUT SG Series 225 & 300 ........................................................................................................................................................... 10
3INTRODUCTION ............................................................................................................................................ 11
4DESCRIPTION ................................................................................................................................................ 12
4.1 BLOCK DIAGRAM AND MAIN ELEMENTS ..................................................................................................................................... 12
4.2 OPERATION MODES.............................................................................................................................................................................. 13
4.2.1 Normal operation mode........................................................................................................................................................................... 13
4.2.2 eBoost™ operation mode (option) ....................................................................................................................................................... 13
4.2.3 Utility failure operation ............................................................................................................................................................................. 14
4.2.4 Utility recovery operation........................................................................................................................................................................ 14
4.2.5 Automatic Bypass ....................................................................................................................................................................................... 15
4.2.6 Manual Bypass (option)............................................................................................................................................................................. 15
4.3 PARALLEL SYSTEM OPERATION....................................................................................................................................................... 16
4.3.1 Introduction to the parallel system..................................................................................................................................................... 16
4.3.2 Features of RPA parallel system........................................................................................................................................................... 17
4.3.3 System control.............................................................................................................................................................................................. 17
4.3.4 Synchronization ........................................................................................................................................................................................... 17
4.3.5 Load sharing.................................................................................................................................................................................................. 17
4.4 RECTIFIERS PARALLELED ON THE SAME BATTERY.................................................................................................................. 18
4.5 RECYCLING AT THE END OF SERVICE LIFE.................................................................................................................................. 19
5CONTROL PANEL .......................................................................................................................................... 20
5.1 CONTROL PANEL.................................................................................................................................................................................... 20
5.2 TABLE OF FUNCTIONS AND INDICATIONS ON CONTROL PANEL ..................................................................................... 21
6LCD SCREEN .................................................................................................................................................. 23
6.1 HOME SCREEN ........................................................................................................................................................................................ 23
6.2 METERING ................................................................................................................................................................................................. 25
6.3 ALARMS...................................................................................................................................................................................................... 28
6.3.1 Events (alarms and messages).............................................................................................................................................................. 29
6.3.2 Alarms list........................................................................................................................................................................................................ 29
6.3.3 Messages list.................................................................................................................................................................................................. 33
6.3.4 Event report SG Series 225 & 300......................................................................................................................................................... 36
6.4 SETUP 37
6.5 COMMANDS ............................................................................................................................................................................................. 43
7OPERATION.................................................................................................................................................... 44
7.1 PROCEDURES FOR SINGLE SG Series 225 & 300 ..................................................................................................................... 45
7.1.1 Start-up of the SG Series 225 & 300 .................................................................................................................................................... 45
7.1.2 UPS shutdown with Load transfer on Manual Bypass Q2 (option)........................................................................................ 49
7.1.3 From Manual Bypass Q2 (option) to normal function VFI.......................................................................................................... 51
7.1.4 Complete UPS shutdown.......................................................................................................................................................................... 53
7.1.5 Restore to normal operation after “Load Off”................................................................................................................................. 54
7.1.6 Restore to normal operation after EPO (Emergency Power Off) ............................................................................................ 55

Modifications reserved Page 6/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
7.2 PROCEDURES FOR SG Series 225 & 300 PARALLEL SYSTEM AND PARALLEL SYSTEM WITH COMMON
BATTERY..................................................................................................................................................................................................... 56
7.2.1 SG Series 225 & 300 Parallel System start-up ................................................................................................................................ 56
7.2.2 Parallel System shutdown with Load transfer on Manual Bypass Q2 (option)................................................................ 61
7.2.3 From Manual Bypass Q2 (option) to normal function VFI.......................................................................................................... 63
7.2.4 Separate a UPS Unit from the Parallel System (System Redundancy)................................................................................ 65
7.2.5 Reconnect a UPS unit to a Parallel System...................................................................................................................................... 67
7.2.6 Complete Parallel System shutdown.................................................................................................................................................. 69
7.2.7 Restore to normal operation after “Load Off”................................................................................................................................. 71
7.2.8 Restore to normal operation after EPO (Emergency Power Off) ............................................................................................ 73
8OPTIONS......................................................................................................................................................... 75
8.1 COMMUNICATION OPTIONS ............................................................................................................................................................. 75
8.2 OPTIONS IN UPS CABINET.................................................................................................................................................................. 75
8.3 CONNECTION FOR OPTIONS............................................................................................................................................................. 76
8.3.1 Remote Signaling Box (RSB) .................................................................................................................................................................... 76
9MAINTENANCE.............................................................................................................................................. 77
9.1 MAINTENANCE........................................................................................................................................................................................ 77
9.1.1 Service check................................................................................................................................................................................................. 77
9.1.2 Fans and ventilation................................................................................................................................................................................... 77
9.1.3 Other components with limited lifetime............................................................................................................................................ 77
9.1.4 Battery.............................................................................................................................................................................................................. 78
9.1.5 Long shut-down periods of the UPS-system .................................................................................................................................. 78
9.1.6 UPS room conditions and temperature............................................................................................................................................. 78
9.1.7 Long shut-down periods of the UPS-system .................................................................................................................................. 78
10 NOTES............................................................................................................................................................. 79
10.1 NOTES FORM............................................................................................................................................................................................ 79

Modifications reserved Page 7/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
1 IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for models SG Series 225 & 300 that should be followed
during installation and maintenance of the UPS and battery.
GENERAL
- Move the UPS in an upright position in its original package to the final destination room.
To lift the cabinets, use a forklift or lifting belts with spreader bars.
- Check for sufficient floor and elevator loading capacity.
- Check the integrity of the UPS equipment carefully.
If you notice visible damage, do not install or start the UPS.
Contact the nearest Service Center immediately.
- WARNING! RISK OF ELECTRICAL SHOCK:
Do not remove covers, there are no user serviceable parts inside.
- After switching off takes 5 minutes for the DC capacitors to discharge because a lethally high voltage
remains at the terminals of the electrolytic capacitors.
- All maintenance and service work should be performed by qualified service personnel.
The UPS contains its own energy source (battery).
- The field-wiring outlets may be electrically live, even when the UPS is disconnected from the utility.
- Dangerous voltages may be present during battery operation.
- The battery must be disconnected during maintenance or service work.
- This UPS contains potentially hazardous voltages.
- Be aware that the inverter can restart automatically after the utility voltage is restored.
INSTALLATION
- This UPS must be installed and connected only by trained personnel.
- Verify accurately during Commissioning and Maintenance of the UPS, for the following:
Damaged components, squeezed wires and cables, or not correctly inserted plugs.
- After removing the sidewalls of the UPS, make sure that all earth connections when reassembling, are
correctly reattached.
- This UPS is intended for use in a controlled indoor environment free of conductive contaminants and
protected against animals intrusion.
- WARNING! HIGH EARTH LEAKAGE CURRENT:
Earth connection is essential before connecting to AC input!
- Switching OFF the unit does not isolate the UPS from the utility.
- Do not install the UPS in an excessively humid environment or near water.
- Avoid spilling liquids on or dropping any foreign object into the UPS.
- The unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed 104°F (40°C).
- Optimal battery life is obtained if the ambient temperature does not exceed 77°F (25°C).
- It is important that air can move freely around and through the unit. Do not block the air vents.
- Avoid locations in direct sunlight or near heat sources.
STORAGE
- Store the UPS in a dry location; storage temperature must be within -13°F (-25°C) to 131°F (+55°C).
- The optimal temperature for Battery storage is 68°F (20°C) to 77°F (25°C) and shall never exceed the range
-4°F (-20°C) to 104°F (40°C).
- If the unit is stored for a period exceeding 3 months, the battery must be recharged periodically (time
depending on storage temperature).
BATTERY
- The battery-voltage is dangerous for person’s safety.
- When replacing the battery, use the same cells number, voltage (V), capacity (Ah).
All the battery used, shall be of the same manufacturer and date of production.
- Proper disposal or recycling of the battery is required.
Refer to your local codes for disposal requirements.
- Never dispose of battery in a fire: they may explode.
- Do not open or mutilate battery: their contents (electrolyte) may be extremely toxic.
If exposed to electrolyte, wash immediately with plenty of water.
- Avoid charging in a sealed container.
- Never short-circuit the batteries.
When working with batteries, remove watches, rings or other metal objects, and only use insulated tools.
- In case of air shipment, the cables +/- going to the battery fuses/terminals shall be disconnected and isolated.

Modifications reserved Page 8/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
Safety instructions when working with battery
EXTERNAL BATTERY MUST BE INSTALLED AND CONNECTED TO THE UPS BY
QUALIFIED SERVICE PERSONNEL ONLY.
INSTALLATION PERSONNEL MUST READ THIS ENTIRE SECTION BEFORE HANDLING
THE UPS AND BATTERY.
DANGER!
Full voltage and current are always present at the battery terminals.
The battery used in this system can provide dangerous voltages, extremely high currents and a
risk of electric shock.
If the terminals are shorted together or to ground they may cause severe injury.
You must be extremely careful to avoid electric shock and burns caused by contacting battery
terminals or shorting terminals during battery installation.
Do not touch uninsulated battery terminals.
A qualified service person, who is familiar with battery systems and required precautions, must
install and service the battery.
The installation must conform to national and local codes.
Keep unauthorized personnel away from the battery.
The qualified service person must take these precautions:
1 Wear protective clothing, such as rubber gloves and boots and protective eye wear
Batteries contain caustic acids and toxic materials and can rupture or leak if mistreated.
Remove rings and metal wristwatches or other metal objects and jewelry.
Do not carry metal objects in your pockets where the objects can fall into the battery
cabinet.
2 Tools must have insulated handles and must be insulated so that they will not short battery
terminals.
Do not allow a tool to short between individual or separate battery terminals or to the
cabinet or rack.
Do not lay tools or metal parts on top of the battery, and do not lay them where they could
fall onto the battery or into the cabinet.
3 Install the battery as shown on the drawing provided with the battery.
When connecting cables, never allow a cable to short across a battery’s terminals, the
string of battery, or to the cabinet or rack.
4 Align the cables on the battery terminals so that the cable lug will not contact any part of
the cabinet or rack, even if the battery is moved.
Keep the cable away from any sharp metal edges.
5 Install the battery cables in such a way that the UPS or battery cabinet doors cannot pinch them.
6 Do not connect the battery terminal to Ground.
If any battery terminal is inadvertently grounded, remove the source of the ground.
Contacting any part of a grounded battery can cause a risk of electric shock.
7 To reduce the risk of fire or electric shock, install the battery in a temperature and humidity
controlled indoor area, free of contaminants.
8 Battery system chassis ground (earth) must be connected to the UPS chassis ground (earth).
If you use conduits, this ground conductor must be routed in the same conduit as the
battery conductors.
9 Where conductors may be exposed to physical damage, protect the conductors in
accordance with all applicable codes.
10 If you are replacing the battery or repairing battery connections, shut OFF the UPS and
remove the battery fuses.

Modifications reserved Page 9/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
Safety symbols and warnings
Safety warnings
The text of this manual contains some warnings to avoid risk to the persons and to avoid damages to
the UPS system and the supplied critical loads.
The non-observance of the warnings reminding hazardous situations could result in human injury and
equipment damages.
Please pay attention to the meaning of the following warnings and symbols.
Throughout this manual the following symbols are defined:
WARNING, if instruction is not followed injury or serious equipment damage may
occur!
CAUTION, internal parts have dangerous voltage present.
Risk of electric shock!
PE (Earth) – GND (Ground)
PROTECTIVE GROUNDING TERMINAL:
A terminal which must be connected to earth ground prior to making any other
connection to the equipment.
A terminal to which or from which an alternating (sine wave) current or voltage
may be applied or supplied.
A terminal to which or from which a direct current or voltage may be applied or
supplied.
This symbol indicated the word “phase”.
This symbol indicates the principal on/off switch in the on position.
This symbol indicates the principal on/off switch in the off position.

Modifications reserved Page 10/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
2 LAYOUT
2.1 LAYOUT SG Series 225 & 300
SGS_225-300_S2_UPS_GE_02
Fig. 2.1-1 SG Series 225 & 300 general view
4
3
2
1
2
3
4
1
0OFF
Q2
I ON
Q1
I ON
0OFF
SGS_225-300_S2_UPS_03
43
2
1
15
14
13
12 98
20
19
567
17
16 18 21
10
22
11
Fig. 2.1-2 SG Series 225 & 300 general view with open doors
0OFF
Q2
I ON
Q1
I ON
0OFF
SGS_225-300_S2_Switches Q1-Q2_01
Fig. 2.1-3 Manual operated switches
Fig. 2.1-4 Control panel
P4 Customer Interface Board
Q1 UPS output switch
Q2 Manual Bypass switch (option)
SNMP 3-ph SNMP/WEB plug-in adapter (option)
XA Terminals for 24Vdc
Auxiliary Power Supply connection
XA
SGS_225-300_Customerinterface_03
4
3
2
1
1
2
3
4
P4
XB
SNMP
Fig. 2.1-5 Connectivity Rack XB Terminals for EPO (Emergency Power
Off) connection

Modifications reserved Page 11/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
3 INTRODUCTION
An Uninterruptible Power Supply (UPS) provides the power for critical loads that need a reliable,
continuous, disturbance free supply.
In case the power provided by the Utility fails, or exceeds the permitted tolerances, the power to supply
the Load is provided by the Battery for the specified time at the rated Load (or longer at a reduced Load)
or until the Utility power returns.
SG Series 225 & 300 is a true double conversion VFI (Voltage Frequency Independent) UPS system where
the Load is continuously supplied by the Inverter through the Rectifier.
In case of trouble on the Inverter Output Voltage, or when overload or short-circuit on the output occur,
the Load is instantly transferred to the Utility via the Automatic Bypass.
The UPS automatically returns to normal mode when the failure condition is restored.
Key features:
• More Critical equipment supported
Rated at 0.9 Power Factor, SG Series 225 & 300 delivers more real power than other UPS in the
market.
With today’s trend toward power factor corrected loads, SG Series 225 & 300 can support more
total Load than any other UPS available, allowing you to support a greater number of today’s
enterprise computing Power Factor Corrected (PFC) equipment.
• No single point of failure
Redundant Parallel Architecture (RPA) is an exclusive GE technology.
With RPA, SG Series 225 & 300 UPS are controlled in a true peer-to-peer configuration where all
critical elements and functions (including Bypass) are redundant.
SG Series 225 & 300 is designed to be the most reliable power protection system available on the
market today.
• High Efficiency
Using IGBT technology and Space Vector Modulation (SVM) strategy, SG Series 225 & 300 offers low
output voltage distortion and provides efficiencies up to 93%.
• Fully digital
Digital Signal Processor (DSP), Flash memory and SVM strategy, are the technology corner stones
of new age of power quality and power reliability.
• Extremely flexible
Tailor made power protection to meet your individual installation requirements; SG Series 225 &
300 offers various options like input harmonic filters and our comprehensive GE Power Diagnostic
software suite for mission control and data protection to cover all your application needs.

Modifications reserved Page 12/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
4 DESCRIPTION
4.1 BLOCK DIAGRAM AND MAIN ELEMENTS
Fig. 4.1-1 Block diagram
The SG Series 225 & 300 system can be divided into the following main elements:
Control System
SG Series 225 & 300 is designed with microprocessor-controlled signal processing circuits.
The interface between the operator and the unit is provided by the monitoring system on the front panel.
This monitoring system consists of an active mimic diagram, a keyboard and a backlit display.
Rectifier
The standard Rectifier consists of a 6-pulse SCR-bridge, which converts the three-phase Utility Voltage
into a controlled and regulated DC-voltage.
This regulated DC-voltage is used to supply power to the Inverter, and to provide charging power to the
Battery.
Inverter
The Inverter converts the DC voltage into a three-phase AC-voltage with constant amplitude and
frequency, which is completely independent and isolated from the AC-input voltage.
Automatic Bypass
The Automatic Bypass consists of a static semiconductor-switch (SSM: Static Switch Module), used to
provide an uninterrupted transfer of the Load from Inverter to Utility.
Back-feed Protection
All SG Series UPS's are equipped with an automatic system for the protection against voltage back
feeding towards Utility, through the Bypass (Applied Standard IEC 62040-1).
This protection works automatically by opening contactor K6 and eventually K7, and acts in case of
internal defects of the system, or due to wrong manipulations on the Manual Bypass Q2 (option).
Manual Bypass (option)
The Manual Bypass consists of a pair of manual switches (Q1 and Q2), which removes the UPS from the
Load for maintenance, while still supplying the Load with power directly from the Utility.
Battery
The Battery supplies the DC power to the Inverter when the Utility is out of accepted tolerances.

Modifications reserved Page 13/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
4.2 OPERATION MODES
4.2.1 Normal operation mode
During normal operation, the Rectifier converts
input AC power to DC.
The DC power provides input power for the
Inverter and charging power for the Battery.
The Inverter converts the DC power to continuous
and regulated AC power, which supplies the
critical load.
The control panel reports the Battery charge
status and the expected backup time with the
actual load.
Fig. 4.2.1-1 Block diagram normal operation mode
4.2.2 eBoost™ operation mode (option)
eBoost™
ehigh efficiency (up to 99%)
Boost fast power transfer (< 4ms)
When the eBoost™ Operation Mode is selected,
and the Utility Power is available, the Load is
normally powered through the Automatic
Bypass.
When the Utility Voltage is detected out of the
prescribed tolerances, the Load is automatically
transferred to the Inverter.
Fig. 4.2.2-1 Energy flow in eBoost™ Operation Mode
When the Utility recovers, the Load returns to the Automatic Bypass after a variable time defined by the
control unit.
The eBoost™ Operation Mode can be configured directly by the user for scheduled activation,
considering the Utility reliability and criticality of the Load.
The selection between the two operation modes “VFI Mode and eBoost™ Operation Mode”, or switching
between operation modes at required time, can be done through the UPS control panel (see Section 7.4
/
eBoost).
NOTE !
The eBoost™ Operation Mode is available only if enabled at the factory or by a GE
GLOBAL SERVICES FIELD ENGINEER.

Modifications reserved Page 14/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
4.2.3 Utility failure operation
When the Utility is no longer within acceptable
tolerances, the Battery will provide the DC power to the
Inverter.
The Inverter will maintain continuous AC power to the
Load until the Battery Voltage reaches the lower limit of
the Inverter operation capability.
During the discharge, the LCD screen displays the
estimated time the Battery can support the critical Load.
Prior to the Battery completely discharging, the "stop
operation"alarm (shutdown imminent) warns the
operator that the Battery is almost discharged and the
UPS is about to shut down.
Fig. 4.2.3-1 Block diagram Utility Failure operation
In case of parallel operation
With a parallel system for power capacity (see Section 4.3)
• With the Bypass Utility power available, a low Battery warning on any unit will cause the Load to
be transferred to Utility (after a selectable time delay).
• With Bypass Utility power not available, a low Battery warning on any unit will start the “stop
operation” timer (adjustable). The Load will shut down at the end of the “stop operation” time period.
With a parallel system for redundancy (see Section 4.3)
• When a Battery low warning occurs on a unit not necessary to support the present load, this unit
will shut down after a timeout period (selectable). The Load is shared between the other units.
As the warning occurs on one unit necessary to support the present load, the system starts the
"stop operation" timeout (selectable).
The Load will shut down at the end of the “stop operation” time period.
4.2.4 Utility recovery operation
As soon as the AC input power recovers, the Rectifier will
start automatically, supplying DC power to the Inverter
and recharging the Battery.
If the Inverter was previously shut down due to low
Battery, the Load will be initially powered by Utility
through the Automatic Bypass.
When the Battery is recharged enough to ensure a
minimum time of operation with the present load, the
Inverter will start automatically and the Load will be
transferred back to the Inverter.
Fig. 4.2.4-1 Block diagram Utility recovery operation
In case of parallel operation
When the AC input power recovers, the Rectifiers will start up sequentially, according to their
number in the parallel system. This minimizes the initial inrush current.
The Inverters will start up automatically, but only when the Battery has recharged enough for a
minimum runtime with the present load.
When enough Inverters to supply the Load have been restarted, the Load will be transferred from
the Automatic Bypass back to the Inverter output.

Modifications reserved Page 15/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
4.2.5 Automatic Bypass
In normal operation, the Load is supplied by the
Inverter.
When the control system detects a fault in the
Inverter, an overload condition or a short-circuit
condition, the Automatic Bypass will transfer the
critical Load to the Utility without interruption.
When the Inverter recovers, or the overload or
short-circuit condition is corrected, the Load will
be automatically transferred back to the Inverter.
If the UPS is unable to return to normal mode
following an automatic transfer to Bypass mode,
an alarm condition will be initiated.
A Manual Bypass (operator initiated) will not be
considered as an alarm condition.
Fig. 4.2.5-1 Block diagram Automatic Bypass
In case of parallel operation
Each unit has its own internal Bypass.
These units are continuously exchanging information, enabling all of the internal Bypass circuits in a
parallel system to operate simultaneously.
If the Inverter of a unit fails, its Bypass circuit remains available to the Parallel System.
It is excluded only if the unit is separated from the common bus by opening its output switch Q1.
4.2.6 Manual Bypass (option)
The Manual Bypass circuit consists of Q1 and Q2
manual switches, which permits transfer of the
Load directly to the unconditioned AC power
without interruption, leaving the UPS available for
maintenance.
Fig. 4.2.6-1 Block diagram Manual Bypass

Modifications reserved Page 16/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
4.3 PARALLEL SYSTEM OPERATION
4.3.1 Introduction to the parallel system
Two or more equal power units can be paralleled to increase the output power (paralleling for capacity)
or to improve the overall reliability of an UPS system (paralleling for redundancy).
The outputs of parallel units are connected to a common power bus, and in normal operation the units
connected on the parallel bus share the Load equally.
The modular concept of SG Series 225 & 300 allows parallel operation of up to 6 units, without using
paralleling switchgear, external bypass circuits or common control circuitry (see Fig. 4.3.1-1).
Parallel units for power capacity
Several units can be paralleled in order to achieve output power greater than the maximum power of a
single unit.
The maximum total power shared between the paralleled units is equal to the total installed nominal
power.
In the event of a failure of one unit, the power supplied by the UPS system becomes insufficient and the
Load will be transferred to the Utility Bypass source.
Parallel units for redundancy
The nominal power rating of the n+1 out of n redundant paralleled modules must be equal to or greater
than the required Load power.
The Load will be equally shared by the nunits connected on the output bus.
Should one of the nparalleled units trip Off-line, the remaining (n+1) modules will supply the load,
maintaining conditioned power to the critical load.
From this results higher reliability and security for the Load plus a higher MTBF (Mean Time Between
Failures).
Fig. 4.3.1-1 Block diagram parallel system operation

Modifications reserved Page 17/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
4.3.2 Features of RPA parallel system
The SG Series 225 & 300 Parallel System is designed to provide a complete Redundant Parallel
Architecture, and is free from common equipment.
Not only the Inverters are redundant, but also the Bypass functions are designed with redundant
modular concept.
When one UPS needs maintenance or service, the Load is powered by the other units supplying the
Load bus.
The redundant communication bus to which all units are connected keeps each unit informed about the
status of all the other units.
The control panel located on each unit allows controlling and monitoring the status of this unit.
4.3.3 System control
A high-speed redundant, serial communication bus guarantees the exchange of data and thus the
communication between the CPU's of each unit.
Each module controls it's own function and operational status and communicates with all other
modules, in order to act or react if necessary, adapting it to the new conditions.
4.3.4 Synchronization
All units are identical, but one unit is arbitrarily selected as the reference and all the other units
synchronize to this unit, which in turn, synchronizes to the Utility Bypass voltage, as long as the later is
within tolerances.
In case of reference failure, another unit in the parallel system is automatically chosen to take over the
reference role.
The Bypass Input for all the units of the parallel system must be supplied from the same AC source (no
phase shift allowed between them).
4.3.5 Load sharing
On each unit of the parallel system, Inverter Output Voltage and Current are measured and applied to a
Load sharing bus.
An eventual difference between the units is therefore automatically equalized.
NOTE !
It is strongly recommended that no transformers, automatic circuit breakers or
fuses should be inserted between the unit’s output and the Load common bus
bars.
However, it is recommended that a disconnect or isolation switch be inserted.

Modifications reserved Page 18/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
4.4 RECTIFIERS PARALLELED ON THE SAME BATTERY
NOTE !
A parallel system with a Common Battery for two or more Rectifiers, requires a
particular installation and adequate setting of some parameters, (accessible only
through password), and can therefore only be done by a QUALIFIED ENGINEER from GE.
Usually each Rectifier-Inverter Unit runs with its own Battery.
In case of parallel units are running with a Common Battery (max. 4 UPS - see Fig 4.4-1), the sharing
circuit between individual Rectifier is integrated in the communication bus of the system in order to
assure an equal sharing of the Rectifiers output currents.
Fig. 4.4-1 Diagram RPA system with Rectifiers on Common Battery
1 –
2 –
3 –
4 –
5 –
6 –
7 –
8 –
Rectifier
Inverter
Automatic Bypass
Manual Bypass
Utility Power
Load Bus Bar
External Battery Fuse
Battery
Pay attention to the following recommendations:
• The units delivered for this functioning mode needs a special parameters setting, so they must be
prepared in advance before the installation.
• The installation must be performed only with the UPS system must be completely shut down.
• The AC Rectifiers input power (5) must be the same, with clockwise phase rotation for each unit.
• Each Rectifier must be set for the same floating DC voltage and the same Battery current limitation.
• It is mandatory to install the fuses / MCCB (7) on each line connecting the Rectifiers to the common
Battery for maintenance / safety reasons.
• In case one must be powered down for maintenance, switch-OFF the concerned unit before open
the DC fuses / MCCB on the Battery line (7).
• It is mandatory to connect an external NO free contact “Battery Fuses” to the UPS and to enable the
function by setting the parameter (see Section 4.1 of the “Installation Guide”).
• If an emergency generator set supply the UPS, and the free contact “Generator ON” is connected to
the Customer interface, connect a separate NO free contact on each parallel unit.
• The parameters enabling the Battery test, both manual and automatic, must be set in the same
mode on all the units having the Rectifiers on Common Battery.
• Do not connect the temperature sensor for automatic battery floating voltage compensation.
• Do not enable the function Boost charge (parameter 87).

Modifications reserved Page 19/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
4.5 RECYCLING AT THE END OF SERVICE LIFE
NOTE !
This product has been designed to respect the
environment, using materials and components respecting
eco-design rules.
It does not contain CFCs (chlorofluorocarbons) or HCFCs
(hydrochlorofluorocarbons).
RECYCLING AT THE END OF SERVICE LIFE !
GE, in compliance with environment protection
recommends to the User that the UPS equipment, at the
end of its service life, must be recovered conforming to
the local applicable regulations.
WARNING !
Leads contained in the batteries is a dangerous substance
for the environment, therefore it must be correctly
recycled by specialized companies!

Modifications reserved Page 20/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
5 CONTROL PANEL
5.1 CONTROL PANEL
Fig. 5.1-1 Control panel
The control panel, positioned on the UPS front door, acts as the UPS user interface and comprises of the
following elements:
• Back lit Graphic Display (LCD) with the following characteristics:
− Multilanguage communication interface:
English, German, Italian, Spanish, French, Finnish, Polish, Portuguese, Czech, Slovakian, Chinese,
Swedish, Russian and Dutch;
− Synoptic Diagram indicating UPS status.
• Command pushbuttons and parameters setting.
• UPS status control LED.
This manual suits for next models
2
Table of contents
Other GE UPS manuals

GE
GE FGC TLE Series User manual

GE
GE 1000-1500-2000-3000 VA User manual

GE
GE Digital Energy LP 11U Instruction Manual

GE
GE 225 User manual

GE
GE Digital Energy LP 31 Series User manual

GE
GE VH Series 700 User manual

GE
GE SG 750 UL S2 Series User manual

GE
GE Digital Energy SG Series User manual

GE
GE 700 VA User manual

GE
GE Match User manual

GE
GE Digital Energy LP 33 Series User manual

GE
GE TLE Scalable Series User manual

GE
GE VH UL series User manual

GE
GE Digital Energy SitePro 400 VAC CESeries 7 User manual

GE
GE Lanpro 33 User manual

GE
GE SG SERIES 10 User manual

GE
GE 8 Series User manual

GE
GE GT6000 User manual

GE
GE LP 33U Series User manual

GE
GE SG Series 400 User manual