GE Digital Energy LP 33 Series User manual

g G
E
LP 33 / 10 - 20 - 30 kVA
OPERATING MANUAL
UNINTERRUPTIBLE POWER SUPPLY
Digital Energy TM
LP 33
10 – 20 – 30 kVA
Series 4
g
GE Digital Energy SA
6595 Riazzino (Locarno)
Switzerland
Telephone: +41 (0) 91/850 51 51
Fax: +41 (0) 91/850 51 44
LP Series UPS Technology for the digital world

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 2/82 Operating Manual LP 33 / 10-20-30 kVA
Model: LP 33 / 10 - 20 - 30 kVA / Series 4
Date of issue: 01.08.2003
File name: OPM_LPS_33E_10K_30K_4CN_V010
Revision: 1.0
Author: Raimondo Bizzozero
Identification No.
Up-dating
Revision Concerns Date
COPYRIGHT © 2003 by GE
All rights reserved.
The information contained in this publication is intended solely for the purposes indicated.
The present publication and any other documentation supplied with the UPS system is not to be
reproduced, either in part or in its entirety, without the prior written consent of GE.
The illustrations and plans describing the equipment are intended as general reference only and
are not necessarily complete in every detail.
The content of this publication may be subject to modification without prior notice.

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 3/82 Operating Manual LP 33 / 10-20-30 kVA
Dear Customer,
We thank you for selecting our products
and are pleased to count you amongst
our very valued customers at GE.
We trust that the use of the LP 33
Uninterruptible Power Supply system,
developed and produced to the highest
standards of quality, will give you
complete satisfaction.
Please read carefully the Operating
Manual, which contains all the
necessary information and describes all
you need to know about the use of the
UPS.
Thank you for choosing GE !
Manufactured by: Distributed by: Your service contact:
g
GE
GE Digital Energy SA
6595 Riazzino (Locarno)
Switzerland

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 4/82 Operating Manual LP 33 / 10-20-30 kVA
Table of contents Page
1SAFETY RULES......................................................................................................................6
1.1 IMPORTANT SAFETY RULES ........................................................................................... 7
1.2 SAFETY SYMBOLS AND WARNINGS...............................................................................9
2INTRODUCTION .....................................................................................................................10
2.1 GENERAL DESCRIPTION..................................................................................................10
3DESCRIPTION ........................................................................................................................11
3.1 PRINCIPAL DIAGRAM AND MAIN ELEMENTS DESCRIPTION ....................................... 11
3.2 OPERATION MODES .........................................................................................................12
3.3 RPA PARALLEL SYSTEM .................................................................................................. 15
3.4 SERVICE AND TECHNICAL SUPPORT ............................................................................16
3.5 WARRANTY........................................................................................................................16
3.6 RECYCLING AT THE END OF SERVICE LIFE.................................................................. 17
4INSTALLATION.......................................................................................................................18
4.1 TRANSPORT ......................................................................................................................18
4.1.1 Dimensions and weight ................................................................................................ 19
4.2 DELIVERY...........................................................................................................................20
4.3 STORAGE...........................................................................................................................20
4.3.1 Storage of the UPS ......................................................................................................20
4.3.2 Storage of the battery...................................................................................................21
4.4 PLACE OF INSTALLATION ................................................................................................ 22
4.5 VENTILATION AND COOLING...........................................................................................23
4.6 UNPACKING .......................................................................................................................24
4.7 CABLING.............................................................................................................................26
4.7.1 Fuse discrimination (co-ordination of breakers tripping)...............................................27
4.7.2 Fuse ratings.................................................................................................................. 28
4.7.3 Input / output cable ratings ........................................................................................... 29
4.8 CONNECTIONS..................................................................................................................30
4.8.1 Common input mains ...................................................................................................30
4.8.2 Separate input mains (option) ...................................................................................... 31
4.8.3 External battery connection..........................................................................................32
4.8.4 RPA system - Control bus connection..........................................................................33
4.9 UPS FUNCTIONING AS FREQUENCY CONVERTER ......................................................35
5LAYOUT ..................................................................................................................................36
5.1 LAYOUT LP 33 / 10 - 20 KVA .............................................................................................36
5.2 LAYOUT LP 33 / 30 KVA ....................................................................................................37
6SYSTEM HANDLING ..............................................................................................................38
6.1 CONTROL PANEL .............................................................................................................. 38
6.2 COMMAND PUSH BUTTONS AND SWITCHES................................................................ 39

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 5/82 Operating Manual LP 33 / 10-20-30 kVA
7LCD SCREEN..........................................................................................................................40
7.1 METERING SCREENS (METERING)................................................................................. 40
7.2 EVENT SCREENS (ALARM) .............................................................................................. 43
7.2.1 Alarms list.....................................................................................................................43
7.2.2 Messages list................................................................................................................ 47
7.2.3 Event report LP 33 ..........................................................................................................50
7.3 MENU SCREENS (MENU) .................................................................................................51
7.3.1 User parameters screen...............................................................................................52
8OPERATION............................................................................................................................56
8.1 PROCEDURES FOR SINGLE LP 33 .................................................................................... 56
8.1.1 Start-up of the LP 33.......................................................................................................56
8.1.2 UPS shutdown with load transfer on manual bypass (Q2) ........................................... 58
8.1.3 Start-up following the operation on manual bypass......................................................60
8.1.4 Complete shutdown......................................................................................................62
8.2 PROCEDURES FOR PARALLEL SYSTEM LP 33................................................................ 63
8.2.1 Parallel System start-up of the LP 33 .............................................................................63
8.2.2 Parallel UPS shutdown with load transfer on manual bypass (Q2) .............................. 65
8.2.3 Start-up following the operation on maintenance bypass............................................. 67
8.2.4 Shutdown of a single unit in a parallel system..............................................................68
8.2.5 Start-up an additional unit in a parallel system............................................................. 69
8.2.6 Complete shutdown of a parallel system...................................................................... 70
9CUSTOMER INTERFACE....................................................................................................... 71
9.1 SERIAL PORT J27 - RS232................................................................................................ 71
9.2 RELAY CARD .....................................................................................................................72
9.3 EPO (EMERGENCY POWER OFF) ...................................................................................73
10 OPTIONS ...............................................................................................................................74
10.1 OPTIONS GENERAL VIEW................................................................................................74
10.2 OPTIONS ASSEMBLY AND CONNECTION ......................................................................75
10.2.1 Customer Interface.......................................................................................................75
10.2.2 Optional battery cabinet connection ............................................................................. 78
11 MAINTENANCE .....................................................................................................................79
11.1 GENERAL MAINTENANCE ................................................................................................ 79
11.2 COOLING FAN MAINTENANCE ........................................................................................79
11.3 BATTERY MAINTENANCE................................................................................................. 79
11.4 SERVICE REQUIRED.........................................................................................................80
12 NOTES ...................................................................................................................................81
12.1 NOTES FORM .................................................................................................................... 81
13 ANNEX ...................................................................................................................................82
13.1 TECHNICAL DATA SHEET ................................................................................................82
13.2 SCHEMATICS.....................................................................................................................82

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 6/82 Operating Manual LP 33 / 10-20-30 kVA
1 SAFETY RULES
With this document, GE gives to the user all the necessary information about the correct use of the
UPS.
Please read carefully this Operating Manual before installing or operating the UPS.
We recommend that this manual be kept next to the UPS for future references.
If any problems are encountered with the procedures contained in this manual, please contact the
nearest Service Centre before you proceed.
All UPS installation, maintenance and service work should be performed by qualified service
personnel only.
The KNOWLEDGE and the FULLY compliance of the safety instructions and the
warning contained in this manual are
THE ONLY CONDITION
to avoid any dangerous situations during installation, operation, maintenance
work, and to preserve the maximum reliability of the UPS system.
NOTE !
LP 33 / 10 - 20 - 30 kVA is a Class A-UPS Product (according to EN 50091-2).
In a domestic environment, this product may cause radio interference, in
which case, the user may be required to take additional measures.
While every care has been taken to ensure the completeness and accuracy
of this manual, GE assumes no responsibility or liability for any losses or
damages resulting from the use of the information contained in this
document.
GE
refuses any responsibility in case of non-
observance, unauthorised alterations or improper
use of the delivered UPS.

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 7/82 Operating Manual LP 33 / 10-20-30 kVA
1.1 IMPORTANT SAFETY RULES
GENERAL
• Move the UPS in an upright position in its original package to the final destination room.
• To lift the cabinets, use a forklift or lifting belts with spreader bars.
• Check for sufficient floor and elevator loading capacity.
• Check carefully the integrity of the UPS equipment.
In case you note some visible damage, do not put the UPS under voltage, but contact the
nearest Service Centre.
• Warning: risk of electrical shock.
• Apart the front hinged lockable doors, do not remove any covers, there are no user
serviceable parts inside.
• All maintenance and service work should be performed by qualified service personnel.
• The outlet-bars may be electrically live, even when the UPS is disconnected from the mains.
• Dangerous voltages may be present during battery operation.
• The battery protections must be removed before any maintenance or service work.
• Be aware that the inverter can restart automatically after the utility voltage is restored.
INSTALLATION
• This UPS must be installed and connected only by trained personnel.
• Verify accurately during Commissioning and Maintenance of the UPS, for the following:
Damaged components, squeezed wires and cables, or not correctly inserted plugs.
• After removing the sidewalls of the UPS, make sure that all earth connections when
reassembling, are correctly reattached.
• This UPS is intended for use in a controlled indoor environment free of conductive
contaminants and protected against animals intrusion.
• High earth leakage current: Earth connection essential before connecting to AC input.
• Switching OFF the unit does not isolate the UPS from the mains.
• Do not install the UPS in an excessively humid environment or near water.
• Avoid spilling liquids on or dropping any foreign object into the UPS.
• The unit must be placed in a sufficiently ventilated area; the ambient temperature should not
exceed 40°C (104°F).
• Optimal battery life is obtained if the ambient temperature does not exceed 25°C (77°F).
• It is important that air can move freely around and through the unit.
• Do not block the air vents.
• Avoid locations in direct sunlight or near heat sources.

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 8/82 Operating Manual LP 33 / 10-20-30 kVA
STORAGE
• Store the UPS in a dry location; storage temperature must be within -25°C to 55°C (-13°F to
131°F).
• If the unit is stored for a period exceeding 3 months, the batteries must be recharged
periodically (time depending on storage temperature).
BATTERY
• Warning: the nominal battery-voltage is normally higher than 2 x 240 VDC.
• Never short circuit battery.
• When working with battery, remove watches, rings or other metal objects, and only use
insulated tools.
• Avoid charging in a sealed container.
• When replacing the battery, use the same number and voltage (V) and capacity (Ah).
• All the cells in the same battery string should be of the same type and the same age.
• Do not connect battery strings of different type in parallel.
• Proper disposal or recycling of the batteries is required.
Refer to your local codes for disposal requirements.
• Never dispose of battery in a fire: it may explode.
• Do not open or mutilate batteries: their contents (electrolyte) may be extremely toxic.
If exposed to electrolyte, wash immediately with plenty of water.
WARNING !
The UPS contains hazardous voltages.
Observe carefully the safety instructions to prevent
risk of electrical shock.
Parallel version secured with RPA
When included in the text, this symbol refers to operation
needed only for parallel system.

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 9/82 Operating Manual LP 33 / 10-20-30 kVA
1.2 SAFETY SYMBOLS AND WARNINGS
Safety warnings
The text of this manual contains some warnings to avoid risk to the persons and to avoid damages
to the UPS system and the supplied critical loads.
The non-observance of the warnings reminding hazardous situations could result in human injury
and equipment damages.
Please pay attention to the meaning of the following warnings and symbols:
WARNING !
Referred to procedures or operations which could cause damages to the
persons or to the system, when not correctly operated.
NOTE !
Warns the user about important operations or procedures described in this
manual.
Safety symbols
When the text includes one or more of the following symbols, that means exist a potentially
hazardous situations.
Please remind the meaning of each symbol.
CAUTION
Related to all the potentially hazardous situations which may result in injury.
DANGER OF PARTS ELECTRICALLY LIVE
Related to all the situation with potentially hazardous voltage.
DANGER OF EXPLOSION
Used to indicate conditions where exploding parts can cause serious injury.
DANGER OF CRUSHING
Used when moving the equipment due to the heavy weight.
DANGER OF OVERHUNG LOAD
Used when the equipment is lifted by a crane.
DO NOT TOUCH
Risk of parts with hazardous voltages or parts in movement.

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 10/82 Operating Manual LP 33 / 10-20-30 kVA
2 INTRODUCTION
2.1 GENERAL DESCRIPTION
The LP 33 Uninterruptible Power Supply (UPS) provides the energy supply for critical loads which
need a reliable, continuous free from voltage disturbances and frequency fluctuations supply.
In case the mains fails, or it exceeds the permitted tolerances, the energy to supply the load is
furnished by the battery with a backup time dependent on its capacity, until the mains recovers.
LP 33 is a truly On-line double conversion Uninterruptible Power Supply (UPS),
equipped with automatic bypass, where the load is normally supplied by the
inverter.
LP 33 can be configured, if chosen, for the IEM mode (Intelligent Energy
Management) permitting the maximum energy saving.
The main typical performances of the LP 33 system are the following:
• On-line double conversion technology to provide an excellent quality power supply.
• Input power factor 1.
• Input current THD 8%.
• Automatic bypass and manual bypass to improve reliability and maintenance.
• Microprocessor controlled supervision.
• Dual AC inputs (optional).
• IEM mode operation (Intelligent Energy Management).
• Compact and agreeable design expressly conceived for “Office environment”.
• Low level acoustic sound, 50 dB (A) (10 and 20kVA) and 55 dB (A) (30kVA), to avoid
noise to the persons operating in the same environment.
• Multi-language LCD screen.
• Total battery management: SBM (Superior Battery Management)
• High battery capacity, 25 minutes (10 kVA) and 10 minutes (20 and 30 kVA), with battery
housed in the UPS cabinet.
• Wide rectifier input voltage tolerance: 324 ÷478 VAC (phase - phase).
• Wide rectifier input frequency tolerance: +/-10% (45 ÷55 for 50 Hz and 54 ÷66 for 60 Hz).
• RPA (Redundant Parallel Architecture) up to 4 units.
• GE Connectivity.
• Compliance with European standard 50091-2.

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 11/82 Operating Manual LP 33 / 10-20-30 kVA
3 DESCRIPTION
3.1 PRINCIPAL DIAGRAM AND MAIN ELEMENTS DESCRIPTION
Fig. 3.1-1 UPS principal diagram
The Uninterruptible Power Supply System LP 33 / 10 - 20 - 30 kVA can be divided into the following
main elements:
Electronics
The UPS is designed with a microprocessor–controlled supervision and diagnostic system.
Communication between user and UPS is achieved by the front panel consisting of an LCD
screen, displaying the operation modes, the measurements and the events / alarms.
Rectifier
The rectifier converts the 3-phase mains voltage into a controlled and regulated DC-voltage, in
order to supply power to the booster, and to charge the battery through the battery-charger.
Inverter
The inverter converts the DC voltage into a three-phase AC-voltage with constant amplitude and
frequency, which is completely independent from the AC-input voltage.
Automatic Bypass
The automatic bypass consists of a static semiconductor-switch (SSR: Static Switch Relay), used
to provide an uninterrupted transfer of the load from inverter to mains when operating in On-line
mode.
If chosen the IEM mode, the SSM transfer the load from mains to inverter in case the utility fails.
Back-Feed Protection
All LP 33 UPS’s are equipped with an automatic system for the protection against voltage back
feeding towards Utility, through the Bypass (Applied Standard IEC 62040-1).
This protection works automatically by opening contactor K6 (in series with the thyristors of the
static switch) and eventually K7, and acts in case of internal defects of the system, or due to wrong
manipulations on the maintenance bypass Q2.
Manual Bypass
The manual bypass consists of a pair of manual switches Q1 and Q2, which allow the isolation of
the UPS from the load, while still supplying the load with power directly from the mains.
Battery
The battery, normally stored by the battery-charger, supplies the DC energy to inverter in the
event of mains failure.

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 12/82 Operating Manual LP 33 / 10-20-30 kVA
3.2 OPERATION MODES
This section describes the different possible operation modes of the UPS explaining the function of
the main modules of the UPS.
On-line mode operation
Under normal conditions the load is
permanently powered by the inverter with
constant amplitude and frequency.
The rectifier, powered by the mains, supplies
the inverter and the battery-charger keeps
the battery fully charged.
Fig. 3.2-1 Energy flow in On-line mode operation
The inverter converts the DC voltage in a new AC sine wave voltage with constant amplitude and
frequency independently from the input mains power.
IEM mode operation (Intelligent Energy Management)
When the IEM mode is selected, and the
mains power is available, the load is normally
powered through the automatic bypass.
When the mains voltage is detected out of the
prescribed tolerances, the load is
automatically transferred to the inverter.
When the mains recovers, the load returns to
the automatic bypass after a variable time
defined by the control unit.
Fig. 3.2-2 Energy flow in IEM mode operation
The IEM mode can be configured directly by the user for higher efficiency, considering the mains
reliability and criticality of the load.
The selection between the two operation modes “On-line mode and IEM mode”, or switching
between operation modes at required time, can be done through the UPS console panel (see
Section 7.3.1-5).
In case of parallel system
IEM mode (Intelligent Energy Management) cannot be enabled for RPA Parallel System.

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 13/82 Operating Manual LP 33 / 10-20-30 kVA
Automatic bypass operation
In On-line operation mode, the load is
permanently supplied by the inverter but, in
case of trouble on the inverter, or when
overload or short-circuit on the output occur, if
the mains voltage do not exceed the admitted
tolerances, the load is instantly transferred to
the mains through the automatic bypass,
taking advantage of the higher short circuit
power.
Fig. 3.2-3 Energy flow in automatic bypass operation
When the inverter recovers, the load will be re-transferred automatically to the inverter.
In case of parallel system
Each unit has its own bypass.
All the bypasses in the system work together, their control being managed in the same manner
by all units.
The units are continuously exchanging information before taking such decision.
In case the inverter of one unit fails, its bypass remains operating.
It is excluded only if the unit is separated from the common bus by opening its output switch Q1.
Mains recovery operation
As soon as the mains recovers, the rectifier
starts up automatically supplying the inverter
and the battery-charger recharges the
battery.
In case the inverter has been shut down
following a complete discharge of the battery,
when the mains recovers the system start up
automatically.
Fig. 3.2-4 Energy flow at mains recovery operation
When the energy stored in the battery is sufficient to ensure a minimum time of operation with the
actual load, in case of a future mains failure, the load will be retransfered to inverter (if selected
On-line mode).
In case of parallel system
When the AC input power recovers, the rectifiers will start up sequentially according to their
number in the parallel system in order to avoid an initial inrush current.
The inverters will start up automatically, but only when the battery has recharged enough
for a minimum runtime with the present load.
When enough inverters to supply the load have been restarted, the load will be transferred
from the automatic bypass back to the inverter busbars.

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 14/82 Operating Manual LP 33 / 10-20-30 kVA
Manual bypass operation
The manual bypass circuit consisting of Q1
and Q2 manual switches, permits the transfer
of the load directly to the mains without
interruption, leaving the UPS galvanically
separated from the output load.
This type of operation is normally used when
the UPS system must be completely turned off
for maintenance or reparation. Fig. 3.2-5 Energy flow in manual bypass operation
Mains failure operation
In the event of a mains power failure, the
rectifier and the battery-charger turn OFF,
while the inverter continues to supply the
load without interruption using the energy
stored in the battery.
During the battery discharge, the LCD screen
displays the remaining autonomy, based on
the battery capacity and the applied load. Fig. 3.2-6 Energy flow during mains failure operation
In the event of an extended mains failure, before the battery is fully discharged, the alarm “stop
operation” warns the user that the UPS will start the shutdown procedures when the indicated
time expired (normally 3 minutes).
In case of parallel system
With parallel system for power capacity:
• With the bypass mains power available as the warning “battery low” occurs on one unit,
after timeout (selectable) the load is transferred to mains.
• With missing bypass mains power as the warning occurs on one unit, the system starts the
timeout (selectable) of “Stop operation” and then the output load shuts down.
With redundant parallel system:
• As the warning battery low occurs on one unit unnecessary to support the present load, after
timeout (selectable) this unit shuts down and the load is shared between the other units.
As the warning occurs on one unit necessary to support the present load, the system starts
the timeout (selectable) of “stop operation” and then the output load shuts down.

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 15/82 Operating Manual LP 33 / 10-20-30 kVA
3.3 RPA PARALLEL SYSTEM
The RPA (Redundant Parallel Architecture) allows to extend the unit to a parallel system with 2, 3,
or 4 units LP 33 connected on the same bus, which ensure the highest reliability rate and increase
the power availability.
Parallel system for power capacity
Two or more units can be paralleled in order to
achieve output power superior to the maximum
power delivered by a single UPS unit.
The maximum total load shared between the n
parallel units can achieve the 100% of the
installed nominal power system.
In the event of one unit fails, the load will be
suddenly transferred to the mains by the
bypass.
Parallel system for rendundancy
The parallel system can be defined redundant
only in case the nominal power rating of n-1
units of nparallel units is sufficient to supply the
required load power.
Mains Input
Load
Fig. 3.3-1 RPA system diagram
The load in a parallel redundant system, is equally shared by nunits connected on the output bars.
Should one of the parallel units trip off-line, the remaining (n-1) units will share the load maintaining
the applications protected by inverter until the normal situation restores.
Load sharing between parallel units
The control bus exchanging the data between the microprocessors of the paralleled units provide
for a constant proportional load sharing in every load condition.
Management and synchronisation of the parallel system
All the units are identical without master and slaves.
One unit is arbitrarily selected as the reference (the first unit connected on power bus) being this
unit the first synchronised with the mains voltage, and all the other units synchronise with the first
one.
In case the reference unit fails or it is excluded from the parallel power bus any other unit will take
over the reference role.
The AC input power source of all the bypasses must be the same for all the units of the parallel
system excluding any phase shift between them.
Control bus of the parallel system
A high-speed serial bus, guarantees communication, synchronization and load sharing between
the UPS modules.
Each module controls it’s own function, while the Master (each unit can be Master) controls and
commands the status of the system.
The parallel system exclude more rectifiers connected on common battery.
No transformers, fuses or automatic circuit breakers should be inserted
between the unit’s output and the load common busbars.

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 16/82 Operating Manual LP 33 / 10-20-30 kVA
3.4 SERVICE AND TECHNICAL SUPPORT
For any request of technical support please
contact the supplier who provided the system.
Stamp of your Dealer or local responsible of the Technical
Assistance (see page 3)
Fig. 3.4-1 Identification label
The requested data permitting to identify your
UPS are marked on the identification label
fixed on the front of the cabinet, behind the
lower front door.
For fast and efficient Technical Support
solutions, please mention the data marked on
the identification label.
3.5 WARRANTY
GE, operating through its authorised agents, warrants that the standard products will be free of
defects in materials and workmanship for a period of 24 months (12 months for battery), after the
date of the invoice, or such other period as may be specified.
NOTE !
This warranty does not cover failures of the product which result from
incorrect installation, misuse, alterations by persons other than authorised
agents, or abnormal working conditions.

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 17/82 Operating Manual LP 33 / 10-20-30 kVA
3.6 RECYCLING AT THE END OF SERVICE LIFE
NOTE !
This product has been designed to respect the environment, using materials
and components respecting eco-design rules.
It does not contain CFCs (Carbon Fluor Clorid) or HCFCs (Halogen Carbon
Fluor Clorid).
GE, in compliance with environment protection recommends to the
User that the UPS equipment, at the end of its service life, must be
recovered conforming to the local applicable regulations.
WARNING !
Leads contained in the batteries is a dangerous substance for the
environment, therefore it must be correctly recycled by specialised
companies!

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 18/82 Operating Manual LP 33 / 10-20-30 kVA
4 INSTALLATION
4.1 TRANSPORT
The UPS is fixed on transport socket suitable for forklift, which include a special layer of Ethafoam
to protect the equipment against the transport shock.
Normally the UPS is packaged with carton box.
On request the equipment can be packaged in wooden case.
Move the UPS in its original package to the final destination room.
Do not stack other package on top: they could damage the upper side of the cabinet.
NOTE !
When moving the UPS, pay attention to: FRAGILE SENSITIVE
TO DAMPNESS TO HEAT
SENSITIVE TO FROST
SENSITIVE
Forklift
The UPS may be lifted with a forklift in
upright position from right and left side.
Take note of the centre of gravity marked on
the package.
NOTE !
Check for sufficient floor and elevator
loading capacity.
Transport UPS only in upright position.
Do not stack other package on top of
the UPS.
Forklift
Crane
Fig. 4.4-1 LP 33 lifting
Crane
If the UPS has to be lifted by crane, use
suitable carrying belts taking note of the
centre of gravity marked on the package.
WARNING !
When loading / downloading and when
moving the UPS, it is forbidden:
When loading / downloading and when
moving the UPS, pay attention to:

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 19/82 Operating Manual LP 33 / 10-20-30 kVA
4.1.1 Dimensions and weight
Dimensions and weight LP 33
UPS
Dimensions
(W x D x H)
Weight
without
battery
Weight with
standard battery
10 kVA 500 x 780 x 1310 mm
19.7” x 30.7” 51.58”
135 Kg
298 lbs
269 (7Ah) / 367 (14Ah) Kg
594 (7Ah) / 810 (14Ah) lbs
20 kVA 500 x 780 x 1310 mm
19.7” x 30.7” 51.58”
147 Kg
325 lbs
379 (14Ah) Kg
836 (14Ah) lbs
Fig. 4.1.1-1 Dimensions LP 33
30 kVA 660 x 780 x 1310 mm
19.7” x 30.7” 51.58”
185 Kg
408 lbs
533 (21Ah) Kg
1’176 (21Ah) lbs
Dimensions and weight with carton package (standard)
UPS
Dimensions
(W x D x H)
Weight
without
battery
Weight with
standard battery
10 kVA 630 x 890 x 1580 mm
24.8” x 35.1” x 62.2”
165 Kg
364 lbs
299 (7Ah) / 397 (14Ah) Kg
660 (7Ah) / 876 (14Ah) lbs
20 kVA 630 x 890 x 1580 mm
24.8” x 35.1” x 62.2”
170 Kg
375 lbs
402 (14Ah) Kg
887 (14Ah) lbs
SGT4000_dimensions packing_01IT
CENTER
of
GRAVITY
CENTER
of
GRAVITY
H
T
B
Fig. 4.1.1-2 Dimensions with
carton package
30 kVA 790 x 890 x 1580 mm
31.1” x 35.1” x 62.2”
200 Kg
441 lbs
548 (21Ah) Kg
1’209 (21Ah) lbs
NOTE !
The weight of each single piece is marked outside the package!

g G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 20/82 Operating Manual LP 33 / 10-20-30 kVA
4.2 DELIVERY
When delivered, check carefully the package integrity and the physical conditions of the UPS
equipment.
In case of any damage sustained during transport, immediately inform the carrier and contact your
local Service Centre.
A detailed report of the damage is necessary for any insurance claim.
NOTE !
A damaged UPS must never be installed or connected to mains or battery!
4.3 STORAGE
The equipment is carefully packed for
transport and storage so that it is in a perfect
condition when eventually installed.
Never leave an UPS outside the building and
do not store the UPS one on top of the other.
It is recommended to store the UPS in its
original package in a dry, dust free room
and far away from chemical substances,
with temperature not exceeding -25°C to
55°C (-13°F to 131°F).
4.3.1 Storage of the UPS
Some important functions of the UPS, such as the customised functions, are defined by
parameters stored in a RAM memory.
The RAM is supplied by a small backup battery located on the Control Unit board.
If the storage time of the UPS exceeds 1 year, these functions should be verified by an
authorised Service Centre before putting the UPS into operation.
NOTE !
In case of storage of the UPS pay attention to: FRAGILE SENSITIVE
TO DAMPNESS TO HEAT
SENSITIVE
TO FROST
SENSITIVE
Other manuals for Digital Energy LP 33 Series
4
Table of contents
Other GE UPS manuals

GE
GE TLE 160 User manual

GE
GE FGC TLE Series User manual

GE
GE Match lite 500 User manual

GE
GE Digital Energy LP 33 Series User manual

GE
GE GT Series User manual

GE
GE TLE Scalable Series User manual

GE
GE 400 Series User manual

GE
GE 750 UL S2 User manual

GE
GE Digital Energy User manual

GE
GE TLE series 600 User manual

GE
GE Digital Energy LP 33 Series User manual

GE
GE Digital Energy LP 11U User manual

GE
GE Digital Energy LP 31 Series User manual

GE
GE 8 Series User manual

GE
GE LP33 Series 80 User manual

GE
GE Digital Energy SitePro 400 VAC CESeries 7 User manual

GE
GE 1000 VA User manual

GE
GE NetPro Series User manual

GE
GE lp33 20 series User manual

GE
GE 600 - 1500 VA User manual