
2
1.0 General safety precautions
IMPORTANT - Please study all the instructions
before installing and commissioning the lter.
Please keep manual for future reference.
Instruct all users in the function and operation of the
product.
Maintenance, replacement of lter cartridges should
only be done in accordance with section 4 in this
manual.
Power cables and pneumatic air hoses should be repla-
ced at once, if they are damaged. This should only be
done by trained electrician and ventilation tter.
Do not dismantle any factory-mounted parts, since it
impedes the commissioning of the equipment.
All electrical installations must be carried out by an
authorised electrician.
1.1 Danger
It is dangerous to dismantle the lter while in operation.
When installing or servicing of the lter make sure that
the power is disconnected.
1.2 Field of application
GeoFilter GFO-XT is used for ltration of oil saturated air
or fumes from polluting industrial processes such as ma-
chining, cutting and metal working involving cutting oil.
The GeoFilter GFO-XT comes with lter cartridges of
dierent pleated textiles with or without coating
(minimum ltration eciency of 99,90% according to
BIA-test - see section 1.3.)
1.3 Technical data
Model No. of
cartridges Filter area [m²] Max. Air ow
GFO-XT-3 3 14,7 m² 1.800 m³/h
GFO-XT-6 6 29,4 m² 3.600 m³/h
GFO-XT-9 9 44,1 m² 5.400 m³/h
GFO-XT-12 12 58,8 m² 7.200 m³/h
Model Dimensions
(HxBxD) mm.
Inlet Outlet
GFO-XT-3 2032x325x927 Ø250mm Ø250mm
GFO-XT-6 2032x625x927 Ø315mm Ø315mm
GFO-XT-9 2032x925x927 Ø400mm 2xØ315mm
GFO-XT-12 2032x1225x927 Ø500mm 3xØ315mm
Temperature surroundings -10°C - +65°C
Relative humidity must be below <90%
The pressure drop in the lter will vary depending on
the load and how dirty the lter cartridges are. The lter
cartridges must be replaced, when the pressure drop
exceeds 1.200 Pa.
Table of content
1.0 General safety precautions.................. 2
1.1 Danger ................................. 2
1.2 Field of application . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3 Technical data............................ 2
1.4 Construction ............................. 2
2.0 Installation. .............................. 3
2.2 Test Run - adjusting ....................... 3
3.0 User instruction........................... 3
4.0 Maintenance............................. 3
4.1 Replacing lter cartridges................... 3
4.2 Trouble shooting ......................... 4
6.0 Declaration of conformity ................... 4
1.4 Construction
Cabinet: Sturdy frame/cabinet, made of galvanised
steel plate (corrosion class lll), with lter cone and
deector in the inlet.
150
400
Airflow [m³/h]
Pressure drop [Pa]
800 1200
300
450
600
750
900
1050
1200
1350
1500
1650
GFO filter
200 600 1000 1400 1600 1800 2000 2200
Lower curve = clean filter
Upper curve = dirty filter