GfS Day Alarm
Assembly instructions

GfS-Day Alarm Art.-Nr.: 700 000/710 000/730 000/740 000/741000
2MA_GfS-Tagalarm_0515_GB
GENERAL DESCRIPTION
INSTALLATION INSTRUCTIONS
The GfS Day Alarm is a cost-eective and simple solution to secure emer-
gency exits. The opening status of the emergency exit door is monitored by
a radio or cable reed contact.
When walking through the door an accoustic alarm (95dB) and flash-light
is triggered. Authorized persons may deactivate the GfS Day Alarm by the
integrated key switch.
If somebody forgets to close the door after an authorised walk-through, an
acoustic intervalic alarm is triggered 15 sec. after the emergency exit door
has been opened.The green LED flashes.
As soon as the door is closed, the red LED illuminates again, the interval
tone expires and the device is activated again.
By using the key switch, it is possible to deactivate the GfS Day Alarm for
a long period.
The actual status of the GfS Day Alarm is indicated by a green and red LED.
The battery-operated GfS Day Alarm LC, however, does not integrate a
flash light. The GfS Day Alarm LC which integrates battery monitoring just
operates in combination with cable reed contacts.
All versions incorporate an automatic alarm switch-o, a floating-contact
for alarm transmissions and an interface to connect external access control
systems.
Open GfS Day Alarm unit. Remove red plastic cap and pull out the panel
with the LEDs and profile cylinder. Mount the GfS Day Alarm unit with the
screws.
The two upper screws have to be screwed in first and the unit be hung in.
To secure the unit the two lower screws have to be screwed in. Install the
reed contact at the door (installation depends on the version that was or-
dered).
Start-up after first installation
Before connecting the power supply please make sure that the door and
thus the reed-contact is closed.
Delivery state
When installed for the first time the GfS Day Alarm is deactivated.
Battery operated versions
Please insert the battery first.
Radio reed contact
GfS-Day Alarm
Key Switch outdoor
Reed contact
GfS Day Alarm
Display panel
Key switch
Junction box

Art.-Nr.: 700 000/710 000/730 000/740 000/741000 GfS-Day Alarm
3
MA_GfS-Tagalarm_0515_GB
Disposal
Dispose an obselet GfS Exit Control at a a colleting point for electronic
waste or at your supplier.Dispose the packaging material at a paper collect-
ing point for paper resp.plastic.You may not dispose an obsolte device the
general garbage.
Warranty
Within the legal warrenty time we intend to repair all defect devices,
whether the defect is caused by the material or assembly, or replace them.
The warenty expires after a third-party repair.
Conformity
This product complies with the essential requirements of the R&TTE guide-
line 1999/5/EG.The certificate of conformity you may request from your
supplier.
Service
In case of a system failure or a defect GfS Door Terminal please contact the
following address:
Activation
Insert key and turn clock-wise as far as it will go. The green LED lights up.
Now turn the key anticlockwise and remove it. Open the door briefly and
close it again. The red LED shines, the unit is armed.
Unauthorized use
If the door is opened, the reed contact will send a signal which is received
by the GfS Day Alarm. The red LED flashes and a visual and an accoustic
alarm is triggered. The GfS Day Alarm LC has no flash-light.
Reset GfS Day Alarm
Insert the key into the integrated cylinder and turn it clockwise as far as it
will go. Turn key anticlockwise and remove it. The alarm expires and the
LED shines green. Close the door or if it is closed already wait for 15 sec-
onds. The LED shines red and the GfS Day Alarm unit is activated again.
Authorized passage
Insert the key and turn it to the right.
The green LED lights up. Turn the key to the middle position and remove it.
Open the door and walk through. Close the door again. The red LED shines
and the the GfS Day Alarm is activated again. In case that nobody walks
through the door the green LED shines for approx. 15 sec and changes then
to red. The GfS Day Alarm is activated again.
The LED of the battery operated versions of the GfS Day Alarm (GfS Art.No.
710.000 and 741.000) expires after 10 sec. and the GfS Day Alarm is acti-
vated again.
The door is open
If the door is not closed properly after authorized use, an accoustic signal
is audible after 15 seconds of opening time and the green LED flashes. As
soon as the door is closed, the red LED shines, the accoustic alarm stops
and the units alarm function is activated.
Permanent opening
Insert the key and turn clockwise as far as it will go. The green LED is
switched on. Leave in this postion until the LED switches o. After that turn
key anticlock and remove. Now the door can be freely used without trigger-
ing the alarm. The green LED flashes, which signals “door permanently
open”. To switch the alarm on, turn key clockwise as far as it will go. The
green LED shines. Now turn key anticlockwise and remove. Close the door
or if the door is closed already, wait 15 seconds. Now the LED shines red
and the system is armed.
Start-up after power failure
After the power failure, the GfS Day Alarm unit switches on and an alarm
sound is emitted. This is to draw the attention of the provider of the system
to the fact that the supervision of the door was interupted and the door
might still be open!
To switch o the alarm, turn key clockwise as far as it will go. The LED is
green and the alarm switches o. Now turn key anticlockwise and remove.
Open the door once and close it again. The LED switches to red and the unit
is armed.If the door was in the “permanently open position” before the
power failure, it will remain in this mode.
FUNCTIONS

GfS-Day Alarm Art.-Nr.: 700 000/710 000/730 000/740 000/741000
4MA_GfS-Tagalarm_0515_GB
GfS Day Alarm GfS Art No. 700 000/730 000 with radio reed contact – terminal diagram
3
2
1
5
9
8
4
7
6
Floating contact
GND
External key switch
COM
Bridge for radio reed contact
+ 12 V
External access
control system
floating contact
External key switch
NC
NO
Jumper Pos. 1–3
TECHNICAL DATA Art.-Nr.: 700 000/730 000
• Connectionofexternalalarmdevicesbyfloatingcontactpossible
•Resettingonlywithinternalkeyswitch
•Permanentopening
•Door-too-long-open-alarm
•Externalkeyswitchforauthorizeduseonly(includingprotection
against tampering)
The relais is permanently pulled (power supply control). When an alarm is
triggered, the relais drops out, that means in case of an alarm COM and
NC are closed, in all other cases COM and NO are closed.
Jumper set
Pos. 1-2: After 3 minutes the sirène is switched-off automatically.
The flash-light remains active till the GfS Day Alarm is reset.
Pos. 2-3: The siren and falsh light is permanently activated in case of
an alarm.
Power plug GfS Art. No. 700.000 (scope of delivery)
IN/PRI 230 V ~ 50 Hz 17 W
OUT/SEC 12 V DC 600 mA 7,2 VA
Intergrated power supply unit for mains supply
730.000 and 740.000 (scope of delivery)
IN/PRI 230 V ~ 50 Hz 17 W
OUT/SEC 12 V DC 600 mA 7,2 VA
Radio reed contact 868,3 MHz
Power supply
Receiver 12 V
Transmitter (battery integrated into radio reed contact) 3 V CR2032
Transmission range
avange in a building approx. 30 m
1
2
3
9
8
4
7
3
6
2
5
1
Jumper for radio reed contact
External access
control system
floating contact
Floating contact
GND
external key switch
COM
+ 12 V DC
external key switch
NC
NO

Art.-Nr.: 700 000/710 000/730 000/740 000/741000 GfS-Day Alarm
5
MA_GfS-Tagalarm_0515_GB
GfS Day Alarm GfS Art. No 700 000/730 000 with cable reed contact – terminal diagram
TECHNICAL DATA Art.-Nr.: 700 000/730 000
• Connectionofexternalalarmdevicesbyfloatingcontactpossible
• Resettingonlywithinternalkeyswitch
• Permanentopening
• Door-too-long-open-alarm
• Externalkeyswitchforauthorizeduseonly(includingprotection
against tampering)
The relais is permanently pulled (power supply control). When an alarm is
triggered, the relais drops out, that means in case of an alarm COM and
NC are closed, in all other cases COM and NO are closed.
Jumper 1 set
Pos. 1-2: After 3 minutes the sirène is switched-off automatically.
The flash-light remains active till the GfS Day Alarm is reset.
Pos. 2-3: The siren and falsh light is permanently activated in case
of an alarm.
Jumper 2
Pos. 1-2 For cable reed contact
Power plug GfS Art. No. 700.000 (scope of delivery)
IN/PRI 230 V ~ 50 Hz 17 W
OUT/SEC 12 V DC 600 mA 7,2 VA
Intergrated power supply unit for mains supply
730.000 and 740.000 (scope of delivery)
IN/PRI 230 V ~ 50 Hz 17 W
OUT/SEC 12 V DC 600 mA 7,2 VA
Cable reed contact
with 2m cable
Max. distance between reed contact and magnetic counter part
between 5 to max. 10 mm.
Radio transmitter might be retrofit
1 2 3 4 5 6
3
2
1
5
9
8
4
7
6
floating contact
GND
external key switch
COM
reed contact
reed contact
+ 12 V DC
External access
control system
floating contact
external key switch
NC
NO
1
2
3
Jumper 1 Pos. 1–3Jumper 2 Pos. 1–2
9
8
4
7
3
6
2
5
1
reed contact
floating contact
GND
external key switch
COM
reed contact
+ 12 V DC
external key switch
NC
NO
External access control system
floating contact

GfS-Day Alarm Art.-Nr.: 700 000/710 000/730 000/740 000/741000
6MA_GfS-Tagalarm_0515_GB
GfS Day Alarm INOX GfS Art. No 740 000 with radio reed contact – Terminal diagram
TECHNICAL DATA Art.-Nr.: 740 000
Mains supply
Door alarm secured, reed contact is closed.
Receiver is closed.
In case that cable reed contacts are connected ( also in case of battery
operation) jumper 1 must be set on position 1+2
Red LED shines
Relais is pulled (COM and NO connected)
Authorized use
Turn key in internal key switch or use the external key switch (clamp 6)
briefly (< 5 sec.)
Green LED shines permanently.
The alarm remains deactivated till the door is closed again.The LED
shines red again.
If the door has not been opened for 15 sec the alarm is automatically
activated again. The LED shines red. If the door has not been closed after
15 sec. a door-too-long-open-alarm is triggered.
Door-too-long-open-alarm
Relais switches o (COM and NC connected)
Green LED flashes slowly (every 1,5 sec). Buzzer gives alarm every 3 sec.
for about 200ms (short beep).
When the door is closed again, the GfS Alarm is activated again. The LED
shines red again. The hold-open time might be extended by turning again
clockwise to max. end stop.
Alarm
The reed contact has been opened while the GfS Day Alarm is armed.
Buzzer resounds (DIP 4 is OFF)
Flash light is activated
Red LED flashes quickly (0,3 sec. on/0,3 sec. o)
Relay switches o (COM and NC are connected)
Buzzer expires after 3 min. while DIP 5 is ON. Otherwise the buzzer
resounds permanently.
To quit: Only by operating the key switch (internal or external). Not
possible with external opening contact.
Permanent opening
Insert the key and turn clockwise as far as it will go. The green LED is
switched on. Leave in this postion until the LED switches o (about 5
sec.). After that turn key anticlock and remove. Now the door can be
freely used without triggering the alarm. The green LED flashes, which
signals that the GfS Day Alarm is permanently deactivated. To activate
the GfS Day Alarm again, briefly turn key clockwise as far as it will go.
The green LED shines. Now turn key anticlockwise and remove it. Close
the door or if the door is closed already, wait 15 seconds. Now the LED
shines red and the system is armed again.
External switch
In case that the GfS Day Alarm receives a permanent external release
signal, the GfS Alarm is activated again after 20 sec. There is no
permanent external release feature available.
1
2
3
4
5
6
7
8
9
10
external key switch
Jumper for radio reed contact
External access control system
floating contact
external key switch
NO
NC
COM
12 V
GND
Key switch parallel to internal key switch
3
4
5
6
7
8
2
1

Art.-Nr.: 700 000/710 000/730 000/740 000/741000 GfS-Day Alarm
7
MA_GfS-Tagalarm_0515_GB
GfS Day Alarm INOX GfS Art. No 740 000 with cable reed contact – Terminal diagram
TECHNICAL DATA Art.-Nr.: 740 000
1
2
3
4
5
6
7
8
9
10
3
4
5
6
2
1
3
4
5
6
7
8
2
1
Jumper 1 Pos. 1–2
external key switch
reed contact
External access control system
floating contact
external key switch
NO
NC
COM
24 V
GND
Key switch parallel to internal key switch
Clamp Functions
1–3 Floating relay, 30 V/0,5 A max
48 – 12 V/DC (max 13 V)
5GND
6 + 7 Parallel to internal key switch
To be connected with GND
7 + 8 External key switch
9 + 10 Reed contact
GfS Day Alarm with receiver requires jumper
Functions DIP switch
Standard hold open time 15 sec. (DIP 1-3 OFF)
DIP 1 ON Hold open time + 5 sec.
DIP 2 ON Hold open time + 10 sec.
DIP 3 ON Hold open time + 20 sec.
Like this hold open times may be realized in 5 sec. steps from
15 to 50 sec.
DIP 4 ON Silent Alarm
DIP 5 ON Automatic alarm switch-o after 3 min.
DIP 6-8 Reserve

GfS-Day Alarm Art.-Nr.: 700 000/710 000/730 000/740 000/741000
8MA_GfS-Tagalarm_0515_GB
GfS Day Alarm INOX GfS Art. No 741 000 with cable reed contact – battery operated
TECHNICAL DATA Art.-Nr.: 741 000
1
2
3
4
5
6
7
8
9
10
external key switch
reed contact
External access control system
floating contact
external key switch
NO
NC
COM
24 V
GND
Key switch parallel to internal key switch
Battery operation
Basic functions of the GfS Day Alarm with battery operation are similar to
those of mains operation.
Dierences
Relay operates in the opposite way (it is permanently deactivated, in case
of an alarm it will be activated). While the GfS Day Alarm is activated the
red LED is switched on for approx. 15 sec. Then the LED expires and the
GfS Day Alarm operates in a stand by mode (while waiting for external
signals). During the permanent opening mode the green LED flashes every
60 sec.
Batterie Control
only active when battery operated. Voltage is being measured after the red
LED is switched-o and then every 12 hours. The green LED is triggered
briefly (100ms) in order to put some load on the battery. In case that the
battery supply is less than 7,5V the buzzer sounds briefly. Now the meas-
urement takes place every 60 sec. and triggers a brief alarm.
Operation in parallel
With mains supply it is also possible to use a battery in parallel (only with-
out integrated receiver). In case of power failure the GfS Day Alarm starts
to be battery operated after 15 sec. When the power failure is over the GfS
DayAlarm operates automatically again with mains supply.

Art.-Nr.: 700 000/710 000/730 000/740 000/741000 GfS-Day Alarm
9
MA_GfS-Tagalarm_0515_GB
GfS Day Alarm LC
•Connectionofexternaldeviceswithoatingcontactpossible
•Conrmationonlyviainternalkeyswitch
•Permanentopenfunction(1xashinggreenLEDtheno)
•Door-too-long-openfunction
•Externalkeyswitch:onlyforauthorisedwalk-throughprotectedagainst
tampering
•Batteryoperation–whilebatteryoperatedtherelayisnotpulled
permanently. In the event of an alarm, it opens, i.e. in the event of
alarm the COM and NO are closed, in the open and/or active mode,
COM and NC are closed.
•Batterycontrol
•Alarmswitchesoafter3minutes(jumperwithoutfunction)
•Noremotereedcontactavailable
Cable reed contact
with 2m cable
Max. distance between reed contact and magnetic counter part
between 5 to max. 10mm.
Power supply
9 V block battery (in the scope of delivery):
Power consumption in standby: 10–15 μA
Current consumption during alarm: 60–80 mA
or 12V External power supply (optional)
GfS Day Alarm GfS Art. No 710 000 with cable reed contact – battery operated
TECHNICAL DATA Art.-Nr.: 710 000
3
2
1
5
9
8
4
7
6
Floating contact
GND
external key switch
COM
reed contact
reed contact
+ 12 V DC
external key switch
NC
NO
Jumper without function (when battery operated
alarm switches o automatically after 3min)
External access
control system
floating contact
9
8
4
7
3
6
2
5
1
reed contact
floating contact
GND
eternal key switch
COM
reed contact
+ 12 V DC
eternal key switch
NC
NO
Impuls freischalten
(potentialfrei)

GfS-Day Alarm Art.-Nr.: 700 000/710 000/730 000/740 000/741000
10 MA_GfS-Tagalarm_0515_GB
SETTINGS FOR REMOTE REED CONTACT
PLACE BATTERY IN REMOTEREED CONTACT
Programming of additional radio reed contacts
Press the program button (Prog) once briefly (1 sec max.).
You will notice a blinking light signal (f =1 Hz). Handle the transmitters one
after the other that shall work with the receiver.
A well received “address” will be confirmed by a long light signal (approx.
4 sec). Each receiver can program a maximum of 32 transmitters.
You end the programming by pushing the program button 3 short times in
sequence (max. 1 sec each time). The light signal turns o and the receiver
is operational. The programming is retained after a long power failure.
Deleting of selected transmitters
It is possible to delete selected transmitters without having to reset the
receiver totally. Push the program button for a minimum of 3 seconds. The
light signal blinks. Operate the transmitter that shall be deleted. This is
confirmed by a long light signal. Push the program button once shortly.
Reset is completed.
Reset
While resetting all programmed transmitters are deleted and the receiver
can be programmed with 32 new transmitters. For a reset push the pro-
gram button for a long time (minimum of 3 sec). The light signal blinks.
Now press the program button once more (minimum of 3 sec).
The memory is erased. This is confirmed by a long light signal. Push the
program button once briefly. The reset is finished.
Programming button
LED
1. Open the device: Press the small tab
on the side and draw-o the cover
towards the top.
2. Insert the included battery CR 2032 (3 V lithium)
inside the battery clip.
3. Mount the counterpart with the raw magnet parallel to the reed
contact. The distance should not be more than 10 mm!
max 10 mm

Art.-Nr.: 700 000/710 000/730 000/740 000/741000 GfS-Day Alarm
11
MA_GfS-Tagalarm_0515_GB
The installer has informed the operator of the following:
Functionality and use
Resetting the alarm
Battery change (optional)
Special functions
The option of transmitting the alarm
Hand out operating manual to the operator
Version
GfS Day Alarm with external power supply (GfS Art.-No. 700 000)
GfS Day Alarm battery operated (GfS Art.-No. 710 000)
GfS Day Alarm with integrated power supply (GfS Art.-No. 730 000)
GfS Day Alarm INOX with integrated power supply
(GfS Art.-No. 740 100)
GfS Day Alarm INOX battery operated (GfS - Art.-No. 741 000)
Others
Cable reed contact Remote reed contact
Technical approval (installer) for the mutual safeguarding for the local dealer/assembler and end customer
City, date
Signature
Company

GfS-Day Alarm Art.-Nr.: 700 000/710 000/730 000/740 000/741000
12 MA_GfS-Tagalarm_0515_GB
Technical approval (operator) for the mutual safeguarding for the local dealer/assembler and end customer
The installation has been done properly
The function of the GfS Day Alarm have been checked, the GfS Day Alarm operates correctly
Pecularities of the building site
All GfS Day Alarms are accessible
The GfS Day Alarm has been tested and approved
Version
GfS Day Alarm with external power supply (GfS Art.-No. 700 000)
GfS Day Alarm battery operated (GfS Art.-No. 710 000)
GfS Day Alarm with integrated power supply (GfS Art.-No. 730 000)
GfS Day Alarm INOX with integrated power supply
(GfS Art.-No. 740 100)
GfS Day Alarm INOX battery operated (GfS - Art.-No. 741 000)
Others
Cable reed contact Remote reed contact
City, date
Signature
Company

Art.-Nr.: 700 000/710 000/730 000/740 000/741000 GfS-Day Alarm
13
MA_GfS-Tagalarm_0515_GB
NOTES

GfS-Day Alarm Art.-Nr.: 700 000/710 000/730 000/740 000/741000
14 MA_GfS-Tagalarm_0515_GB
OPERATION
Authorized use
Description Key LED
Insert key and turn to the right as far as it will go.
The green LED shines.
green LED
shines
Then turn back the key into the middle position and remove it.
Open the door and walk through.
Close the door, the red LED shines and the GfS Day Alarm is activated again. red LED
shines
turn
as far as
it will go
turn
Reset of alarm
Description Key LED
Insert the key and turn clockwise as far as it will go.
Green LED shines
green LED
shines
Then turn back the key into the middle position and remove it.
Close the door or – in case that the door is already closed – wait for approx. 15 sec.
The LED shines red, the GfS Day Alarm is activated. red LED
shines
turn
as far as
it will go
turn
Reset permanent deactivation
Description Key LED
Insert key and turn to the right as far as it will go.
The green LED shines. green LED
shines
turn
as far as
it will go
Permanent deactivation
Description Key LED
Insert key and turn to the right as far as it will go.
The green LED shines. green LED
shines
Stay in this position, till the LED expires. untill
green LED
expires
Now the door can be used without triggering an alarm.
The green LED blinks, the GfS Day Alarm is permanently deactivated. green LED
flashes
turn
as far as
it will go
hold

Art.-Nr.: 700 000/710 000/730 000/740 000/741000 GfS-Day Alarm
15
MA_GfS-Tagalarm_0515_GB
PROGRAMMING
Programming additional remote reed contacts
Description Programming button LED
Press programming buttom briefly once (max. 1 sec.). A light signal is emited (f=1 Hz).
Operate the reed-contacts one after another which are supposed to work together with the
GfS Day Alarm. A well received signal is confirmed by a light signal which is emitted for
about 4 sec. Up to 32 senders might be taught-in.
Finish programming
Press the programming buttom 3x briefly each time for max. 1 sec.
The light signal expires and the receiver is in operation.
1x press
(max. 1 sec.)
3x press
(each time
max. 1 sec.)
flashes
shines for
approx. 4 sec.
expires
Deleting single senders
Description Programming button LED
Press programming buttom for at least 3 sec.
Operate the radio reed contact which is supposed to be deleted.
LED shines for a long period of time
Press briefly just once on the programming buttom and finish the delete process.
press for
at least
3 sec.
1x press
max. 1 sec.
flashes quickly
shines for a
long period
of time
expires
Reset (delete all taught in senders)
Description Programming button LED
Press programming buttom for at least 3 sec.
Press programming buttom for at least 3 sec.
Press briefly just once the programming buttom in order to finish the reset process.
press for
at least
3 sec.
press for
at least
3 sec.
1x press
max. 1 sec.
flashes quickly
shines for a
long period
of time
expires

GfS – Gesellschaft für Sicherheitstechnik mbH
Tempowerkring 15 ∙ D-21079 Hamburg Tel. 0 40 - 79 01 95 0 ∙ Fax 0 40 - 79 01 95 11 ∙ info@gfs-online.com ∙ www.gfs-online.com
Table of contents
Other GFS Security System manuals