DEC 2016 GFS-530a (Formerly A-60)
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES DRY TYPE
UPRIGHT
DESCRIPTION AND OPERATION
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
• Water Working Pressure Rating - 175 psi (12 Bars)
• Factory tested hydrostatically to 500 psi (34 Bars)
• Maximum low temperature glass bulb rating is -67°F (-55°C)
• Frame - bronze •Deflector - brass •Screw - brass
•Bulb Seat - brass •Spring - nickel alloy •Seal - teflon
•Retainer - brass •Pin - stainless steel
•Torsion Spring - stainless steel •Orifice Insert - brass
• Bulb - glass with alcohol based solution, 3mm size
• 3/4”NPT or 1”NPT •Outer Tube - galvanized steel pipe •Inner Tube - stainless steel
TECHNICAL DATA
• See reverse side for Approvals and Specifications.
• Temperature Ratings -
135°F (57°C), 155°F (68°C), 175°F (79°C)
200°F (93°C), 286°F (141°C)
UPRIGHT
CLASSIFICATION AVAILABLE SPRINKLER
TEMPERATURES BULB COLOR N.F.P.A. MAXIMUM CEILING
TEMPERATURE
ORDINARY
INTERMEDIATE
HIGH
135°F/155°F
175°F/200°F
286°F
57°C/68°C
79°C/93°C
141°C
ORANGE/RED
YELLOW/GREEN
BLUE
100°F
150°F
225°F
38°C
66°C
107°C
The Globe Quick Response GLSeries Dry Type Upright Sprinkler is
designedforuseinspecialapplicationssuchasfreezingenvironments.
As an example, they may be efficiently used when connected to a wet
type sprinkler system and extended into an unheated attic space.
The Globe Quick Response GL Series Dry Type Upright Sprinkler
utilizes a 3mm frangible glass ampule as the thermosensitive element.
This provides sprinkler operation approximately six times faster than
ordinary sprinklers. At the ampule's rated temperature, the sprinkler
opens releasing the bulb seat, causing the inner tube assembly to
move, allowing the spring assembly to pivot alongside the inner tube.
At this time, water flows through the sprinkler and is distributed by the
deflector,inanapproveddischargepattern.Itcanbeinstalledwherever
standard spray sprinklers are specified but offers the additional feature
of greatly increased safety to life. Quick Response Sprinklers should
be used advisedly and under the direction of approving authorities
having jurisdiction.
The heart of Globe's GLSeries sprinkler proven actuating assembly
isahermeticallysealedfrangibleglassampulethatcontainsaprecisely
measuredamount offluid. When heat isabsorbed, theliquid withinthe
bulb expands increasing the internal pressure. At the prescribed tem-
perature the internal pressure within the ampule exceeds the strength
oftheglasscausingtheglasstoshatter. Thisresultsinwaterdischarge
which is distributed in an approved pattern.