JAN 2017 GFS-300 (Formerly A-3)
CLASSIFICATION AVAILABLE SPRINKLER
TEMPERATURES BULB COLOUR AS2118 MAXIMUM CEILING
TEMPERATURE
ORDINARY 155°F 68°C RED 100°F 38°C
INTERMEDIATE 175°F/ 200°F 79°C/ 93°C YELLOW/GREEN 150°F 66°C
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
• See reverse side for Approvals and Specifications.
• Temperature Rating - 155°F (68°C), 175°F (79°C), 200°F (93°C)
• Water Working Pressure Rating - 175 psi (12 Bars)
• Factory tested hydrostatically to 500 psi (34 Bars)
• Maximum low temperature glass bulb rating is -67°F (-55°C)
• Frame - bronze • Deflector - brass • Screw - brass
• Lodgement Wire - stainless steel • Bulb seat - copper
• Spring - nickel alloy • Seal - teflon
• Bulb - glass with alcohol based solution, 3mm size
• Escutcheon Assembly - steel
TECHNICAL DATA
RESIDENTIAL
AUTOMATIC SPRINKLERS
MODEL GL3010
PENDENT
RECESSED PENDENT
DESCRIPTION AND OPERATION
RESIDENTIAL
PENDENT
RESIDENTIAL
RECESSED PENDENT
The Globe Model GL3010 Residential Sprinkler has a low profile
yet durable design, which utilizes a 3mm frangible glass ampule
as the thermosensitive element. It features economy, aesthetics
and low flow.
The combination of the 3mm frangible glass ampule and spe-
cially designed deflector makes the Model GL3010 Residential
Sprinkler the ultimate in life safety and fire control. This Globe
Pendent and Recessed Pendent Residential Sprinkler has met the
strict requirements of Underwriters Laboratories Inc. as described
in the UL Standard for Residential Sprinklers for Fire Protection
Service, UL 1626, and should be used accordingly. This sprinkler
should also be installed in accordance with the appropriate NFPA
Standard 13, 13D or 13R and under the direction of the approving
authorities having jurisdiction.
TheheartofGlobe'sModelGL3010sprinklerprovenactuating as-
semblyisahermeticallysealedfrangibleglassampulethatcontains
a precisely measured amount of fluid. When heat is absorbed, the
liquid within the bulb expands increasing the internal pressure. At
theprescribedtemperature,theinternal pressurewithintheampule
exceeds the strength of the glass causing the glass to shatter. This
resultsinwaterdischargewhichisdistributedinanapprovedpattern.
The sprinkler and escutcheon are not factory assembled.
Assembly is done in the field.