manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. hager
  6. •
  7. Power Supply
  8. •
  9. hager VC Service manual

hager VC Service manual

VC & VH Consumer Unit
Instructions/Data Sheet
This Consumer Unit and Hager devices conform with the following standards:
Consumer Unit: BS EN 61439-3 including Annex ZB.
Switch-disconnectors: BS EN 60947-3.
Residual Current Circuit Breaker (RCCB): BS EN 61008-1
Residual current operated circuit breaker with integral overload (RCBO): BS EN 61009-1
Miniature Circuit Breaker (MCB): BS EN 60898-1
Installation Instructions:
All product(s) must be installed by a suitably competent electrician
Giving consideration to their intended use and in accordance with the
current edition of BS 7671 (IET Wiring Regulations).
The Electricity at Work regulations and the Health and Safety at Work Act
shall be complied with.
Only equipment and arrangements specied in Hager’s technical
documentation / catalogue shall be used.
Install in the horizontal plane only.
Important notice:
To prevent potential overheating from loose connections the installer
shall check connections are tight to the torque levels stated in these
instructions prior to energizing this board. This check should include
factory made connections which may have loosened in transit.
Tightening torque values to be applied (Nm)
Switch-disconnector’s: 40A & 63A: 2.8 Nm
Switch-disconnector’s: 100A: 3.3 Nm
RCCB’s 40A & 63A: 2.8 Nm
RCCB’s 80A & 100A: 3.3 Nm
MCBs: 2.8 Nm
RCBO’s: 2.8 Nm
Earth & Neutral terminal bar connections: 2.0 Nm
Single conductors below 1.5mm² need to be doubled back in the
terminal bar
Front metal cover xing screws: 2.0 Nm
Good workmanship and proper materials must be applied by the installer.
Metalclad units are provided with knockouts for standard 20, 25, and
32mm conduit and large rear knockouts.
Insulated units are provided with breakouts for standard mini trunking.
Rear cable entries should be scored along the weak point with a sharp
knife, and tapped sharply to remove.
Pull and lift the terminal bar support away from the unit resting the rail
supported by the earth strap. After xing conduit/ cable glands, locate
the rail support and press down.
Note: Only BASEC approved cable should be used
1.0mm2to 16mm2for outgoing cables
up to 35.0mm2for incoming live cables
Single conductors below 1.5mm² need to be doubled back in the terminal bar.
Cable entry facilities:
Metal Unit - Removing and replacing the terminal rail for cabling:
GB
1ZD0632 - Issue 5 03-15
ZD0632ZD0632
Guidance Notes:
The total load must not exceed the rating of the incoming device or the assigned assembly rating (InA) whichever is the lower. Each neutral and earth
connection must correspond numerically to its outgoing way. Additional blanks (ref. JK01B) are available to cover spare ways.
A pack is provided to label this consumer unit, please consult us for spares or replacements.
Operating Instruction leaet is provided overleaf. This leaet should be left for the end user.
Single conductors below 1.5mm² need to be doubled back in the terminal bar.
Consumer Units incorporating RCDs in TT systems should incorporate an S type (time Delayed) RCCB, e.g. 100 mA s-type RCCB . Alternatively a main
switch with RCBO protection on all outgoing circuits should be used.
Precautions need to be taken to prevent faults to earth on the supply side of the RCD (as per BS7671 regulation 531.4.1)
IP Ratings:
Cable access into the consumer unit must maintain the integrity so far as reasonably practicable. In essence, for surfaces accessible after installation,
this means maintaining the requirement for the horizontal top surface of the enclosure to provide a degree of protection of at least IP4X and elsewhere,
IP 2XC. For rear cable access, the minimum number of knockout(s) shall be removed.
Warranty
This distribution board is offered with a 24 month warranty against defective material or manufacture. If a warranty claim is necessary, please call the
technical support number given at the bottom of the page and we will be pleased to help.
For dimensional information and weights please consult the Hager catalogue.
Hager Technical Help Line: 01952 675 689
Hager Technical Fax: 01952 675 557
Website: www.hager.co.uk
E-mail us: info@hager.co.uk
Fitting Hager MCBs and RCBOs:
Only equipment and arrangements specied in Hager’s technical
documentation / catalogue shall be used.
Isolate the electrical supply from the consumer unit.
1. Isolate the electrical supply from the consumer unit.
2. Remove the front cover.
3. Fully slacken the lower terminal of the device.
4. Fully open the bottom device clip (g 1.)
5. Locate the device onto the din rail, and busbar. Ensure that the
busbar tooth is within the device terminal cage.
6. Close the bottom device clip.
7. While holding the device rmly onto the busbar, fully tighten the lower
terminal screw.
8. After tting all outgoing devices and connecting all outgoing cables,
please check the tightness of all cable connections. This should
include all factory made connections, which may have loosened
during installation or transit.
g 1.
IP Code Description
IP2XC Protection against access
with a tool (2.5mm diameter,
100mm long) making contact
with live hazardous parts
IP4X A probe of 1mm diameter
shall not enter the enclosure
Insulated Unit - Removing and replacing the top wall for top surface cabling
(IP4X using foam inserts; 1mm2- 10mm2 conductors BS6004)
1. Press in with index nger on one end release clip while pressing in with thumb
on the inner release clip repeat on the other and lifting the wall away from the
unit.
2. After xing the unit, to replace and reseal, place one of the foam seal strips in
the underside of the wall feature and the other in the base (behind the cables).
Locate the wall and press down. Additional xing points are provided.
Max outgoing top entry cable size 10mm2CSA.
Max incoming Main tails top entry cable size 25mm2CSA.
If larger cables are needed, then enter from any other cable entry point other than
top.
2ZD0632 - Issue 5 03-15
ZD0632 ZD0632
IP2XC
IP2XC
IP4X
3ZD0632 - Issue 5 03-15
Interface characteristics
Rated & operational voltage (Un / Ue)
230V a.c. 50Hz
Rated insulation voltage (Ui)
320V a.c. 50Hz
Rated impulse withstand voltage (Uimp)
4kV
Rated current of the Assembly (InA)
100A, 63A, 40A
Note: Dependent upon rating of main incoming device
Rated current of an Outgoing circuit (Inc)
MCB 6A - 63A (marked rated current on device)
RCBO 6A - 50A (marked rated current on device)
Rated current of outgoing unit (Inc)
RCCB 40A -100A (marked rated current on device)
Rated conditional short-circuit current of the ASSEMBLY (Icc)
Annex ZB: 16 kA rms at 250V, power factor 0.6 with equipment and arrangements specied in Hager’s technical documentation /
catalogue.
Protection against electric shock
Consumer unit shall be installed in an electrical system conforming to the current edition of IEC 60364 / BS 7671
Rated diversity factor (RDF) / Values of assumed loading
1way = 1.0
2way – 3way = 0.8
4way – 5way = 0.7
6way – 9way = 0.6
10way and above = 0.5
Note: RDF only applies to continuously and simultaneously loaded
circuits.
In principle, this means adjacent circuit-breakers having a load
‘on’ time exceeding 30 minutes or where a load not exceeding 30
minutes has an ‘off’ time less than the ‘on’ time, will need to have
the rated diversity factor applied as indicated.
Rated frequency (fn)
50 Hz
Pollution degree
2
Types of system earthing for which the ASSEMBLY is designed
TNC-S, TN-S when installed in an electrical installation complying with BS 7671
Hager recommends for TT systems a 100A type S time delayed RCCB or a main switch with RCBO protection only on all outgoing circuits.
Indoor use only
Stationary ASSEMBLY
Degree of protection
IP2XC with Door Open / closed and full compliment of outgoing devices and or blanks tted.
Note: Where cables are installed through top wall of enclosure, gaps of IP4X to be maintained.
Intended use
Intended for use in domestic (residential) or similar premises.
Electromagnetic compatibility (EMC) classification
EMC Environment B
External design
VC & VH: Wall-mounted, surface type, enclosed assembly.
Mechanical impact protection
IK 05
The type of construction
Fixed parts
Type A DBO (Distribution board for use by ordinary persons)
MCB
tripped
Use circuit as
normal
Use circuit as
normal
Unplug faulty
appliance until
repaired. Reset device.
Other appliances may
be used
Try & reset device once
Try & reset device once
Turn OFF
all MCBs devices
Reset RCCB
Turn ON MCBs
devices one at a time
until RCCB trips again,
identifying faulty circuit
Unplug all
appliances from
circuit and reset
device / replace fuse*
Plug in & switch on
appliances one at a time
until device trips / blows,
identifying faulty appliance
What device
is it?
Does device
stay ON?
Does device
stay ON?
Does device
stay ON?
Does device
supply socket
outlets
Does device
stay ON?
START
YES
YES
YES
YES
YES
MCB
or
RCBO RCCB
NO
NO
NO
NO
NO
T
T
T
ON ON ON
Blank RCCB RCBO (two module) MCB RCBO Switch
(one module)
4ZD0632 - Issue 5 03-15
Insulated
Dimensions
(mm)
Enclosure Size
23456
A110 240 310 380 490
B180 245 245 245 245
CN/A N/A N/A N/A N/A
D94 105 105 105 105
Hybrid
Dimensions
(mm)
Enclosure Size
234567
A168 220 240 310 380 490
B193 230 245 245 245 245
CN/A N/A N/A N/A N/A N/A
D124 110 120 120 120 120
A
D
D
A
B
B

This manual suits for next models

1

Other hager Power Supply manuals

hager TS 111 Installation instructions

hager

hager TS 111 Installation instructions

hager TX 110 User manual

hager

hager TX 110 User manual

hager TGA200 User manual

hager

hager TGA200 User manual

hager TX 110 User manual

hager

hager TX 110 User manual

hager 2903 User manual

hager

hager 2903 User manual

hager TXA111 User manual

hager

hager TXA111 User manual

hager Essensya WE111 Series User manual

hager

hager Essensya WE111 Series User manual

hager TKC110 User manual

hager

hager TKC110 User manual

hager TXA114 User manual

hager

hager TXA114 User manual

hager HXA031H User manual

hager

hager HXA031H User manual

hager TXA 112 User manual

hager

hager TXA 112 User manual

hager TXA 111 User manual

hager

hager TXA 111 User manual

hager TXA112 User manual

hager

hager TXA112 User manual

hager TGA200 User manual

hager

hager TGA200 User manual

hager TXA112 User manual

hager

hager TXA112 User manual

hager TG200 User manual

hager

hager TG200 User manual

hager TX 111 User manual

hager

hager TX 111 User manual

hager 2904 User manual

hager

hager 2904 User manual

Popular Power Supply manuals by other brands

GE Infinity M Series installation guide

GE

GE Infinity M Series installation guide

EnerSys Alpha XRT-TPPL quick start guide

EnerSys

EnerSys Alpha XRT-TPPL quick start guide

Atten ST-1509 user manual

Atten

Atten ST-1509 user manual

LevelOne FVT-5000 user manual

LevelOne

LevelOne FVT-5000 user manual

Pulsar PSBEN 5012C manual

Pulsar

Pulsar PSBEN 5012C manual

Bosch AL 1830 CV Original instructions

Bosch

Bosch AL 1830 CV Original instructions

Jantar SPIDER W40 quick start guide

Jantar

Jantar SPIDER W40 quick start guide

AVS Electronics POWER 1Q manual

AVS Electronics

AVS Electronics POWER 1Q manual

Keithley Series 2200 Operation guide

Keithley

Keithley Series 2200 Operation guide

Amrel PPS-1326 manual

Amrel

Amrel PPS-1326 manual

MRC PWR-3030 Operation manual

MRC

MRC PWR-3030 Operation manual

Pulsar MSRK 2512 manual

Pulsar

Pulsar MSRK 2512 manual

Energizer Arc3 quick start guide

Energizer

Energizer Arc3 quick start guide

Cisco AIR-PWRINJ1500-2 installation instructions

Cisco

Cisco AIR-PWRINJ1500-2 installation instructions

National Instruments FD-11601 CALIBRATION PROCEDURE

National Instruments

National Instruments FD-11601 CALIBRATION PROCEDURE

Goobay DF 1730 LCD manual

Goobay

Goobay DF 1730 LCD manual

BEL LEC120 Series Installation instruction

BEL

BEL LEC120 Series Installation instruction

Norman BP320 Operation instructions

Norman

Norman BP320 Operation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.