
19 Control
To read the current baud rate: read register 21.
To change the baud rate: write a value from the table above to register 21.
Note: When changing the instrument’s baud rate, the baud rate for the COM port must
change in time to successfully receive the response conrming the new baud rate. If it
does not, then the baud rate will change on the instrument, but the response from the
serial terminal will not be understood. Since the serial terminal is set to communicate
at a specic baud rate during the initial conguration, you will have to redene the
terminal baud rate to continue communications.
Setpoint Type
The setpoint type is the signal which will be used to dene the setpoint (controllers only).
To read the setpoint type: read register 516. The values are detailed below.
To change the setpoint type: write one of the following values to register 516 to set the
setpoint source:
0: Analog input.
1: Digital. The setpoint is saved in ash memory as a power up setpoint.
2: Digital. The setpoint is not saved in ash memory.
Changing the Setpoint
The setpoint is the flow rate that a controller attempts to achieve and maintain by
proportionally changing the position of the valve (controllers only).
To read the current setpoint: read register 2106. This is the current setpoint. It may dier
from the commanded setpoint due to limited resolution on congured maximum ramping,
indicated by register 524.
To set the desired setpoint: write the setpoint, as a signed 2-byte integer, to register
33524. The setpoint is equal to the value after formatting with the factory-set number of
decimal places.
Example: if ow units are SCCM, to obtain a setpoint of 10 SCCM, write 10 to
register 33524.
Communication Watchdog
A communication watchdog (controllers only) will force a zero setpoint and close the controller
valve if no serial communication is received within a user-dened time period. The time is
set in milliseconds, and valid values are 0–5000. If zero, the watchdog is disabled.
Note: The Communication Watchdog is only available when the setpoint is being set via
MODBUS communication and the Setpoint Source is set to "unsaved digital" (see page 11).
All other setpoint sources (ASCII, saved digital, analog) are not impacted by the
Communication Watchdog.
: read register 514.
: write a value from 0–5000 to register 514.
Taring the Instrument
Taring adjusts the ow sensor oset so that the current ow value reads zero. This action
gives the instrument a zero reference, ensuring that the instrument provides its most
accurate ow measurements. It is recommended to tare the instrument:
• After installation
• If the instrument is hit with any signicant impact
• After any signicant changes to the temperature or pressure.
To tare the instrument: write 0xAA55 (43605) to register 39. Note that performing a tare
will interrupt any currently-executing measurement.
To enable autotare (controllers only): write 1 to register 515. The instrument will tare ow