
97811C (Rev. A - 5/04) PAGE 2
OVLEBPFR, OVLSBPFR, OVLSEBPFR
OVL - EBPFR/SBPFR/SEBPFR COOLER INSTALLATION
The freeze resistant package must be mounted on an interior wall in a heated area. The room temperature of
the interior heated area must be 50° F (10° C) or higher. The freeze resistant package may be surface or re-
cessed mounted. If recess mounted the surface of the cover must be flush with the interior wall surface. The
package is furnished with screws for mounting the cover to the box. If the box is recess mounted, do not fasten
the top and bottom of the cover to the box. Use the holes on the front only.
1. Wall should already be framed for the fountain using the rough-in dimensions shown in Fig's. 1, 2, 3, 4, 5, or
6. Shown dimensions pertain to installation location (framing must support up to 150 Lbs. weight for single
fountain and 300 Lbs. for dual fountains). These dimensions are required for compliance with ANSI Standard
A117.1 and ADA(Framing shown for reference).
2. Attach wall plate assembly to wall as shown in Fig's. 3, 4, or 6 using 5/16" x 2" long bolts and flat washers
(not provided). Tighten securely, (Fastener must match wall type, i.e. lag screws for wood studs, bolts and
anchors for masonry construction).
3. Install back panel. Place the upper edge of the panel above hanger on the wall. Slide the panel down until it
engages the hanger. Be sure back panel is firmly engaged before releasing it.
4. Remove bottom access panel from fountain basin and save screws. Install the fountain to the back panel
and wall using (4) 5/16" x 3/4" long bolts and washers (provided) thru holes in back panel. A washer is used
on the bottom two (2) holes only. Tighten securely.
5. Assemble the operating cable to the fountain bracket. (Fountain should be mounted to exterior wall)
Create a loop in the cable and thread the free end of the cable through the wall into the freeze resistant box.
The adjustment nuts should be in the middle of threaded area on the operating cable. See Figure 7.
6. Connect free end of operating cable to the valve-operating bracket. The end of the cables must be recessed
into the indents on the pivot brackets. Remove cable free play by adjusting the jam nuts on the ends of the
operating cable. See Figure 7.
7. Connect water line from fountain bubbler into freeze resistant box. The connection to the box uses a quick
connect water fitting. Position the water line, in the fountain, to drain back into interior mounted box. Any
water left standing, in the exterior line, can freeze . See Fig. 13.
To insert tubing, push tube straight into fitting until it reaches a positive stop. To remove tubing from the
fittings, relieve water pressure, push in on dark gray collar while pulling out on the tubing. See Figure 12.
8. Connect drain and water supply lines to the freeze resistant fountain. Refer to Figure 1, 2, 3, 4, 5 or 6 for
component positions. Inline strainer must be used on the inlet water line. See Fig. 11.
Start-up
1. Turn on building water supply and check all connections for leaks. Repair as required.
2. Stream height is factory set at 45-50 PSI. If stream height (See Fig. 14) needs to be changed adjust the
regulator in the freeze resistant package. Clockwise adjustment raises stream height, counter clockwise
adjustment will lower stream.
3. Adjust operating cable as required. Cable system should have a minimal amount of free play to allow for
proper valve operation. If the system is too tight the valve will stay in the on position creating constant water
flow. Too much free play will result in non-operation of the valve with the push-buttons.
4. Note: Water from the drain back tube in the freeze resistant package, will continue to run while the valve is
actuated.
5. After cable system is adjusted properly stuff flexible insulation into any openings between the outside wall
and the interior box.
6. Recheck all connections. If all connections are leak free replace cover(s) on the freeze resistant box(es)
and fountain(s).