HANKISON HPET Series User manual

HIGH PRESSURE
REFRIGERATED
TYPE
COMPRESSED
AIR DRYERS
CONTENTS
GENERAL SAFETY INFORMATION.............................. 2
RECEIVING, MOVING, AND UNPACKING.................... 2
1.0 INSTALLATION ........................................................ 3
2.0 OPERATION ............................................................ 5
3.0 MAINTENANCE....................................................... 6
SIZING............................................................................ 7
ENGINEERING DATA .................................................... 8
P&I DIAGRAM................................................................ 9
WIRING DIAGRAMS ............................................... 10-12
DIMENSIONS / WEIGHTS........................................... 13
TROUBLESHOOTING GUIDE..................................... 14
PARTS LIST ................................................................. 15
WARRANTY ................................................................. 16
INSTRUCTION MANUAL
HPET Series with ColdWave™ Technology
Models: HPET- 4, HPET- 6, HPET- 7.5,
HPET-10
5004258 09/08
18-2-675 5th Edition
SERVICE DEPARTMENT: (724) 746-1100

2
GENERAL SAFETY INFORMATION
1. PRESSURIZED DEVICES:
This equipment is a pressure containing
device.
• Donotexceedmaximumoperating
pressure as shown on equipment
serial number tag.
• Makesureequipmentisdepressurizedbeforeworking
onordisassemblingitforservice.
2. ELECTRICAL:
This equipment requires electricity to
operate.
• Installequipmentincompliancewithall
applicable electrical codes.
• Standardequipmentissuppliedwithelectrical
enclosuresnotintendedforinstallationinhazardous
environments.
• Disconnectpowersupplytoequipmentwhenperforming
anyelectricalservicework.
3. BREATHING AIR:
• Airtreatedbythisequipmentmaynot
besuitableforbreathingwithoutfurther
purication.
Refertoapplicablestandardsandspeci-
cationsfortherequirementsforbreathingqualityair.
RECEIVING, MOVING, AND UNPACKING
A. RECEIVING
Thisshipmenthasbeenthoroughlychecked,packedand
inspectedbeforeleavingourplant.Itwasreceivedin
goodconditionbythecarrierandwassoacknowledged.
CheckforVisibleLossorDamage.Ifthisshipmentshows
evidenceoflossordamageattimeofdeliverytoyou,in-
sistthatanotationofthislossordamagebemadeonthe
delivery receipt by the carrier’s agent.
B. UNPACKING
CheckforConcealedLossorDamage.Whenashipment
has been delivered to you in apparent good order, but
concealeddamageisfounduponunpacking,notifythe
carrier immediately and insist on his agent inspecting the
shipment. Concealed damage claims are not our respon-
sibilityasourtermsareF.O.B.pointofshipment.
C. MOVING
In moving or transporting dryer, do not tip dryer onto its
side.
D. STORAGE/SHUT DOWN
Dryer should not be stored outside (either
packedorunpacked)orexposedtotheweather.Damageto
electrical and control components may result.
IMPORTANT: WATER-COOLED UNITS-Iftheunitisshut
downinbelowfreezingtemperatures,thewater-cooledcon-
densermayfreezeandcausepermanentdamage.Condenser
must be drained when the unit is shut down.
IMPORTANT: Do not store dryer in temperatures above 130°F
(54.4°C).

3
IMPORTANT: READ PRIOR TO STARTING THIS EQUIPMENT
1.0 INSTALLATION
1.1 Location
A. For typical placement in a compressed air system, see
drawing.
B. Aircompressorintake–Locateaircompressorsothat
contaminantspotentiallyharmfultothedryer(e.g.ammo-
nia)arenotdrawnintotheairsystem.
C. FreeAirFlow-Allowaminimumof36inches(914mm)
clearanceforfreeairow.
Service-Tofacilitatemaintenanceleave36inches
(914mm)ofclearanceinfrontofdryer.
D. Standard units are designed to operate in ambients:
Air-cooled:40to110°F(4to43°C).
Water-cooled:40to130°F(4to54°C).
E. Theinstallationofaexibleconnectionpriortothedryeris
recommendedtopreventpossibledamagefromvibration.
NOTE: Outdoorinstallation–Standardunitsaredesignedfor
indoorinstallation.Contactmanufacturerifinstallingoutdoors.
Aftercooler
Separator
Dryer
Oil Removal
Filter
Compressor
Air Inlet
Air Outlet
Condensor
Water Outlet Connection
6-10HP W/C Models Only
Water Inlet Connection
6-10HP W/C Models Only
Drain Outlet
Water Outlet Connection
4HP W/C Model Only
Water Inlet Connection
4HP W/C Model Only
Primary Electrical Entry
Secondary Electrical Entry
Control Panel
Moisture Separators
Electric Timed Drain Assembly
w/3-Way Valve
Models 4, 6, 7.5, and 10

4
1.2 Mounting
Mountthedryeronalevelsolidsurface.Holesareprovidedin
thedryerbasetopermanentlymountthedryertotheoor.
1.3 Piping Connections
A. AirInlet-Connectcompressedairlinefromairsource
toairinlet.(Referencemarkingsondryerorseecallout
drawingonpage13forairinlet/outletconnectionloca-
tions.)
NOTE: Customer piping needs to be properly supported.
Useback-upwrenchwhenmakingpipingconnections.
RefertoSerialNumberTagformaximum
workingpressure.Donotexceeddryer’sMaximumWorking
Pressure.
NOTE: Install dryer in air system at highest pressure possible
(e.g.beforepressurereducingvalves).
NOTE: Install dryer at coolest compressed air temperature
possible.Maximuminletcompressedairtemperature:120°F
(49°C).Ifinletairexceedsthistemperature,precooltheair
withanaftercooler.
B. AirOutlet–Connectairoutlettodownstreamairlines.
NOTE: Customer piping needs to be properly supported.
Useback-upwrenchwhenmakingpipingconnections.
C. Bypasspiping–Ifservicingthedryerwithoutinterrupting
the air supply is desired, piping should include inlet and
outlet valves and an air bypass valve.
D. Watercooledmodels–coolingwaterinletandoutlet
1. Connect cooling water supply to cooling water inlet.
2. Connect cooling water return line to cooling water
outlet connection.
NOTE: Strainer and water regulating valve are supplied on
water cooled models.
1.4 Electrical Connections
IMPORTANT: Use copper supply wires only.
A. Dryer is designed to operate on the volt-
age,phase,andfrequencylistedonthe
serial number tag.
B. Electrical entry on larger dryers is through
a hole in the cabinet. It is located on the right side panel
whenfacingthefrontoftheunit.Connectpowersource
to terminal strip in electrical enclosure as shown on the
wiring diagram included with the dryer.
NOTE:Refrigerationcondensingunitisdesignedtoruncon-
tinuously and should NOTbewiredtocycleon/offwiththeair
compressor.
1.5 Moisture Separator
A. Separatorhasanexternaldrainwhichauto-
matically discharges collected condensate.
NOTE: It may be desirable to pipe the con-
densatefromtheAutomaticDrainoutlettoa
suitable drain.
B. Formanualdraining,convenientdryerdepressurization,
and drain valve maintenance, a three-way valve assembly
is installed between the drain port on the moisture separa-
tor and the drain valve. On all models, the three-way
valveismountedtothebasepan.Reviewthefollowing
forproperdrainfunction:
• AutomaticDraining-Valvehandleshouldbepositioned
paralleltothevalvebody(asshown),withthearrow
on the handle pointing toward the drain valve. In this
position,condensatewillowfromthebowltothedrain
valve.
• DrainIsolation(Shutdown)-Valvehandleshallbe
turnedperpendiculartothevalvebody(rotate90°).In
thisposition,condensateowisshutoff.
Solenoid Valve
Automatic Discharge
Line
Manual Discharge Line
3-Way Valve
Drain Inlets
• ManualDraining-Drainvalvehandleshallberotated
slightly past the drain isolation position to allow
throttlingthroughthevalveformanualdischargeand
depressurization.
NOTE: Discharge is at system pressure. Drain line should be
anchored.
NOTE: Condensate may contain oil. Comply with applicable
laws concerning proper disposal.

5
Ifwaterispresentdownstreamofthedryer,
alwaysverifythatanycondensatedrainsinstalledupstreamof
thedryeraredrainingproperlybeforeattemptingtoreadjust
the LED setting.
1. Forminimuminletairpressuresthatfallbetweencolumn
values,thesettingforthelowerpressureisrecommended.
(i.e.selectthe300psicolumnvaluesfor324psiinletpres-
surelistedinTable1.)
2. Wherethedryerisconsistentlyoperatingatlessthanmax-
imum capacity, it may be possible to increase the LED set
pointtominimizeairloss.Discretionaryadjustmentstothe
dryer should only be made on a hot, humid day when the
maximumexpectedairloadisowingthroughthedryer.
Failuretodosomaypreventthecondensatefromdraining
completelywhenoperatingunderpeakloadconditions.
Table 1 Timed drain illuminated LED Settings
Inlet Pressure
300 400* 500 600 725
Dryer Model
411222
611112
7.5 1 1 1 1 2
1011111
* Recommended and pre-programmed factory settings for each model dryer.
Assumes inlet conditions with 120°F ambient and 10°F air-cooled aftercooler
approach temperature.
Table 2 Timed drain illuminated LED Settings
LED
Illuminated
Minutes
between
Drain Cycles
1st 1
2nd 3
3rd 5
4th 10
5th 20
6th 30
7th 40
8th 50
9th 60
2.0 OPERATION
2.1 Minimum/Maximum Operating Conditions
A. Maximuminletairpressure:725psig(50barg)
B. Minimuminletairpressure:15psig(1.0barg)
C. Maximuminletairtemperature:120°F(49°C)
D. Maximumambienttemperature:
Air-cooledmodels:110°F(43°C)
Water-cooledmodels:130°F(54°C)
E. Minimumambienttemperature:40°F(4°C)
Condensate
Draining
Drain
Push-to-Test
On/Off
Switch
Switch Legend
Power On
Light
Compressor
On Light
Dew Point
Temperature
Indicator
2.2 Start-up
IMPORTANT:Energizedryerdisconnectswitch(providedby
others,seeNEC)24hoursbeforerefrigerationcompressor
is started! Never use the disconnect switch to shut-down the
dryerforaextendedperiodoftime(exceptforrepair).Failure
tofollowtheseinstructionsmayresultinanon-warrantable
compressorfailure.
NOTE: It is recommended that dryer be started 15 minutes
beforecompressedairowbegins.
NOTE:Ifthereisnopowertothecontrolboardforaperiod
oftwoweeksormore,itmayreturntothedefaultmode.
1. ConrmOn/OffSwitchisinthe“Off”position.
2. Checkforproperelectricalvoltage.
3. Energizedryerdisconnectswitch(seeIMPORTANTnote
above)
4. Forwater-cooledmodels:after24hours,begincooling
waterow.
5. ToggleON/OFFswitchtotheONpositiontoenergize
dryer. Green power-on light will illuminate.
6. Slowlypressurizeunitairsidebyopeninginletisolation
valve.Checkforleaks.
7. After15minutes,openoutletisolationvalveslowly.
8. Close air by-pass valve.
2.3 Timer Drain
NOTE: The Timer Drain LED level has been pre-programmed
atthefactoryforyourspecicdryermodel.Programmingis
baseduponaminimumof400psigsaturatedinletairpressure
andmaximumenergyefciency.Thedrainopentimeisxed
atonesecondandasmallamountofairwillbeexhaustedwith
eachcycle.Generally,noadjustmenttothetimerisrequired.

6
2.4 Timer Drain Programming Mode
1. Pressthe“DrainIntervalProgram”button.The“Conden-
sateDraining”LEDwillstarttoash,andtheilluminated
LEDonthe“DewPointTemperatureIndicator”willidentify
thefactorysettingfor“MinutesBetweenDrainCycles.”
(SeeTable1)
2. Pressandreleasethe“DrainIntervalSelector”buttonto
sequencethe“MinutesBetweenDrainCycleLED’s”from
lefttorightuntilreachingyourselection.The“Red”LEDis
notused(ReferenceTable2for“DrainCycleIntervals”)
3. Toinitiatethenewsetting,pressthe“DrainIntervalPro-
gram”button(thiswillstorethenewsettingandexitthe
program).
4. ExitingtheProgramwillcausetheTimerDraintodis-
charge and begin a new cycle.
NOTE:Failuretoperformstep3within25secondsofcom-
pletingstep2willcausetheunittorevertbacktotheprevious
setting.
NOTE:Intheeventofabrieforextendedperiodofpower
loss,theunitwillretaintheexistingprogramsettingandwill
begin a new cycle once power is reapplied. Had drain been
readytodrainbeforethelossofpower,thedrainbowl’scapac-
itywouldpreventdownstreamooding.Condensatewilldrain
completelywithinacoupleofcycles.(Manuallypressingthe
“Push-to-Test”buttonwoulddrainbowlimmediately)
2.5 Operating Check Points
Checkthefollowingonaperiodicbasis:
A. Green power on light is illuminated.
B. Dew point indicator is in green area.
C. Condensateisdischargingfromdrain.
Condensate Draining
(Flashes in
programmingmode)
Drain Interval
Program
Dew Point
Temperature
Indicator
Drain Interval
Selector
(LED illuminated
indicates drain
cyclesetting)
3.0 MAINTENANCE
3.1 Condenser Coil
A. Air-cooled-cleanoffaccumulateddustanddirtmonthlyor
as necessary in dirty environments.
B. Water-cooled-cleanstrainermonthly,moreoftenif
required.Shutoffwater,removesmallplugtorelievepres-
sure, then remove large plug to remove strainer. Clean
strainer and replace.
3.2 Moisture Separator/Oil Removal Filter
NOTE: Prepackagedmaintenancekitsareavailablethat
includeallnecessarylterandtimeddrainvalvecomponents.
MaintainmaximumperformanceandefciencywithGenuine
Parts.Seepage15fororderinginformation.
When to replace the Separator/Filters
Replacelterelementannually,orwhenpressuredrop
acrossdryerisexcessive.
Whenremovingliquidsatratedowconditions,anin-
creaseinpressuredropwilloccurastheseparator/lter
elements become loaded with solid particles.
A A
Separator Head
Separator Element O-Rings
Separator Bowl O-Ring
Separator Element Replacement Sleeve
Separator Bowl Insulation
Separator Element Bottom Cap
Separator Element Nut
Drain Compression Fitting
Separator Bowl
Air InletAir Outlet

7
Procedure for Separator / Filter Element Replacement
THIS FILTER IS A PRESSURE CONTAINING
DEVICE. DEPRESSURIZE BEFORE SERVICING.
1. Isolatedryer(closeinletandoutletvalvesifinstalled)or
shutoffairsupply.
2. Removefrontpanelanddepressurizelterbyslowlyopen-
ing manual drain by-pass valve.
3. Disconnectdrainlinefrombottomofseparator.
4. Disassemblelterhousing.
a. Forallmodels-removethelterbowl,unscrewingit
fromthelterheadbyhandorstrapwrench.
5. Cleanlterbowl.
6. Remove and replace complete element.
a. Unscrewtheoldlterelementanddiscard.Also,
discardthesmallO-ringthatsealstheltertothelter
assembly head.
7. InstallnewlterelementandbowlwithnewO-ringsprop-
erlyseatedtoheadorbowl(dependentupondryersize).
8. Connect drain line and replace panel.
9. Repressurizedryerandresumeoperation.
3.3 Check separator daily to be sure automatic drain is
discharging.
3.4 Blow down separator weekly by pushing test button
on control panel.
3.5 Rebuild drain mechanism annually.
Tofacilitateservice,maintenancekitsareavailable.
SIZING
Determining dryer capacity at actual operating conditions
Todeterminethemaximuminletowcapacityofadryeratvari-
ousoperatingconditions,multiplytheratedcapacityfromTable
1 by the multipliers shown in Table 2.
Example:Howmanyscfmcananair-cooledmodel4handle
when compressed air to be dried is at 350 psig and 90°F; am-
bient air temperature is 80°F?
Answer:1250x1.19x1.12=1666scfm.
Table 1. Rated Capacity
Ratedcapacity(scfm)@725psiginletpressure,100°Finlet
temperature,and100°Fambienttemperatureand60Hertz
operation.
MODEL RATED FLOW
(scfm) m3/hr
4
6
7.5
10
1250
1750
2000
3000
2125
2975
3400
5100
Table 2. Capacity Adjustment Factors for Air Inlet
Temperature and Pressure
INLET PRESSURES INLET TEMPERATURES
(psig) (barg) 80°F
27°C
90°F
32°C
100°F
38°C
110°F
32°C
120°F
49°C
300 to 725 21 to 50 1.49 1.19 1.00 0.83 0.72
Table 3. Capacity Adjustment Factors for Ambient Air
Temperature
AMBIENT
TEMPERATURE
°F (°C)
CAPACITY
ADJUSTMENT
FACTOR
80°F(27°C) 1.12
90°F(32°C) 1.06
100°F(38°C) 1.00
110°F(32°C) 0.94
Water-cooled
(85°F, 29.4°C
coolingwater)
1.15
Table 4. Capacity Adjustment Factors for Electrical
Frequency
50 Hertz 60 Hertz
0.83 1.00

8
Models 4 6 7.5 10
Air System Data
Maximum / Minimum Inlet Air Pressure (compressed air at inlet to dryer) 725 psig (50 barg) / 15 psig (1.0 barg)
Maximum / Minimum Inlet Air Temperature (compressed air at inlet to dryer) 120°F (49°C) / 40°F (4°C)
Maximum / Minimum Ambient Temperature Air-cooled: 110°F (43°C) / 40°F (4°C), Water-cooled: 130°F (54°C) / 40°F (4°C)
Outlet Air Temperature (nominal at rated conditions) 85°F (29°C)
Refrigeration System Data
Refrigeration Capacity @ Rated Flow (BTU/hr)* 60 Hz 42,140 57,310 69,370 92,550
50 Hz 41,400 58,000 70,900 93,300
Refrigerant Type R-404a
Refrigerant Charge See Data Tag on Dryer
Suction Pressure Setting 78 psig (5.4 barg)
Compressor Control Ranges (out-in) (air-cooled models) High 450 - 350 psig (31.0 - 24.1 barg)
Low 84 - 67 psig (5.8 - 4.6 barg)
Compressor Control Ranges (out-in) (water-cooled models) High 320 - 280 psig (22.1 - 19.3 barg)
Low 84 - 67 psig (5.8 - 4.6 barg)
Air-Cooled Condensers
Air Flow Across Condenser (cfm) 60 Hz 3,400 4,230 5,300 4,900
50 Hz 2,830 3,530 4,420 4,080
Condenser Fan Switch Setting (in-out) Fan 1 300 - 230 psig (21 - 16 barg)
Fan 2 N/A 325 - 255 psig (22 - 18 barg)
Water-Cooled Condensers
Water Regulating Valve Setting 135 psig (9.3 barg)
Required Available Water Pressure Differential 40 psig (2.8 barg) - minimum
Flow Required with 85°F Cooling Water (gallons per minute) 60 Hz 12 14 21 27
50 Hz 10 12 18 23
Electrical Data
Nominal Voltage 230/3/60**
Min. - Max. Voltage 207 - 253
Input Power @ Rated Flow (watts) * 5,010 7,710 9,710 14,400
Minimum Circuit Ampacity 25.4 28.0 48.0 63.0
Maximum Overcurrent Protector (amps) 40 45 75 100
Compressor Rated Load Amps 8.2 9.3 15.7 21.1
Compressor Locked Rotor Amps 49.5 70.0 99.0 127.0
Compressor Winding Resistance (ohms) 3.64 2.27 1.41 1.02
Nominal Voltage 460/3/60
Min. - Max. Voltage 414 - 506
Input Power @ Rated Flow (watts) * 5,010 7,710 9,710 14,400
Minimum Circuit Ampacity 12.7 14.0 24.0 31.5
Maximum Overcurrent Protector (amps) 20 20 35 50
Compressor Rated Load Amps 8.2 9.3 15.7 21.1
Compressor Locked Rotor Amps 49.5 70.0 99.0 127.0
Compressor Winding Resistance (ohms) 3.64 2.27 1.41 1.02
Nominal Voltage 575/3/60**
Min. - Max. Voltage 518 - 633
Input Power @ Rated Flow (watts) * 5,010 7,710 9,710 14,400
Minimum Circuit Ampacity 10.2 11.2 19.2 25.2
Maximum Overcurrent Protector (amps) 15 15 30 40
Compressor Rated Load Amps 8.2 9.3 15.7 21.1
Compressor Locked Rotor Amps 49.5 70.0 99.0 127.0
Compressor Winding Resistance (ohms) 3.64 2.27 1.41 1.02
Nominal Voltage 380-420/3/50
Min. - Max. Voltage 342 - 462
Input Power @ Rated Flow (watts) * 3,590 5,380 7,120 10,400
Minimum Circuit Ampacity 12.7 14.0 24.0 31.5
Maximum Overcurrent Protector (amps) 20 20 35 50
Compressor Rated Load Amps 8.2 9.3 15.7 21.1
Compressor Locked Rotor Amps 49.5 70.0 99.0 127.0
Compressor Winding Resistance (ohms) 3.64 2.27 1.41 1.02
* For 60 Hz, 35°F Evaporator, 100°F Ambient; for 50Hz, 35°F Evaporator, 77°F Ambient
** 230/3/60 and 575/3/60 units use equipment transformers on incoming power. Compressor and fan voltage is 460/3/60.
ENGINEERING DATA

9
P&I DIAGRAM
Models 4, 6, 7.5 and 10
AIR
INLET
AIR
OUTLET PROCESS GAS
SYSTEM
REFRIGERATION
SYSTEM
LOW
PRESSURE
SIDE
HIGH
PRESSURE
SIDE
IN
TEMP
(OPTIONAL)
SERVICE
VALVE /
MANUAL
DRAIN
AUTOMATIC
ELECTRIC
DRAIN
CONDENSATE
DRAIN
CARTRIDGE
TYPE
MOISTURE
SEPARATOR
AIR–AIR
HEAT
EXCHANGER
PRE–COOLER
REHEATER
EVAPORATOR
HEAT
EXCHANGER
SET
#4
(USED
ON
MODEL
10)
CARTRIDGE
TYPE
MOISTURE
SEPARATOR
CARTRIDGE
TYPE
MOISTURE
SEPARATOR
CARTRIDGE
TYPE
MOISTURE
SEPARATOR
SERVICE
VALVE /
MANUAL
DRAIN
SERVICE
VALVE /
MANUAL
DRAIN
SERVICE
VALVE /
MANUAL
DRAIN
AUTOMATIC
ELECTRIC
DRAIN
AUTOMATIC
ELECTRIC
DRAIN
AUTOMATIC
ELECTRIC
DRAIN
CONDENSATE
DRAIN
CONDENSATE
DRAIN
CONDENSATE
DRAIN
AIR–AIR
HEAT
EXCHANGER
PRE–COOLER
REHEATER
AIR–AIR
HEAT
EXCHANGER
PRE–COOLER
REHEATER
AIR–AIR
HEAT
EXCHANGER
PRE–COOLER
REHEATER
EVAPORATOR
EVAPORATOR
EVAPORATOR
HEAT
EXCHANGER
SET
#3
(USED
ON
MODELS
7.5–10)
HEAT
EXCHANGER
SET
#2
HEAT
EXCHANGER
SET
#1
HIGH
TEMPERATURE
SWITCH
(OPTIONAL)
OUT
PRESSURE
(OPTIONAL)
DISTRIBUTOR
THERMO–EXPANSION
VALVE
LIQUID
INJECTION
VALVE
SIGHT
GLASS
SIGHT
GLASS
FILTER / DRYER
LIQUID
SHUT–OFF
VALVE
RECEIVER
AIR
COOLED
CONDENSER
(STANDARD)
DISCHARGE
PRESSURE
GAUGE
(OPTIONAL)
WATER
COOLED
CONDENSER
(OPTIONAL)
COOLING
WATER
(OUT)
COOLING
WATER
(IN)
COOLING
WATER
COOLING
WATER
REGULATING
VALVE
STRAINER
OPTIONAL
WATER
COOLED
CONDENSER
DETAIL
HOT
GAS
BY–PASS
VALVEHOT
GAS
SHUT–OFF
VALVE
LOW
PRESSURE
SWITCH HIGH
PRESSURE
SWITCH
FAN
SWITCH
(AIR
COOLED
UNITS
ONLY )
FAN
SWITCH
(AIR
COOLED
UNITS
ONLY )
ACCESS
FITTING
ACCESS
FITTING
SERVICE
DISCHARGE
VALVE
COMPRESSOR
ACCESS
FITTING
SERVICE
SUCTION
VALVE
ACCUMULATOR
SUCTION
FILTER
CRANKCASE
HEATER
PRESSURE
RELIEF
VALVE
SUCTION
PRESSURE
GAUGE
(OPTIONAL)

10
WIRING DIAGRAM
Models4,6,7.5and10(230-400-460V/3/50-60Hz)
(Page1of2)
208V
230V
400V
460V
575V
H6
H6
H6
H6
H6
H5
H4
H3
H2
H1
L2 L1
FACTORY
SET
TO
460V
X1 X2
FU3
XF
X3
H6 H5 H4 H3 H2 H1
FU1
FU2
L3
L1
L3
L1
X
(4 Terminal Blocks)
TB2 XNN
(4 Terminal Blocks)
TB2
N
TO
SHEET
02
X
TO
SHEET
02
L1 L3
FROM
LINE
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
3
PHASE
60
Hz
TB1L1 L2 L3 PE
DISCONNECT
L1
L2
L3
L1
L1 L1
L3
L2
T1
L2
L2
L3
L3
T1
T2 T2
T3
T3
L3 L3
REF
SHEET
01
LINE
20
REF
SHEET
02
LINE
12
T3
T2
T1
T1
T2
T3
TB2
PE
MTR1 COMPRESSOR
COMPRESSOR
HARNESS
T1
T2
TB2
PE
T2
T3
TB2
PE
PE
TB2
L3
1L2
-2NC
-1NC CONT
1
L2
TO
LINE
22
L1
MTR2 FAN
1
(air-cooled only)
MTR3 FAN
2
(air-cooled only)
(Models 6, 7.5 and 10)
FPS
2
FAN
2
HARNESS
FPS
1
FAN
1
HARNESS
HEATER
HARNESS
HEATER
1
H1 H2
CONT
1

11
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
FROM
SHEET
01
X
XX
XX
XX
XX
TB2
XX
TB2
X
X 1
O I 15
TB2
SSMP
T1 T2 (7.5
&
10–HP
MODELS
ONLY)
FROM
SHEET
01
N
N
N
N
N
N
TB2 TB2 4 N TB2
CONT
1
A1
2A2
1
22 4
1
COMPRESSOR
CONTACTOR
HPS/LPS
SENSOR
HARNESS
HPS LPS
TB2
NN
M1 M2
SSMP
MODULE
HARNESS
(7.5
&
10–HP
MODELS
ONLY)
SSMP
M2
M1
LINE
NEUTRAL
THERMISTER
THERMISTER
DRAIN
NEUTRAL
DRAIN
LINE
COMPRESSOR
N
3
CONTROL BOARD
–4NO –3NO 5
CONT
1
XX
TB2
3
TB2
DRAIN
HARNESS
BLUE
BROWN
GRN/YELLOW
DRAIN
HARNESS
3
X
TB2
PE PE
2
3
1
TEST ALM
24VAC
(4
–
6 HP
MODELS
ONLY)
(INSTRUMENT
BOARD
LANDING)
TB2 TB1
HARNESS
LANDING
L1
L2
L3
PE
L1
L2
L3
PE
L1
L2
L3
PE
L1
L2
L3
PE
PE
PE
PE
PE
PE
N
N
N
N
X
X
X
X
3
3
2
2
1
1
5
PE
PE
PE
PE
PE
N
N
N
X
X
X
3
3
2
2
1
(7.5
–
10 HP
MODELS
ONLY)
(INSTRUMENT
BOARD
LANDING)
TB2 TB1
HARNESS
LANDING
WIRING DIAGRAM
Models4,6,7.5and10(230-400-460V/3/50-60Hz)
(Page2of2)

12
WIRING DIAGRAM
Models4,6,7.5and10(575-460/3/60TransformerPack)
TB1
L1
L2
L3
PE
TB1
CONNECTION
460/3/60
460V
1
2
3
PE
H4
H3
H2
H1
G
X4
X3X2X1H4H3
H2
H1
G
X4X3X2X1
1
2
3
PE
575V
L1
L2
L3
PE
TRANSFORMER 1
CUSTOMER
CONNECTION
575/3/60
575V VOLTAGE OPTION
TRANSFORMER 2
575V - 460V TRANSFORMER BANK

13
DIMENSIONS / WEIGHTS
MODEL 4 6 7.5 10
DIM “X” – COOLING WATER I/O CONNECTIONS 3/4-14 NPT (FEMALE) 1-14 NPT (FEMALE) 1.1/4-11.5 NPT (FEMALE)
DIM “Y” – AIR I/O CONNECTIONS 3"-8 NPT (MALE) / Rc 3"-11 BSPT (MALE)
WEIGHT, lbs (kg) 889 (404) 939 (427) 1204 (547) 1329 (604)
NOTE: Dimensions and Weights are for reference only. Request certified drawings for construction purposes.
FRONT VIEW RIGHT SIDE VIEW
BOTTOM VIEW
DETAIL ADETAIL B
CONDENSER AIR FLOW
AB
3 (76)
1 [25]
1 [25]
ELECTRICAL ENTRY
1/4"-18 FPT
DRAIN CONNECTION
3/4”-14 NPT (FEMALE)
I/O WATER CONNECTIONS
(HPET 4 W/C MODEL ONLY`)
“X” (FEMALE)
I/O WATER CONNECTIONS
(HPET 6-10 W/C MODELS ONLY)
WATER OUTLET
WATER INLETWATER INLET
WATER OUTLET
19 (482)
8.15/16 (227)
3.7/8 (98)
46.3/8 (1178)
5.29/32 (150)
18.1/8 (460)
3.13/16 (97)4.1/8 (104)
13.1/16 (332)
5.29/32 (150)
59 (1499)
52 (1321) 3.9/16 (91)
50 (1270)
50 (1270)
4 X Ø5/8 (16)
MOUNTING HOLE
“Y” I/O CONNECTIONS
52 (1321)
SECONDARY ACCESS

14
SYMPTOM POSSIBLE CAUSE(S) CORRECTIVE ACTION
A) Water downstream of dryer 1. Residualfreemoistureremainingin
downstream pipelines.
2. Air bypass system is open.
3. Inlet and Outlet connections are reversed.
4. Temperatures surrounding air lines
downstreamofdryerhavedroppedbelow
dryers dew point rating.
5. Excessivefreemoisture(bulkliquid)atdryer
inlet.
6. Condensate not being automatically drained
Drain mechanism is clogged or inoperative.
Drainlineisrestrictedorfrozen.
Electricdrains-timernotsettoallowfor
sufcientcondensateremoval.
7. Dryer overloaded resulting in elevated dew
point.
8. Refrigerationsystemnotfunctioningproperly
resulting in elevated dew point.
9. Separator element not properly installed.
Blow out system with dry air.
Checkvalvepositions.
Checkforcorrectconnection.
Insulateorheattraceairlinesexposedtolow
ambients or dry air to lower dew point.
Installseparatoraheadofdryer.
Replacedrainmechanismifinoperative.
Open drain line.
Electric drains-reset time so that all liquid is
discharged.
Checkinletairtemperatureandpressure,ow
rate(compressorcapacity)andambientairor
water temperature.
See D below.
Checkelementinstallation.
B) High pressure drop across
dryer
1. Excessiveairow
2. Freezingofmoistureinevaporatorbecauseof
refrigerationsystemimproperlyfunctioning.
3. Inlet air strainer clogged.
4. Separatorlterelementclogged
Checkowrate.
See D below.
Clean inlet air strainer.
Replacelterelement.
C) High Temperature Alarm 1. Dryer overloaded resulting in high air outlet
temperature.
2. Refrigerationsystemnotfunctioningproperly
resulting in high air outlet temperature.
3. Unitfunctioningnormallybuttemperature
sensorismalfunctioningornotsecurely
mounted.
See A7.
See D below.
Contactqualiedrefrigerationrepairmanor
manufacturer’sservicedepartment.Checkpower
to unit.
D) Refrigeration system not
functioning properly
1. Poweronlightoff
2. Compressoronlightoff
3. Refrigerationcompressor
cyclesonandoff
a. Powerfailure
b. Line disconnect switch open
c. Blownfuses,openbreaker
d. Faulty wiring, loose terminals
a. ON/OFFswitchis“OFF”
b. Line disconnect switch open
c. Blownfuses,openbreaker
d. Faulty wiring, loose terminals
a. High or low ambient conditions
b. Air-cooled-Dirty,cloggedcondenserns,
obstructedowacrosscondenser,faultyfan
motororfancontrolswitch.
Checkforpowertounit
Close disconnect switch
Checkforcontinuity
Haveelectriciancheckelectricalconnections.
Turnswitch“ON”
Close disconnect switch
Checkforcontinuity
Haveelectriciancheckelectricalconnections
Checkmin./max.temperatureranges
Cleancondenserandcheckforfreeairow,if
problempersistscontactqualiedrefrigeration
repairmanormanufacturer’sservicedepartment.
TROUBLESHOOTING GUIDE

15
PARTS LIST
MAINTENANCE KITS
MODEL 4 6 7.5 10
Includes Elements, Drain Rebuild Kit,
Bowl O-Rings, and Water Valve Strainer
Screen
HPETMK10 HPETMK10 HPETMK11 HPETMK12
PARTS DESCRIPTION 4 6 7.5 10
Compressor 4006286 3210944 3210945 3221271
Fan Motor 3233147 4010923 4010925 4010925
Fan Blade 3219400 3094035 3210272 3210272
Crankcase Heater 4010508 4010508 3223269 3223269
Low Refrigerant Pressure Switch 3230768 3230768 3230768 3230768
High Refrigerant Pressure Switch (AC) 3230770 3230770 3230770 3230770
High Refrigerant Pressure Switch (WC) 3230771 3230771 3230771 3230771
Fan Cutout Switch 1 3230765 3230765 3230765 3230765
Fan Cutout Switch 2 3230766 3230766 3230766 3230766
Hot Gas By-Pass Valve 3232527 3232527 3232548 3232548
Thermal Expansion Valve 3232550 3232550 3232550 3232532
De-Superheating Valve 3232542 3232542 3232542 3232531
Liquid Line Filter Dryer 4006402 4006402 4006402 4006402
Suction Filter — — 4006414 4006414
Cooling Water Regulating Valve 4006391 4006391 4006391 4006392
Cooling Water Strainer 4009635 4009635 4009635 4009636
Cooling Water Strainer Screen 3230673 3230673 3230673 3230662
Temperature Sensor 3210926 3210926 3210926 3210926
Contactor 5002928 5002928 5002928 5002928
Auxiliary Contactor 5002929 5002929 5002929 5002929
Control Transformer 3159128 3159128 3159128 3159128
Fuse Primary 3223953 3223953 3223953 3223953
Fuse Secondary 4010495 4010495 4010495 4010495
Solid State Motor Protector — — 5004378 5004378
Electric Drain Valve 4009870 4009870 4009870 4009870
Display Board 3227172 3227172 3227172 3227172
Display Board Fuse 5002932 5002932 5002932 5002932
On-Off Switch 3230777 3230777 3230777 3230777
(AC) - Air Cooled Model
(WC) - Water Cooled Model

WARRANTY
AUTHORIZATION FROM THE SERVICE DEPARTMENT IS NECESSARY BEFORE MATERIAL
IS RETURNED TO THE FACTORY OR IN-WARRANTY REPAIRS ARE MADE.
Themanufacturerwarrantstheproductmanufacturedbyit,whenproperlyinstalled,operated,applied,andmaintainedinaccor-
dancewithproceduresandrecommendationsoutlinedinmanufacturer’sinstructionmanuals,tobefreefromdefectsinmaterialor
workmanshipforaperiodasspeciedbelow,providedsuchdefectisdiscoveredandbroughttothemanufacturer’sattentionwithin
theaforesaidwarrantyperiod.
Themanufacturerwillrepairorreplaceanyproductorpartdeterminedtobedefectivebythemanufacturerwithinthewarranty
period,providedsuchdefectoccurredinnormalserviceandnotasaresultofmisuse,abuse,neglectoraccident.Normalmainte-
nanceitemsrequiringroutinereplacementarenotwarranted.Thewarrantycoverspartsandlaborforthewarrantyperiodunless
otherwisespecied.Repairorreplacementshallbemadeatthefactoryortheinstallationsite,atthesoleoptionofthemanufac-
turer.Anyserviceperformedontheproductbyanyoneotherthanthemanufacturermustrstbeauthorizedbythemanufacturer.
Unauthorizedservicevoidsthewarrantyandanyresultingchargeorsubsequentclaimwillnotbepaid.Productsrepairedorre-
placedunderwarrantyshallbewarrantedfortheunexpiredportionofthewarrantyapplyingtotheoriginalproduct.
Theforegoingistheexclusiveremedyofanybuyerofthemanufacturer’sproduct.Themaximumdamagesliabilityofthemanufac-
tureristheoriginalpurchasepriceoftheproductorpart.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, WHETHER WRITTEN, ORAL,
OR STATUTORY, AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED
WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR
DAMAGE BY REASON OF STRICT LIABILITY IN TORT OR ITS NEGLIGENCE IN WHATEVER MANNER INCLUDING DESIGN,
MANUFACTURE OR INSPECTION OF THE EQUIPMENT OR ITS FAILURE TO DISCOVER, REPORT, REPAIR, OR MODIFY
LATENT DEFECTS INHERENT THEREIN.
THE MANUFACTURER, HIS REPRESENTATIVE OR DISTRIBUTOR SHALL NOT BE LIABLE FOR LOSS OF USE OF THE
PRODUCT OR OTHER INCIDENTAL OR CONSEQUENTIAL COSTS, EXPENSES, OR DAMAGES INCURRED BY THE BUYER,
WHETHER ARISING FROM BREACH OF WARRANTY, NEGLIGENCE OR STRICT LIABILITY IN TORT.
Themanufacturerdoesnotwarrantanyproduct,part,material,component,oraccessorymanufacturedbyothersandsoldorsup-
pliedinconnectionwiththesaleofmanufacturer’sproducts.
Warranty Period
Partsandlaborfortwo(2)yearsfromthedateofshipmentfromthefactory;heatexchangersarecovered(partsonly)foran
additionalthree(3)years(totalofve[5]).Onunitsthatmanufacturerrequestsbereturnedtothefactory,aonetimeremoval/
reinstallationlaborallowanceasnotedintheServiceWarrantyPoliciesandProceduresHandbookwillapply.Freighttothefactory
fromtheinstallationsiteandtotheinstallationsitefromthefactorywillbepaidbythemanufacturer;meansoftransportationtobe
speciedbymanufacturer.
SERVICE DEPARTMENT: (724) 746-1100
© 2008 SPX Corporation. All rights reserved.
Improvements and research are continuous at Hankison. Specifications may change without notice.
HANKISON, AN SPX BRAND
1000 PHILADELPHIA STREET
CANONSBURG, PA 15317-1700 U.S.A.
TEL | 724 | 745 | 1555 FAX | 724 | 745 | 6040
Email: [email protected]
www.hankisonintl.com
This manual suits for next models
4
Table of contents
Other HANKISON Dehumidifier manuals

HANKISON
HANKISON HPRP 25 User manual

HANKISON
HANKISON HPR Series User manual

HANKISON
HANKISON HPRP 1000 User manual

HANKISON
HANKISON SPX HES Series User manual

HANKISON
HANKISON SPXFLOW HSHD Series User manual

HANKISON
HANKISON HPRplus Series User manual

HANKISON
HANKISON H Series User manual

HANKISON
HANKISON HPRplus HPRP1000 User manual

HANKISON
HANKISON PR500 User manual

HANKISON
HANKISON SPX Flow FLEX Series User manual