INTRODUCTION
This flanged, industrial refrigeration duty solenoid
valve is very simple and compact but rugged in
construction. Body is plated steel alloy with a
direct lifting stainless steel plunger that contains
a teflon seat that closes on a stainless steel
orifice. When electrically energized, seat opens
wide; when de-energized, it closes to stop flow
in the arrow direction on the valve body.
APPLICATIONS
This small, direct lifting valve is used primarily
as a pilot for various larger gas-powered or
liquid powered main valves, as a remote pilot
for back pressure regulators or other devices,
or as a liquid stop valve for expansion valves,
float valves, or as a general purpose pilot line for
ammonia, R22, R134a, CO2 and other approved
refrigerants or oil.
MAXIMUM RATINGS, AMMONIA
Liquid, Receiver Pressure: 15 Tons (52 kW)
Flow Factor: Cv=0.41 (Kv=0.35)
ADDITIONAL FEATURES
Encapsulated Hansen standard coil
300 psi (20 bar) MOPD
Available close-coupled strainer
Heavy-duty, direct lift
CSA Certified Status
Non-asbestos gaskets
KEY FEATURES
MATERIAL SPECIFICATIONS
Body: Steel, plated
Solenoid Tube: Stainless steel
Plunger: Stainless steel
Seat Orifice: Stainless steel
Seat: Teflon
Safe Working Pressure: 400 psig (27 bar),
600 psig (40 bar) available for CO2
Operating Temperature: -60ºF to 240ºF
(-50ºC to 115ºC)
REMOVABLE
SOLENOID TUBE
TEFLON DISC
STAINLESS STEEL
SEAT
MANUAL OPENING
STEM
Specifications, Applications,
Service Instructions & Parts
HS6
SOLENOID VALVE
5/32” (4 mm) PORT
Bulletin S117c
MAR 2006
Flanged
1/4” thru 3/4”
(7 mm thru 20 mm)
for refrigerants
HS6 Solenoid Valve
with Close-Coupled ST050 Strainer
2
S117c
MAR 2006
Item Description Qty Part No.
Coil Kit (115V) 1/2" Fitting w/leads 1 70-1085
Coil Kit (208/230V) 1/2" Fitting w/leads 1 70-1086
Coil Kit (24V) 1/2" Fitting w/leads 1 70-1087
Coil Kit (Other Voltages) 1 FACTORY
Above kits consist of:
1a Bare Coil, 115V 50/60 Hz w/leads 1 70-0580
1b Bare Coil, 208/230V 50/60Hz w/leads 1 70-0581
1c Bare Coil, 24V 50/60Hz w/leads 170-0582
1d Other Voltage Coils 1FACTORY
3Coil Knob 170-0579
Solenoid Tube/Plunger Kit 1 70-1059
Above kit consists of:
5Solenoid Tube 170-0298
4Plunger 170-0295
6 Solenoid Tube Gasket 1 70-0301
2 O-Ring 1 75-0340
3 Coil Knob 1 70-0579
7 Screws (4) 4 70-0297
Gasket Kit 1 70-1011
Above kit consists of:
6Solenoid Tube Gasket 1 70-0301
8Flange Gasket 1 70-0065
9 Stem O-Ring 1 70-0010
10 Stem Washer 1 70-0026
11 Stem Packing 1 70-0025
12 Packing Nut 1 70-0019
13 Pin 1 70-0150
14 Seal Cap Gasket 1 70-0011
15 Assembled Body Replacement Kit 1 70-1012
Complete Valve less Coil Kit
Seal Cap Kit 1 70-1075
Above kit consists of:
16 Seal Cap 1 75-0798
14 Seal Cap Gasket 1 70-0011
Strainer Screen Kit 1 78-1001
Above kit consists of:
17 Screen Assembly 1 78-0005
18 Strainer Cap Gasket 1 78-0016
Bolt and Nut Kit for HS6 less Strainer 1 70-1006
Bolt and Nut Kit for HS6 with Strainer 1 70-1007
Above kits consist of:
20 Flange Nut (7/16" - 14") 2 70-0055
21a Flange Bolt (less strainer) 3.75" 2 70-0073
21b Flange Bolt (with strainer) 5.5" 2 70-0076
19 Strainer Cap 1 78-0002
22 Assembled Strainer Replacement Kit 1 78-1002
23 Flange Kit (FPT, SW, WN, ODS) FACTORY
Includes (2) flanges only.
Specify style/size.
ADVANTAGES
Power saving, low-wattage encapsulated coil; teflon
seat; stainless steel trim; spring-closing; double-seal
manual opening stem. One standard encapsulated
coil fits all Hansen valves.
INSTALLATION
Match arrow on body with system flow direction.
Protect interior of valve from dirt during installation;
normally use close-coupled inlet strainer. Allow 2.25”
(57 mm) above valve for coil removal, 1” (25 mm) below
for seal cap removal, and 3” (76 mm) below strainer
for screen removal. If a pressure reversal can occur,
as during hot gas defrost with liquid recirculation,
use a check valve on the outlet side of the HS6. For
proper flange gasket sealing, care must be taken when
threading or welding to assure flanges are parallel to
each other and perpendicular to pipe. Also, gaskets
should be lightly oiled and all bolts must be tightened
evenly.
ELECTRICAL
The coil draws 16 watts and will operate properly
between 85% and 110% of rated voltage (24V coil
draws 19 watts). Standard coil connection is a 1/2”
fitting (NPSM) for conduit, with two 18” wire leads and
ground wire. Coils with DIN plug or 1/2” NPSM quick
disconnect plug are available. Contact the factory.
All coils are totally encapsulated and meet NEMA 3R
(rainproof) and NEMA 4 (splashproof, approx. IP65)
requirements. The coil should only be energized
while on the solenoid tube. Otherwise, immediate coil
burnout may occur. To avoid bending the solenoid
tube, remove the coil from valve before connecting
any electrical conduit. Pilot lights are available.
INSTALLATION DIMENSIONS
INCHES (MILLIMETERS)
PARTS LIST
2.95”
(75) ALLOW 2.25” (57)
FOR COIL REMOVAL
3.79”
(96)
4.11”
(104)
WITH PILOT LIGHT
2.50”
(64)
1.50”
(38)
1/2” NPSM
STANDARD
3.31”
(84)
4.94”
(125)
3” (76) WITHOUT STRAINER
ALLOW 3” (76)
FOR STRAINER BASKET REMOVAL
3S117c
MAR 2006
COIL WITH DIN PLUG OR 1/2”
NPSM QUICK DISCONNECT
PLUG CONNECTION AVAILABLE
1/4” OIL DRAIN CONNECTION (OPTIONAL)
5
3
1
4
2
7
6
20
23
15
11 9
12
13
16
10
14
19
18
17
22
21
8
4
S117c
MAR 2006
ODS
STD ALSO STD
1/2" (15) 1/4" (7)
3/8" (10)
3/4" (20) 5/8" (16)
Flange Connection Style & Sizes
Inches (Millimeters)
FPT, SW, WN
Color Part No.
Red 70-1100
Amber 70-1101
Green 70-1102
Beacon Pilot Light Kits
Hansen Technologies Corporation
6827 High Grove Boulevard
Burr Ridge, Illinois 60527 USA
Tel: 630.325.1565 Fax: 630.325.1572 Toll: 800.426.7368
Email: [email protected] Web: www.hantech.com
USA ∙Asia ∙Europe ∙India ∙Latin America ∙Middle East
© 2006 Hansen Technologies Corporation
SERVICE AND MAINTENANCE
Failure to open: Wrong voltage coil; low
line voltage; controlling switch or thermostat
not contacting; coil is burned-out; inlet/outlet
pressure differential too high; plunger is jammed
closed with dirt.
Failure to close: Controlling switch or thermostat
not opening contacts; manual opening stem is
turned in; dirt under seat; eroded seat parts;
plunger is jammed upward by dirt.
Before opening the valve for service, be sure it
is isolated from the system and all refrigerant
is removed. Disconnect electrical power from
coil. Remove the coil by unscrewing the coil
knob. Loosen the four solenoid tube screws
and break gasket seal, proceeding cautiously
to avoid any refrigerant still remaining inside the
valve. Remove the tube screws to separate the
solenoid tube from the body.
Check face of teflon seat in plunger, plunger
spring, and seat orifice in body. Clean, polish
or replace parts as necessary. Always replace
the solenoid tube when replacing the plunger.
These are wear parts and must be inspected
as part of a routine maintenance program. The
seat orifice is integral with the body. Install new
solenoid tube gasket and oil lightly. Reassemble
tube to body with four screws. Factory torque is
2 ft-lbs (2.8 Nm). Carefully check the valve for
leaks before restoring to service.
CAUTION
Hansen valves are for refrigeration systems
only. These instructions must be completely
read and understood before selecting, using or
servicing valves. Only knowledgeable, trained
refrigeration mechanics should install, operate,
or service these valves. Stated temperature and
pressure limits should not be exceeded. Solenoid
tubes should not be removed from valves unless
system has been evacuated to zero pressure.
See also the Safety Precautions in the current
List Price and the Safety Precautions Sheet
supplied with product. Escaping refrigerant
might cause personal injury, particularly to the
eyes and lungs.
WARRANTY
All Hansen products, except electronics,
are guaranteed against defective materials
or workmanship for one year F.O.B. factory.
Electronics are guaranteed against defective
materials or workmanship for 90 days F.O.B.
factory. No consequential damages or field labor
is included.
ORDERING INFORMATION
FPT: Female Pipe Thread (American National Standard)
SW: Socket Weld to accommodate American and API pipe
WN: Weld Neck to match American Schedule 40 pipe
ODS: Outside Diameter Sweat, for copper tube size
Standard encapsulated solenoid coil is included
for 50/60Hz 208/230, 115, or 24 volts; other
voltages offered. Standard coil connection is
a 1/2” fitting (NPSM). Coils with DIN plug or
1/2” NPSM quick disconnect plug are available;
please specify when ordering. Pilot lights are
also available.
OPTIONAL BEACON PILOT LIGHTS
Pilot Light Kit includes Beacon pilot light, knob
and o-ring. A/C Coils Only.
TO ORDER:
Specify type, connection type and size, volts,
and strainer if required. Unless otherwise
specified, standard coil with 1/2” connection will
be supplied.
TYPICAL SPECIFICATIONS
“Refrigerant solenoid valves shall have
encapsulated, watertight coils, Teflon seats,
steel or ductile iron bodies, spring closing
pilot and main valve seats, and be suitable for
a safe working pressure of 400 psig (27 bar),
as manufactured by Hansen Technologies
Corporation or approved equal.”

Other Hansen Control Unit manuals

Hansen HCK4-2 Operating instructions

Hansen

Hansen HCK4-2 Operating instructions

Hansen MCV Operating instructions

Hansen

Hansen MCV Operating instructions

Hansen PXV Series Operating instructions

Hansen

Hansen PXV Series Operating instructions

Hansen HGV1 Operating instructions

Hansen

Hansen HGV1 Operating instructions

Hansen HS7 Operating instructions

Hansen

Hansen HS7 Operating instructions

Hansen HS2 Operating instructions

Hansen

Hansen HS2 Operating instructions

Hansen EZ-SRV Series Operating instructions

Hansen

Hansen EZ-SRV Series Operating instructions

Hansen H5600A Operating instructions

Hansen

Hansen H5600A Operating instructions

Popular Control Unit manuals by other brands

Assa Abloy EffEff 1338-14 Installation and mounting instructions

Assa Abloy

Assa Abloy EffEff 1338-14 Installation and mounting instructions

Texas Instruments TPS65912xEVM-081 How to use

Texas Instruments

Texas Instruments TPS65912xEVM-081 How to use

SynthCube Fuzz Bucket manual

SynthCube

SynthCube Fuzz Bucket manual

Waters Alliance e2695 Operator's guide

Waters

Waters Alliance e2695 Operator's guide

Kohler K-10956 Maintenance Guide

Kohler

Kohler K-10956 Maintenance Guide

DEKA Controls SureStart HSS-32A1 Operating	 instruction

DEKA Controls

DEKA Controls SureStart HSS-32A1 Operating instruction

Cabletron Systems MCC-CRIO quick reference

Cabletron Systems

Cabletron Systems MCC-CRIO quick reference

TLV COSPECT PN-COS-16 instruction manual

TLV

TLV COSPECT PN-COS-16 instruction manual

Coleman 9330F4552 installation instructions

Coleman

Coleman 9330F4552 installation instructions

ABB CPTC-02 user manual

ABB

ABB CPTC-02 user manual

Fireye FlameWorx MBUV-100D manual

Fireye

Fireye FlameWorx MBUV-100D manual

Levil Aviation iLevil3 SW instruction manual

Levil Aviation

Levil Aviation iLevil3 SW instruction manual

EGi DOMOS2 instruction manual

EGi

EGi DOMOS2 instruction manual

Azbil ACTIVAL FVY5130J Specifications & instructions

Azbil

Azbil ACTIVAL FVY5130J Specifications & instructions

Xylem McDonnell & Miller PSE-800-M instruction manual

Xylem

Xylem McDonnell & Miller PSE-800-M instruction manual

Watts LFM110-AS Installation operation & maintenance

Watts

Watts LFM110-AS Installation operation & maintenance

GMI D5090S-086 Instruction & safety manual

GMI

GMI D5090S-086 Instruction & safety manual

Jinergy JNMP60 series Installation and maintenance manual

Jinergy

Jinergy JNMP60 series Installation and maintenance manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.