RSR3 Series
1-888-HAY-INDL (1-888-429-4635)
RSR3IOM Rev B ECR 043V
Page 9 of 9
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
www.haywardowcontrol.com
Hayward Flow Control 1-888-HAY-INDL (1-888-429-4635)
RSR3IOM Rev B ECR 043V
Page 9 of 9
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
www.haywardowcontrol.com
Hayward Flow Control
Reason
No power supply attached
The actuator has been operated in excessively high
ambient temperatures, causing the internal thermal
safety to permanently shut down.
The actuator has been operated in an excessively
high ambient environment and the internal
temperature sensor shut down the actuator.
The 3 position / Jog control wiring is activating both
drive directions at the same time.
Required torque is greater than actuator capabilities.
Control signals are not connected to the proper
actuator wiring.
Actuator is binding due to an incorrect mechanical
mount.
Actuator receives more than 20 pulses (less than
0.5 sec duration) and goes into suspended mode to
protect internal electronics from damage.
Incorrectly wired (polarity)
Actuator has been mounted in ambient temperatures
less than -20 deg C and has not reached its internal
minimum operating temperature (>-20 deg C)
At start-up, an autocalibration routine was NOT
performed.
Actuator is not receiving sucient supply voltage.
Improper wire size / length based on wire sizing
tables.
Bridge 2--5 is in place (see wiring diagram)
Bridge 2--5 is NOT in place (see wiring diagram)
The Maximum permissable duty cycle was exceeded
and the actuator is in a safety disconnect mode.
Error / Symptom
Actuator does not work
LED indicator does not light
Actuator does not work
LED indicator shows steady RED
Actuator does not work
LED indicator shows steady
GREEN
Actuator does not work
LED indicator shows blinking RED
A Modulating actuator reaches its
electrical end of travel (0v/4mA
and/or 10v/20mA) before reaching
damper or valve mechanical end
of travel (90 degrees or less of
mechanical travel).
Actuator does not work
LED indicator ashes irregularly
Spring return function is 3 sec / 90
degrees. Should be 10 sec / 90
degrees.
Spring return function is 10 sec /
90 degrees. Should be 3 sec / 90
degrees.
Actuator does not start after more
than 2 cycles in the 3 sec powered
mode.
Solution
Connect power supply and turn on
Operation in conditions outside that which is specied
has caused irreversible damage inside the actuator
which now must be exchanged.
Remove power from actuator and let temperature
decrease. Reduce ambient temperatures by providing
increased airow over actuator, provide cooling from
ductwork, or reposition the actuator away from high
temperature equipment.
Correct wiring error
Increase actuator size to a higher torque output.
Review wiring diagrams and correct control wiring
faults
Remove the actuator from the driven device. Check
actuator operation without load for full rotation angle
operation
Remove power for at least 2 seconds, resetting the
internal protection device. Correct controller pulse
generator error.
Wire #1 MUST be (-,N) and wire #2 MUST be (+,H)
Ensure that the actuator is powered up at all times.
Wait for the actuator internal heater to heat up the
actuator, thereby starting normal operation.
Perform an autocalibration of the actuator (see step 6
on page 2 of this manual).
Increase power supply voltage.
Increase wire gage between actuator and supply.
Disconnect 2--5 Bridge
Connect 2--5 Bridge
Wait approx. 1 minute until internal electronics cool
down for future use.
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
Troubleshooting-