WIRING GUIDE
All wiring must be installed in compliance with the Canadian Electrical Code,
applicable local codes, and any special requirements of the Authority Having
Jurisdiction. Proper wire gauges should be used. The installation wires should
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper connections will prevent a system from responding properly in the
event of a fire.
Remove power from the communication line before installing sensors.
1. Wire the sensor base (supplied separately) per the wiring diagram, Figure 2.
2. Set the desired address on the sensor address switches, see Figure 1.
3. Install the sensor into the sensor base. Push the sensor into the base while
turning it clockwise to secure it in place.
4. After all sensors have been installed, apply power to the control panel and
activate the communication line.
5. Test the sensor(s) as described in the TESTING section of this manual.
CAUTION
Dust covers provide limited protection against airborne dust particles during
shipping. Dust covers must be removed before the sensors can sense smoke.
Remove sensors prior to heavy remodeling or construction.
FIGURE 2. WIRING DIAGRAM:
2
31
2
33
1
2
1
(–)
(+)
+ -
ULC Listed Compatible
Control Panel
CAUTION: Do not loop wire under
terminal 1 or 2. Break wire run to
supervise connections.
CLASS A OPTIONAL WIRING
Remote
Annunciator
(–)
(+)
RA
+–
+
RA
+–
+
RA
+–
+
C0129-11
TAMPER-RESISTANCE
Photoelectric and temperature sensors include a tamper-resistant capability
that prevents their removal from the base without the use of a tool. Refer to
the base manual for details on making use of this capability.
SPECIFICATIONS
Operating Voltage Range: 15 to 32 VDC
Operating Current @ 24 VDC: 200 uA (one communication every 5 seconds with green LED blink on communication)
Maximum Alarm Current: 2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)
Maximum Current: 4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)
Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing
Operating Temperature Range: 32°F to 100°F (0°C to 38°C)
Air Velocity: 0 to 4000 ft./min. (0 to 1219.2 m/min.)
Height: 2.0˝ (51 mm) installed in B300A-6 Base
Diameter: 6.2˝ (156 mm) installed in B300A-6 Base; 4.1˝ (104 mm) installed in B501 Base
Weight: 3.4 oz. (95 g)
Isolator Load Rating: 0.0063*
*Please refer to your isolator base/module manual for isolator calculation instructions.
CAN/ULC S529 listed for Open Air Protection
CAN/ULC S530 listed for Heat Detectors
This sensor must be installed in compliance with the control panel system
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). Sensors offer maximum performance when
installed in compliance with CAN/ULC S524.
GENERAL DESCRIPTION
Models SD365TA and SD365TA-IV are plug-in type multi-sensor smoke sensors
that combine a photoelectronic sensing chamber and 135°F (57.2°C) fixed
temperature heat detector across addressable-analog communications. The
sensors transmit an analog representation of smoke density over a communi-
cation line to a control panel. Rotary dial switches are provided for setting the
sensor’s address. (See Figure 1.) The intelligent photoelectric and temperature
sensors also transmit an alarm signal due to heat at 135°F (57.2°C) per CAN/
ULC S530.
FIGURE 1. ROTARY ADDRESS SWITCHES:
TENS ONES
910
11
12
13
14
15
8
7
6
5
4
3
210
9
8
7
6
5
4
3
210
C0162-00
Two LEDs on the sensor are controlled by the panel to indicate sensor status.
An output is provided for connection to an optional remote LED annunciator
(P/N RA100ZA).
Fire-Lite panels offer different features sets across different models. As a re-
sult, certain features of the photoelectric and temperature sensors may be
available on some control panels, but not on others. SD365TA will support
only LiteSpeed® protocol mode. SD365TA-IV will support either LiteSpeed or
CLIP (Classic Loop Interface Protocol) mode. The possible features available if
supported by the control panel are:
1. The sensor’s LEDs can operate in three ways—on, off, and blinking–and
they can be set to red, green, or amber. This is controlled by the panel.
2. The remote output may be synchronized to the LED operation or con-
trolled independent of the LEDs.
3. Devices are point addressable up to 159 addresses.
Please refer to the operation manual for the UL listed control panel for spe-
cific operation. The photoelectric and temperature sensors require compatible
addressable communications to function properly. Connect these sensors to
listed-compatible control panels only.
SPACING
Fire-Lite recommends spacing sensors in compliance with CAN/ULC S524.
In low air flow applications with smooth ceilings, space sensors 30 feet apart
(9.1 m). When using the photoelectric and temperature sensors as a heat de-
tector in FM3210 compliant applications, space sensors 20 feet apart (6 m).
For specific information regarding sensor spacing, placement, and special ap-
plications, refer to CAN/ULC S524 or the System Smoke Detector Application
Guide, available from Fire-Lite.
I56-9117-001
INSTALLATION AND MAINTENANCE INSTRUCTIONS
SD365TA and SD365TA-IV
Intelligent Photoelectric and Temperature Sensors
10 Whitmore Road
Woodbridge, Ontario L4L-7Z4
Phone: 1-800-778-9958
1 I56-9117-001
08/08/2018
Fire-Lite®and LiteSpeed®are registered trademarks of Honeywell International, Inc. Testifire®is a registrered trademark of SDi, LLC.
TESTING
Before testing, notify the proper authorities that the system is undergoing
maintenance, and will temporarily be out of service. Disable the system to
prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Test-
ing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors
offer maximum performance when tested and maintained in compliance with
CAN/ULC S536.
The sensor can be tested in the following ways:
A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00)
This sensor can be functionally tested with a test magnet. The test magnet
electronically simulates smoke in the sensing chamber, testing the sensor
electronics and connections to the control panel.
1. Hold the test magnet in the magnet test area as shown in Figure 3.
2. The sensor should alarm the panel.
Two LEDs on the sensor are controlled by the panel to indicate sensor
status. Coded signals, transmitted from the panel, can cause the LEDs to
blink, latch on, or latch off. Refer to the control panel technical documen-
tation for sensor LED status operation and expected delay to alarm.
B. Smoke Entry
Sensitivity readings are available through the FACP. Refer to the manufac-
turer’s published instructions for proper use.
Additionally, canned aerosol simulated smoke (canned smoke agent) may
be used for smoke entry testing of the smoke detector. Tested and ap-
proved aerosol smoke products are:
Manufacturer Model
HSI Fire & Safety 25S, 30S (PURCHECK)
SDi SMOKE CENTURIAN, SOLOA4,
SMOKESABRE, TRUTEST
No Climb TESTIFIRE 2000
When used properly, the canned smoke agent will cause the smoke detector
to go into alarm. Refer to the manufacturer’s published instructions for proper
use of the canned smoke agent.
CAUTION
Canned aerosol simulated smoke (canned smoke agent) formulas will vary by
manufacturer. Misuse or overuse of these products may have long term ad-
verse effects on the smoke detector. Consult the canned smoke agent manufac-
turer’s published instructions for any further warnings or caution statements.
C. Direct Heat Method (Hair dryer of 1000-1500 watts).
A hair dryer of 1000-1500 watts should be used to test the thermistors. Di-
rect the heat toward either of the two thermistors, holding the heat source
approximately 12 inches (30 cm) from the detector in order to avoid dam-
aging the plastic housing. The detector will reset only after it has had suf-
ficient time to cool. Make sure both thermistors are tested individually.
D. Multi-Criteria Method.
A Testifire® by SDi provides testing of the smoke and heat sensors. Consult
the manufacturer’s published instructions for complete instructions.
A sensor that fails any of these tests may need to be cleaned as described
under CLEANING, and retested.
When testing is complete, restore the system to normal operation and notify
the proper authorities that the system is back in operation.
CLEANING
Before removing the detector, notify the proper authorities that the smoke
detector system is undergoing maintenance and will be temporarily out of
service. Disable the zone or system undergoing maintenance to prevent un-
wanted alarms.
1. Remove the sensor to be cleaned from the system.
2. Remove the sensor cover by pressing firmly on each of the four removal
tabs that hold the cover in place.
3. Vacuum the screen carefully without removing it. If further cleaning is
required continue with Step 4, otherwise skip to Step 7.
4. Remove the chamber cover/screen assembly by pulling it straight out.
5. Use a vacuum cleaner or compressed air to remove dust and debris from
the sensing chamber.
6. Reinstall the chamber cover/screen assembly by sliding the edge over the
sensing chamber. Turn until it is firmly in place.
7. Replace the cover using the LEDs to align the cover and then gently push-
ing it until it locks into place. Make sure that the thermistors do not be-
come bent under the cover.
8. Reinstall the detector.
9. Test the detector as described in TESTING.
10. Reconnect disabled circuits.
11. Notify the proper authorities that the system is back on line.
SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS
Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.
FIGURE 3: FEATURES OF THE PHOTO/HEAT DETECTOR
Magnet
Test
Marker
LED
Base
Alignment
Notch
Magnet Test Marker LED
Base Alignment Notch
C2023-00
FIGURE 4: CLEANING THE PHOTO/HEAT DETECTOR
Cover Removal
Tabs
Sensor Cover
Sensing Chamber
Cover and Screen
Sensing Chamber
ThermistorThermistor
}
C2024-00
FCC STATEMENT
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference,
and (2) this device must accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there
is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception,
which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following
measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
This Class B digital apparatus complies with Canadian ICES-003.
Please refer to insert for the Limitations of Fire Alarm Systems
DEVICE AND SYSTEM SECURITY
Before installing this product ensure that the
tamper seal on the packaging is present and
unbroken and the product has not been tampered
with since leaving the factory. Do not install this
product if there are any indications of tampering.
If there are any signs of tampering the product
should be returned to the point of purchase.
It is the responsibility of the system owner to
ensure that all system components, i.e. devices,
panels, wiring etc., are adequately protected to
avoid tampering of the system that could result
in information disclosure, spoofing, and integrity
violation.
2 I56-9117-001
©2018 Fire-Lite. 08/08/2018

This manual suits for next models

1

Other Honeywell Accessories manuals

Honeywell PRO 2000 Series Operation manual

Honeywell

Honeywell PRO 2000 Series Operation manual

Honeywell TC806ES1012 Instruction Manual

Honeywell

Honeywell TC806ES1012 Instruction Manual

Honeywell IS-310 User manual

Honeywell

Honeywell IS-310 User manual

Honeywell CRIR-M1 User manual

Honeywell

Honeywell CRIR-M1 User manual

Honeywell V4043 User manual

Honeywell

Honeywell V4043 User manual

Honeywell TE923WD - Display Unit For Professional Weather Station... User manual

Honeywell

Honeywell TE923WD - Display Unit For Professional Weather Station... User manual

Honeywell T7147 Operation manual

Honeywell

Honeywell T7147 Operation manual

Honeywell DC515 P2 Series User manual

Honeywell

Honeywell DC515 P2 Series User manual

Honeywell Lyric LCT500 User manual

Honeywell

Honeywell Lyric LCT500 User manual

Honeywell DW311S User manual

Honeywell

Honeywell DW311S User manual

Honeywell WSK-24 User manual

Honeywell

Honeywell WSK-24 User manual

Honeywell DT7550UK2 DUAL TEC User manual

Honeywell

Honeywell DT7550UK2 DUAL TEC User manual

Honeywell 205273AA User manual

Honeywell

Honeywell 205273AA User manual

Honeywell 4905 Style Manual

Honeywell

Honeywell 4905 Style Manual

Honeywell DT8050M User manual

Honeywell

Honeywell DT8050M User manual

Honeywell oneWireless XYR 6000 User manual

Honeywell

Honeywell oneWireless XYR 6000 User manual

Honeywell Fire-Lite Alarms AD365 User manual

Honeywell

Honeywell Fire-Lite Alarms AD365 User manual

Honeywell IS3016 User manual

Honeywell

Honeywell IS3016 User manual

Honeywell 5 series Operating instructions

Honeywell

Honeywell 5 series Operating instructions

Honeywell RPW318 Manual

Honeywell

Honeywell RPW318 Manual

Honeywell DC515 Series User manual

Honeywell

Honeywell DC515 Series User manual

Honeywell Lyric SIXPIR User manual

Honeywell

Honeywell Lyric SIXPIR User manual

Honeywell NOTIFIER SMART 2 NFX-SMT2 User manual

Honeywell

Honeywell NOTIFIER SMART 2 NFX-SMT2 User manual

Honeywell IAQPoint2 User manual

Honeywell

Honeywell IAQPoint2 User manual

Popular Accessories manuals by other brands

Auriol HG03031A Operation and safety notes

Auriol

Auriol HG03031A Operation and safety notes

Panasonic HG-C1030 instruction manual

Panasonic

Panasonic HG-C1030 instruction manual

ring Motion Sensor quick guide

ring

ring Motion Sensor quick guide

Melissa 631-106 manual

Melissa

Melissa 631-106 manual

Parker GS100 user manual

Parker

Parker GS100 user manual

BEA SUPERSCAN-T user guide

BEA

BEA SUPERSCAN-T user guide

Saxby Lighting Ikon Pro Instruction leaflet

Saxby Lighting

Saxby Lighting Ikon Pro Instruction leaflet

UPPAbaby VISTA PiggyBack 0062 manual

UPPAbaby

UPPAbaby VISTA PiggyBack 0062 manual

Vega VEGACAP 65 operating instructions

Vega

Vega VEGACAP 65 operating instructions

NATURE & DECOUVERTES IROKO manual

NATURE & DECOUVERTES

NATURE & DECOUVERTES IROKO manual

omnicharge Omni Ultimate quick start guide

omnicharge

omnicharge Omni Ultimate quick start guide

XPOtool 62822 Operation manual

XPOtool

XPOtool 62822 Operation manual

Elsner KNX T-UP gl Installation and adjustment

Elsner

Elsner KNX T-UP gl Installation and adjustment

Hydac CS 1000 Series Operation and maintenance instructions

Hydac

Hydac CS 1000 Series Operation and maintenance instructions

Perenio PECMS01 quick start guide

Perenio

Perenio PECMS01 quick start guide

GE Aritech PB501 installation manual

GE

GE Aritech PB501 installation manual

Pitney Bowes F625 operating guide

Pitney Bowes

Pitney Bowes F625 operating guide

Dorema Magnum 260 Air Manual instructions

Dorema

Dorema Magnum 260 Air Manual instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.