5
DIP Switch Setting
A6 B:Manual
Clockwise
Anticlockwise
24V
A5:Self-Adaption Mode
FD-BV-06.2019-V01
DIP Function Function Description of Setting Value
S2-1 Setting of control/
feedback signal
ON 20%:The control/feedback signal is 4~20mA or 2~10VDC
OFF 0: The control/feedback signal is 0~20mA or 0~10VDC (factory default)
S2-2 Setting of control
signal type
ON II:The control signal is current type.
OFF UI:The control signal is voltage type. (factory default)
S2-3 Setting of control
signal input impedance
ON UI:The control signal is voltage type. (factory default)
OFF II:The control signal is current type.
S2-4
Setting of valve
position feedback
signal type
ON IO:The valve position feedback signal is current type.
OFF UO:The valve position feedback signal is voltage type. (factory default)
S2-5 Setting of operating
mode
ON DA: When control signal increases, actuator moves downward. When control signal decreases, actuator moves upward.
OFF RA: When the control signal increases, the actuator moves upward. When control signal decreases, the actuator moves
downward. (factory default)
S2-6 Setting of signal
interruption mode
ON DW:When the control signal type is set as voltage or current, the actuator will automatically provide a minimum control
signal if the signal cable is cut. (factory default)
OFF
UP:1)When the control signal type is set as voltage, the actuator will automatically provide a maximum control signal if
the signal cable is cut.
2)When the control signal is set as current, actuator will automatically provide a minimal signal when the signal cable
S2-7 Setting of self-
adaption mode
ON DF: In power-on self-adaption mode. (factory default)
OFF RF: In manual self-adaption mode.
S2-8 Setting of control
mode
ON Floating control.
OFF Modulating control. (factory default)
S2-9 Reserved
S2-10 Speed setting ON High speed: 600N - 3s/mm, 1800N - 2s/mm.
OFF Low speed: 600N - 4s/mm, 1800N - 3s/mm.(factory default)
Power-on self-adaption: The actuator will directly enter into self-adaption
mode after being powered up. Meanwhile, the yellow indicator on PCB blinks
(1Hz) and the actuator will be automatically full off (traveling to the bot-
tom) and then full on(traveling to the top). When the indicator stops blink-
ing, it means that the process is completed. Afterwards, the actuator will
travel to the designated position of control signal.
Manual self-adaption: Press and hold button S1 on PCB for more than 5s (See
Fig. 1) until the indicator starts blinking (1Hz) to enter into self-adaption
mode. The phenomenon will be the same as power-on self-adaption.