Honeywell NOTIFIER NFC-50/100 User manual

Document LS10001-001NF-E Rev: H
1/8/2018 ECN: 18-117
Notifier FirstCommand
NFC-50/100 & NFC-50/100E
Instruction Manual

2Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning
devices, and a fire alarm control panel (FACP) with remote notifica-
tion capability—can provide early warning of a developing fire. Such
a system, however, does not assure protection against property
damage or loss of life resulting from a fire.
An emergency communication system—typically made up of an
automatic fire alarm system (as described above) and a life safety
communication system that may include an autonomous control
unit (ACU), local operating console (LOC), voice communication,
and other various interoperable communication methods—can
broadcast a mass notification message. Such a system, however,
does not assure protection against property damage or loss of life
resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat detectors
be located throughout a protected premises following the
recommendations of the current edition of the National Fire
ProtectionAssociation Standard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the
recommendations contained in the Guide for Proper Use of System
Smoke Detectors, which is made available at no charge to all
installing dealers. This document can be found at http://
www.systemsensor.com/appguides/. A study by the Federal
Emergency ManagementAgency (an agency of the United States
government) indicated that smoke detectors may not go off in as
many as 35% of all fires. While fire alarm systems are designed to
provide early warning against fire, they do not guarantee warning or
protection against fire.Afire alarm system may not provide timely or
adequate warning, or simply may not function, for a variety of
reasons:
Smoke detectors may not sense fire where smoke cannot reach
the detectors such as in chimneys, in or behind walls, on roofs, or
on the other side of closed doors. Smoke detectors also may not
sense a fire on another level or floor of a building.A second-floor
detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smoke” from a developing fire may
not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, chim-
neys, even wet or humid areas may inhibit particle or smoke
flow.
• Smoke particles may become “cold,” stratify, and not reach the
ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air out-
lets, such as air conditioning vents.
• Smoke particles may be drawn into air returns before reaching
the detector.
The amount of “smoke” present may be insufficient to alarm smoke
detectors. Smoke detectors are designed to alarm at various levels
of smoke density. If such density levels are not created by a devel-
oping fire at the location of detectors, the detectors will not go into
alarm.
Smoke detectors, even when working properly, have sensing limita-
tions. Detectors that have photoelectronic sensing chambers tend
to detect smoldering fires better than flaming fires, which have little
visible smoke. Detectors that have ionizing-type sensing chambers
tend to detect fast-flaming fires better than smoldering fires.
Because fires develop in different ways and are often unpredictable
in their growth, neither type of detector is necessarily best and a
given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning
of fires caused by arson, children playing with matches (especially
in bedrooms), smoking in bed, and violent explosions (caused by
escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm
only when heat on their sensors increases at a predetermined rate
or reaches a predetermined level. Rate-of-rise heat detectors may
be subject to reduced sensitivity over time. For this reason, the rate-
of-rise feature of each detector should be tested at least once per
year by a qualified fire protection specialist. Heat detectors are
designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same
room as the control panel and in rooms used by the system for the
connection of alarm transmission wiring, communications, signal-
ing, and/or power. If detectors are not so located, a developing fire
may damage the alarm system, compromising its ability to report a
fire.
Audible warning devices such as bells, horns, strobes, speak-
ers and displays may not alert people if these devices are located
on the other side of closed or partly open doors or are located on
another floor of a building. Any warning device may fail to alert peo-
ple with a disability or those who have recently consumed drugs,
alcohol, or medication. Please note that:
• An emergency communication system may take priority over a
fire alarm system in the event of a life safety emergency.
• Voice messaging systems must be designed to meet intelligibility
requirements as defined by NFPA, local codes, andAuthorities
Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly dis-
seminated on any local displays.
• Strobes can, under certain circumstances, cause seizures in
people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a
fire alarm signal, do not respond to or comprehend the meaning
of the signal.Audible devices, such as horns and bells, can have
different tonal patterns and frequencies. It is the property
owner's responsibility to conduct fire drills and other training
exercises to make people aware of fire alarm signals and
instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause
temporary or permanent hearing loss.
A life safety system will not operate without any electrical power. If
AC power fails, the system will operate from standby batteries only
for a specified time and only if the batteries have been properly
maintained and replaced regularly.
Equipment used in the system may not be technically compatible
with the control panel. It is essential to use only equipment listed for
service with your control panel.
Telephone lines needed to transmit alarm signals from a premises
to a central monitoring station may be out of service or temporarily
disabled. For added protection against telephone line failure,
backup radio transmission systems are recommended.
The most common cause of life safety system malfunction is inad-
equate maintenance. To keep the entire life safety system in excel-
lent working order, ongoing maintenance is required per the
manufacturer's recommendations, and UL and NFPAstandards. At
a minimum, the requirements of NFPA72 shall be followed. Envi-
ronments with large amounts of dust, dirt, or high air velocity require
more frequent maintenance.A maintenance agreement should be
arranged through the local manufacturer's representative. Mainte-
nance should be scheduled as required by National and/or local fire
codes and should be performed by authorized professional life
safety system installers only.Adequate written records of all inspec-
tions should be kept. Limit-D2-2016

Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be con-
nected to the fire alarm control panel. Disconnect all sources of
power before servicing. Controlunit and associated equipment may
be damaged by removing and/or inserting cards, modules, or inter-
connecting cables while the unit is energized. Do not attempt to
install, service, or operate this unit until manuals are read and
understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product must be
tested in accordance with NFPA 72 after any programming opera-
tion or change in site-specific software. Re-acceptance testing is
required after any change, addition or deletion of system compo-
nents, or after any modification, repair or adjustment to system
hardware or wiring.All components, circuits, system operations, or
software functions known to be affected by a change must be 100%
tested. In addition, to ensure that other operations are not inadver-
tently affected, at least 10% of initiating devices that are not directly
affected by the change, up to a maximum of 50 devices, must also
be tested and proper system operation verified.
This system meets NFPArequirements for operation at 0-49º C/
32-120º F and at a relative humidity 93% ± 2% RH (noncondens-
ing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the sys-
tem's standby batteries and the electronic components may be
adversely affected by extreme temperature ranges and humidity.
Therefore, it is recommended that this system and its peripherals
be installed in an environment with a normal room temperature of
15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indicating
device loops. Most devices cannot tolerate more than a 10% I.R.
drop from the specified device voltage.
Like all solid state electronic devices, this system may operate
erratically or can be damaged when subjected to lightning induced
transients. Although no system is completely immune from light-
ning transients and interference, proper grounding will reduce sus-
ceptibility. Overhead or outside aerial wiring is not recommended,
due to an increased susceptibility to nearby lightning strikes. Con-
sult with the Technical Services Department if any problems are
anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting
circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make all
cable entries from the sides or rear. Before making modifications,
verify that they will not interfere with battery, transformer, or printed
circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tighten-
ing may damage threads, resulting in reduced terminal contact
pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always
ground yourself with a proper wrist strap before handling any cir-
cuits so that static charges are removed from the body. Use static
suppressive packaging to protect electronic assemblies removed
from the unit.
Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to avoid
damage to the control panel and associated equipment. FACP
operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can radi-
ate radio frequency energy and if not installed and used in
accordance with the instruction manual may cause interfer-
ence to radio communications. It has been tested and found
to comply with the limits for classA computing devices pur-
suant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against such
interference when devices are operated in a commercial
environment. Operation of this equipment in a residential
area is likely to cause interference, in which case the user
will be required to correct the interference at his or her own
expense.
Canadian Requirements
This digital apparatus does not exceed the ClassA limits for
radiation noise emissions from digital apparatus set out in
the Radio Interference Regulations of the Canadian Depart-
ment of Communications.
Le present appareil numerique n'emet pas de bruits radio-
electriques depassant les limites applicables aux appareils
numeriques de la classeA prescrites dans le Reglement sur
le brouillage radioelectrique edicte par le ministere des
Communications du Canada.
HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus™, eVance®, FlashScan®, FAAST Fire Alarm Aspiration Sensing Technology®,
Honeywell®, Intelligent FAAST®, NOTIFIER®, ONYX®, ONYXWorks®, SWIFT®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc.
Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered
trademark of The Mozilla Foundation.
©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

4Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent
upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we
strongly recommend that you download the most current version of software for each product prior to commissioning any system.
Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online
Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical
Services.

Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018 5
Table of Contents
Section 1: Product Description...................................................................................................................................... 12
1.1: Product Features ..............................................................................................................................................................................................12
1.2: Input/Output Circuit Specifications.................................................................................................................................................................13
1.2.1: NFC-50/100 Main Control Board.........................................................................................................................................................13
1.2.2: Display Board.......................................................................................................................................................................................16
1.2.3: NFC-CE6 Circuit Expander Module ....................................................................................................................................................16
1.3: Controls and Indicators....................................................................................................................................................................................17
1.3.1: Push-Button Controls............................................................................................................................................................................17
1.3.2: LED Indicators (visible with door closed)............................................................................................................................................17
1.3.3: LED Indicators (visible with door and dress panel open) ....................................................................................................................18
1.4: Components.....................................................................................................................................................................................................18
1.5: Optional Equipment.........................................................................................................................................................................................20
1.6: UL 464 Low Frequency Sounders...................................................................................................................................................................21
Section 2: Installation ..................................................................................................................................................... 22
2.1: Mounting Options............................................................................................................................................................................................22
2.2: Backbox Installation........................................................................................................................................................................................22
Removing the Dress Panel......................................................................................................................................................................22
Removing the Chassis Assembly............................................................................................................................................................23
Mounting the Backbox............................................................................................................................................................................23
2.3: Operating Power..............................................................................................................................................................................................25
2.3.1: AC Power and Earth Ground Connection ............................................................................................................................................25
2.3.2: Secondary Power Source (Batteries) ....................................................................................................................................................27
2.4: Auxiliary DC Power Output Connections .......................................................................................................................................................27
2.5: Input/Initiating Circuits ...................................................................................................................................................................................28
2.5.1: CMD Inputs ..........................................................................................................................................................................................28
2.5.2: External Audio Input ............................................................................................................................................................................29
2.5.3: NAC Follower Input.............................................................................................................................................................................29
2.5.4: Night Ring ............................................................................................................................................................................................30
2.6: Output Circuits.................................................................................................................................................................................................30
2.6.1: Relays ...................................................................................................................................................................................................30
MNS Active Relay - TB1 .......................................................................................................................................................................30
Trouble Relay - TB2...............................................................................................................................................................................31
AC Power Loss Relay - TB3 ..................................................................................................................................................................31
2.6.2: Speaker Circuits....................................................................................................................................................................................31
2.6.3: Notification Appliance Circuit .............................................................................................................................................................32
2.6.4: Speaker Volume Control ......................................................................................................................................................................33
2.6.5: FACP Data Bus.....................................................................................................................................................................................34
NFW-100X .............................................................................................................................................................................................34
FireWarden-100-2...................................................................................................................................................................................34
NFS2-640 and NFS-320 .........................................................................................................................................................................35
ACS Mode Wiring..................................................................................................................................................................................35
2.7: NFC-LOC Local Operator Console.................................................................................................................................................................36
2.8: NFC-RPU Remote Page Unit..........................................................................................................................................................................38
2.9: NFC-RM Remote Microphone........................................................................................................................................................................40
2.10: NFC-50DA, NFC-125DA, NFC-50/100DADistributed Audio Amplifiers..................................................................................................40
2.11: Shielding for External Device Wiring............................................................................................................................................................41
2.12: UL Power-limited Wiring Requirements.......................................................................................................................................................42
2.13: Installation of Option Modules......................................................................................................................................................................43
2.13.1: NFC-CE6 Circuit Expander Module ..................................................................................................................................................43
2.13.2: Audio Amplifier Module (NFC-BDA-25/70V)..................................................................................................................................43
Installation ..............................................................................................................................................................................................43
Power and Control Cables ......................................................................................................................................................................45
Configuration..........................................................................................................................................................................................45
NFC-50/100 Configurations with NFC-BDA-25/70V...........................................................................................................................45
2.13.3: 70.7 VRMS Transformer (NFC-XRM-70V)........................................................................................................................................47
2.14: Addressing External Data Bus Devices.........................................................................................................................................................48
Section 3: Programming................................................................................................................................................. 51
3.1: NFC-50/100 Panel Installation/Maintenance Security Checklist....................................................................................................................51
3.2: Main Menu - User Programming.....................................................................................................................................................................52
3.2.1: Password Options .................................................................................................................................................................................52

6Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
Table of Contents
3.2.2: General/NAC Options ..........................................................................................................................................................................53
General Options......................................................................................................................................................................................53
NAC Options ..........................................................................................................................................................................................54
Console Control......................................................................................................................................................................................54
3.2.3: Address Assignment.............................................................................................................................................................................55
Remote Microphone / Operator Console Address Assignments ............................................................................................................55
Speaker Circuit Address Assignment .....................................................................................................................................................55
3.2.4: Message Buttons...................................................................................................................................................................................56
Message Buttons.....................................................................................................................................................................................56
CMD Input Style.....................................................................................................................................................................................57
3.2.5: Date / Time...........................................................................................................................................................................................57
3.2.6: Send to Panel ........................................................................................................................................................................................57
3.3: Main Menu - Utilities ......................................................................................................................................................................................57
3.3.1: Message Recording...............................................................................................................................................................................58
3.3.2: USB File Options..................................................................................................................................................................................58
3.4: Main Menu - Informational .............................................................................................................................................................................59
3.4.1: Informational ........................................................................................................................................................................................59
Speaker Circuit Buttons..........................................................................................................................................................................59
Version Information................................................................................................................................................................................60
History Information ................................................................................................................................................................................60
3.5: Recording Custom Messages...........................................................................................................................................................................61
3.5.1: Message Record Mode .........................................................................................................................................................................61
3.5.2: External Audio Input ............................................................................................................................................................................61
Recording with External Audio - Example.............................................................................................................................................62
3.5.3: Microphone...........................................................................................................................................................................................62
Recording with Microphone - Example..................................................................................................................................................63
3.5.4: Erasing a User Message........................................................................................................................................................................63
3.5.5: Voice Loader Software.........................................................................................................................................................................63
Writing a Message to the Panel ..............................................................................................................................................................64
Reading a Message from the Panel.........................................................................................................................................................64
Moving a Message to a Different Slot....................................................................................................................................................64
3.6: Programmed Activation by FACP ...................................................................................................................................................................64
3.6.1: FireWarden-100X and FireWarden-100-2 ...........................................................................................................................................65
FACP Programming ...............................................................................................................................................................................65
FACP Message Assignment - Speaker Specific.....................................................................................................................................66
FACP Message Assignment - Zone Specific..........................................................................................................................................66
FACP Programming Menus....................................................................................................................................................................67
3.6.2: NFS2-640 and NFS-320.......................................................................................................................................................................68
FACP Programming ...............................................................................................................................................................................68
Section 4: Operating Instructions.................................................................................................................................. 70
4.1: Main Control Panel Keypad Labels.................................................................................................................................................................70
4.2: NFC-50/100 Switch Functions........................................................................................................................................................................70
4.3: LED Indicators.................................................................................................................................................................................................71
4.4: Operation .........................................................................................................................................................................................................72
4.4.1: Paging from the Microphone................................................................................................................................................................72
4.4.2: Manual Message Control......................................................................................................................................................................72
4.4.3: Fire Alarm Response, System Configured for Fire Only .....................................................................................................................73
4.4.4: Fire Alarm Restoral, System Configured for Fire Only .......................................................................................................................73
4.4.5: Manual Activation ................................................................................................................................................................................73
4.4.6: Manual Activation Restoral..................................................................................................................................................................73
4.4.7: Alarm/Alert Response, System Configured for Mass Notification Only.............................................................................................73
4.4.8: Alarm/Alert Restoral, System Configured for Mass Notification Only...............................................................................................74
4.4.9: Alarm/Alert Response, System Configured for Combo Fire/Mass Notification with Fire Priority.....................................................74
4.4.10: Alarm/Alert Restoral, System Configured for Combo Fire/Mass Notification with Fire Priority.....................................................74
4.4.11: Alarm/Alert Response, System Configured for Combo Fire/Mass Notification with Mass Notification Priority.............................74
4.4.12: Alarm/Alert Restoral, System Configured for Combo Fire/Mass Notification with Mass Notification Priority...............................75
4.4.13: Trouble Condition Response ..............................................................................................................................................................75
4.4.14: Trouble Condition Restoral ................................................................................................................................................................75
4.4.15: External Audio Input Operation .........................................................................................................................................................76
Section 5: Getting Started .............................................................................................................................................. 77
5.1: System Requiring up to 50 Watts of Audio Power ..........................................................................................................................................77

Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018 7
Table of Contents
5.2: System Requiring Up to 100 Watts of Audio Power .......................................................................................................................................77
5.3: System Requiring Greater Than 100 Watts of Audio Power...........................................................................................................................77
Section 6: Power Supply Calculations.......................................................................................................................... 78
6.1: Overview..........................................................................................................................................................................................................78
6.2: Calculating the AC Branch Circuit..................................................................................................................................................................78
6.3: Calculating the System Current Draw.............................................................................................................................................................78
6.3.1: Overview...............................................................................................................................................................................................78
6.3.2: How to use Table 6.2 to calculate system current draws......................................................................................................................78
6.4: Calculating the Battery Size ............................................................................................................................................................................80
6.4.1: NFPA Battery Requirements................................................................................................................................................................80
6.4.2: Selecting and Locating Batteries ..........................................................................................................................................................80
Appendix A: Digital Voice Messages............................................................................................................................. 81
Appendix B: Wiring Requirements ................................................................................................................................ 82
Appendix C: Canadian Applications.............................................................................................................................. 83
C.1: Audio Room Isolator Modules........................................................................................................................................................................83
C.1.1: Description...........................................................................................................................................................................................83
C.1.2: Panel Programming..............................................................................................................................................................................83
C.1.3: Applications .........................................................................................................................................................................................83
Slide-in Labels - Upper Portion...................................................................................................................................... 85
Slide-in Labels - Lower Section ..................................................................................................................................... 87
Index................................................................................................................................................................................. 89
NFC-50/100 and NFC-LOC OPERATING INSTRUCTIONS............................................................................................ 93

8Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
This control panel has been designed to comply with standards set forth by the following regulatory agencies:
• Underwriters Laboratories/Underwriters Laboratories Canada
• National Fire Protection Association
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code
Note: Audible signal appliances used in public mode applications, are required to have minimum sound levels of 75 dBAat 10 feet
(3 meters) and a maximum level of 120 dBA at the minimum hearing distance from the audible appliance.
To ensure that the appliance is clearly heard, the audible appliance sound level must be at least 15 dBA above the average ambient
sound level or 5 dBA above the maximum sound level with a duration of at least 60 seconds, depending on which level is greater,
with the sound level being measured 5 feet (1.5 meters) above the floor.
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 464 Audible Signaling Appliances
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1480 Speakers for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1711 Amplifiers for Fire Protective Signaling Systems
UL 1971 Signaling Devices for Hearing Impaired
UL 2572 Communication and Control Units for Mass Notification Systems
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
CAN/ULC - S527-11 Standard for Control Units for Fire Alarm Systems
This Class (A) digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe (A) est conforme à la norme NMB-003 du Canada.
Other:
Canadian Electrical Code, Part 1
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Notifier Documents:
Notifier Device Compatibility Document Document #15378
NFC Distributed Audio Manual Document #LS10027-001NF-E
NFC-FFT Manual Document #LS10031-001NF-E
NFC-LOC Installation Document Document #LS10028-001NF-E
NFC-RPU Installation Document Document #LS10030-001NF-E
NFC-RM Installation Document Document #LS10029-001NF-E
NFC-CE6 Installation Document Document #LS10033-001NF-E
NFC-CE4 Installation Document Document #LS10002-001NF-E
NFC-BDA-25/70V Installation Document Document #LS10035-001NF-E
NFC-XRM-70V Installation Document Document #LS10032-001NF-E
NFW-100X Manual Document #LS10131-001NF-E
NFS2-640 Listing Document Document # 52741LD
NFS-320 Listing Document Document # 52745LD
FireWarden-100-2 Series Manual Document #52778
Before proceeding, the installer should be familiar with the following documents.

Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018 9
Speaker Circuits
TB20 & TB21
internal options NFC-BDA-25/70V
optional amplifier NFC-CE6
circuit expander
NFC-50DA
50W remote amplifier
NFC-RPU
remote page unit NFC-RM
remote microphone
remote
consoles
distributed
audio
NFC-125DA
125W remote amplifier
NFC-LOC
local operator console
CHG-120
charger CHG-75
charger
external battery
charger - J7
TB24
TB12
TB22
nfcperi.wmf
NAC Circuit
TB19
visual only
NFC-FFT
firefighter telephone
NFC-50/100DA
50/100W remote
amplifier

10 Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
+
+
+
J12
TB15
J9
RTZM
DISPLAY
CAUTION!HIGHVOLTAGE
ecc50layo.wmf
AC Power
(Supervised,
Nonpower-Limited)
120 VAC, 60 Hz, 3.5 amps
or
230 VAC, 50 Hz, 2.0 amps
Special Application DC Power Output (24 VDC)
Supervised, Power-Limited (Class 2) circuit
Supervise with a power supervision relay EOLR-1
Nonresettable Power suitable for powering control
modules and power supervision relays.
NAC Follower Input
Supervised, Power-
Limited (Class 2)
circuits
24 VDC filtered (10
mA maximum),
Requires an FACP
End-of-Line Resistor
AC Loss, MNS Active, &
Fixed Trouble Relay
Non-supervised relay contacts
Contact rating:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Contacts shown below in
normal condition (AC power
with no alarm, trouble, or
supervisory activity)
Fail Safe Trouble relay
switches to the NO position
during trouble conditions and
under loss of all power.
Flash Memory Load Enable
Switch: UP is normal
position for switch, DOWN
position allows for factory
software upgrades
Ethernet Port J2/
for local programming
using a personal
computer and web-
based utility
Battery
24 VDC, supervised,
Non-power-limited,
26 AH maximum
Notification
Appliance Circuit
Style Y (Class B) or
Style Z (Class A)
Supervised, Power-
Limited (Class 2)
(Special
application) 2.0
amps max.
Regulated power:
200mA max.
ELR, 4.7K, 1/2W
(for Style Y wiring)
Optional 50W Amplifier
connectors
Optional 70V
Transformer connector
Optional CE6 Circuit
Expander Connector
Display Board
connector
Speaker Volume Control Override
Style Y (Class B) or Style Z (Class A)
Supervised, Power-Limited (Class 2)
(Special application) 0.25 amps max.
4.7KΩELR, 1/2W required for Style Y
(Class B) wiring
Primary/Secondary Speaker Circuits
Style Y (Class B) or Style Z (Class A)
Supervised, Power-Limited (Class 2)
50W integrated output power. Use of
secondary circuit requires optional
NFC-BDA-25/70V amplifier
15KΩELR, 1W required for Style Y
(Class B) wiring
CMD1 & CMD2 Command Input Circuits
Trigger by contact closure or NAC reverse
polarity (ELR required for messages)
alarm polarity shown.
CMD3 - CMD8 Command Input Circuits
Trigger by contact closure (ELR required
for messages) alarm polarity shown.
(inputs only)
Night Ring Input
Trigger by contact closure
External Operator Interface Power
Supervised, Power-Limited
(Class 2) circuit
24 VDC Nonresettable Power for
external operator interface components.
ExteArnal Data Bus
Supervised, Power-Limited
(Class 2) data connections to
external operator interface
components
FACP Data Bus
Supervised, Power-Limited
circuit dedicated as FACP
serial bus connection
External Audio Riser
Style Y (Class B) or Style Z (Class A)
Supervised, Power-Limited (Class 2)
audio connection to external operator
interface components
Speaker
Voltage
Switch
SW5
To disable
ground fault
detection,
remove
jumper/shunt
from JS2.
NFC-50/100
Trouble LEDs.
See
Section 1.3.3
on page 18 for
more
information.
Basic System Connections - Main Control Board (Section 1.2.1)
Cut jumper to use
external charger
Backup amplifier
test switch SW6
Set switch to
Normal
(down position)
USB-A Port J1/
for local program
download

Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018 11
TB5- External Audio Input/
Audio Riser
SW1- Dipswitch for
BUS addressing
Must be set to
address 2.
ON
JP5 -
isolation/ground
when powered by
source other than
main control board
J2- Connection to
main control board
P2- Microphone
connector J1- USB connector -
connection to a PC for
downloading messages
Refer to Section 3.5.5 on
page 63.
Basic System Connections - Display Board (Section 1.2.2)
disp.wmf
SW2- Distributed Audio Switch
set to UP position if any
NFC-50/125DAs are installed
in the system.
Default is the DOWN position.
JP2 - External Data
Bus termination

12 Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
Section 1: Product Description
The Notifier FirstCommand NFC-50/100 is a single channel, 50 watt, 25 VRMS, emergency voice evacuation panel that may be used for
fire applications, mass notification applications, or both. The NFC-50/100 comes standard with one speaker circuit. The panel provides
the ability to record fourteen field programmable messages (up to 60 seconds each) with an integral microphone or from an external
audio source. An integral power supply with battery charger supplies operational power. A 50 watt audio amplifier is built into each
panel. An optional second 50 watt amplifier (NFC-BDA-25/70V) is also available for backup purposes or to provide an additional 50
watts. The backup amplifier is available in either 25 volts or 70 volts depending on which application is necessary.
Automatic activation of the NFC-50/100 by an FACP is possible via eight Command Input Circuits (CMD) or via the ACS/ANN Bus
serial communications link from the FireWarden-100X, FireWarden-100-2, NFS2-640, and NFS-320 FACPs.
Two Command Input Circuits can be independently field programmed for activation by an FACP NotificationAppliance Circuit reverse
polarity or by closure of a supervised normally open contact and six Command Input Circuits activate on contact closure. CMD 1 and
CMD 2 provide terminals for NAC input and output to allow installation of the audio panel anywhere along the NAC circuit being used
to activate it.
If the message generator fails, the system automatically reverts to a backup tone generator.
Power is fed independently to each amplifier so that a short circuit in one amplifier will not shut down the other. Full output power of 50
watts per amplifier is generated while in a low battery condition. Power is not diminished when the optional 70 VRMS transformer mod-
ule is installed.Audio is amplified utilizing modern integrated circuits as opposed to transformer technology. This provides for very low
signal distortion for crystal clear audio.
Primary applications for the audio panels include protecting structures such as military facilities, restaurants, schools, auditoriums,
places of worship, buildings with occupancies over 50, etc. The NFC-50/100 is designed to interface directly to addressable or conven-
tional (CMD inputs 1-8) fire alarm control panels or can be used with the NFC-50/125DApanel to distribute audio in systems that
require more than 100 watts.
For Canadian applications, refer to Appendix C on page 83.
1.1 Product Features
• Modular design for maximum system flexibility and easy expansion
• Removable terminal blocks for ease of servicing and module replacement
• 50 watts of 25 VRMS audio power (expandable to 100 watts)
• 2 amp Notification Appliance Circuit (NAC) output, sync generator, or follower for protocols:
– System Sensor
– Wheelock
–Gentex
• Optional 70.7 VRMS conversion transformer available for the primary amplifier (note that speaker wiring continues to be supervised
in standby, alarm and when background music is playing with this optional transformer installed)
• Eight Command Input Circuits to activate messages 1 to 8:
– CMD1 and CMD2 are field selectable to be activated from 12 or 24 VDC Notification Appliance Circuits (reverse polarity) or
contact closures
– CMD3-CMD8 are activated by contact closures
• Speaker Circuits
– single Style Y (Class B) or Style Z (Class A) speaker circuit
– two Style Y (Class B) or Style Z (Class A) speaker circuits (with optional NFC-BDA-25/70V Audio Amplifier installed)
– eight Style Y (Class B) or Style Z (Class A) speaker circuits (with optional NFC-BDA-25/70V and NFC-CE6 installed)
• NFC-50/100 can be controlled by an FACP via the ANN/ACS (EIA-485) link. ACS compatible FACPs include the FireWarden-
100X, FireWarden-100-2, NFS2-640, and NFS-320. ANN compatible FACPs include the FireWarden-100-2.
• Integral supervised microphone
• Microphone time-out feature which reverts back to prerecorded message if emergency page exceeds the programmed time
• Up to 14 recorded messages
• 14 prerecorded messages for fire, emergency, and weather alerts
• Field-selectable message and custom message recording capability using the local microphone, a USB port, or an external audio
input
• External Audio Input can be used for background music
• Up to 60 second message duration for all messages
• Integral tone generators field selectable for multiple tone types
• Powered by integral AC power supply or batteries during AC fail
• Programmable delay of immediate, 2 hours or 6 hours reporting of AC Loss
• Piezo sounder for local trouble
• 100 event history log
• Three Form-C relays:
– AC Power Loss Relay - TB1
– System Trouble Relay - TB2
– MNS Active - TB3
• 500 mA(0.5A) Special Application (auxiliary power) output for addressable modules when interfaced with compatible addressable
FACPs and End-of-Line power supervision relays

Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018 13
Input/Output Circuit Specifications Product Description
• System Status LEDs (refer to “Controls and Indicators” on page 17)
• Integral Dress Panel
• Optional TR-CE-B semi-flush trim ring
• Any combination of up to eight (8) of:
– Optional NFC-RM Remote Microphone (includes cabinet).
– Optional NFC-RPU Remote Page Unit (includes cabinet)
– Optional NFC-LOC (includes cabinet)
• Optional NFC-CE6 Circuit Expander
• Optional NFC-BDA-25V amplifier, 50 watts, 25 volts
• Optional NFC-BDA-70V amplifier, 50 watts, 70 volts
• Optional NFC-50DA distributed amplifier, 50 watts
• Optional NFC-125DA distributed amplifier, 125 watts
• Optional NFC-50/100DA distributed amplifier, 50/100 watts
1.2 Input/Output Circuit Specifications
1.2.1 NFC-50/100 Main Control Board
AC Power - TB15
NFC-50/100: 120 VAC, 60 Hz, 3.5 amps (HOT, NEU)
NFC-50/100E: 240 VAC, 50 Hz, 2.0 amps (HOT=HotLeg1, NEU=HotLeg2)
Wire size: minimum #14 AWG (2.00mm2) with 600 V insulation.
Battery (lead acid only) - J7
Maximum Charging Circuit: Normal Flat Charge - 27.3V @ 2.8 amps
Maximum Charger Capacity: 26Amp Hour battery. (NFC cabinet holds max. 18 Amp Hour Battery.
Minimum Battery Size: 12 Amp Hour
MNS Active Relay - TB1
Form-C relay contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive),
Form-C Trouble Relay - TB2
Form-C relay contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amp @ 30 VAC (resistive).
AC Loss Relay - TB3
Form-C relay contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive),
NAC Output - TB19, Terminals 1 (B+), 2 (A+), 3 (A-), & 4 (B-)
One (1) Style Y (Class B) or Style Z (Class A) circuit
Power-limited circuitry (Class 2), supervised
Nominal operating voltage: 24 VDC
Maximum signaling current for special application power: 2.0 amps
Maximum signaling current for regulated power: 200mA
Current limit: fuseless, electronic, power-limited
Maximum wiring impedance: 1 Ω
End-Of-Line Resistor: 4.7 KΩ, ½ watt, (P/N 71252) required for Style Y (Class B) operation
Refer to the Device Compatibility Document for listed compatible devices.
NAC Follower - TB18, Terminals 3 (IN+), 4 (IN-), 1 (OUT+) & 2 (OUT-)
Connections for FACP NAC synchronization trigger signal
Output terminals: pass-through to other system components
Trigger input voltage: 9 to 32 VDC, 24 VDC rated
Input current draw in Alarm condition: 10 mA at rated voltage
Special Application Power (Aux. Power) - TB17 Terminals 1(+) & 2(-)
Up to 500 mA@ 24 VDC of special application power is available for powering addressable modules and associated End-of-Line power
supervision relays.
Power-limited (Class 2) circuitry. Refer to the Device Compatibility Document for a list of compatible devices.
Speaker Volume Control Override - TB23, Terminals 1 (B+), 2 (A+), 3 (A-), & 4 (B-)
Style Y (Class B) or Style Z (Class A) circuit
Special Application power
Power-limited (Class 2) circuitry, supervised
Nominal operating voltage: 24 VDC
Maximum signaling current: 0.25 amps
Current limit: fuseless, electronic, power-limited
End-Of-Line Resistor: 4.7 KΩ, ½ watt, (P/N 71252) required for Style Y (Class B) operation

14 Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
Product Description Input/Output Circuit Specifications
Speaker Circuits
Primary Speaker Circuit - TB20, Terminals 1(+) & 2(-) Style Y (Class B), 4(+) & 5(-) Style Z (ClassA), 3 Shield (Standby and Alarm
Polarity Shown) on main control board
Secondary Speaker Circuit (with optional amplifieronly) - TB21, Terminals 1(+) & 2(-) Style Y (Class B), 4(+) & 5(-) Style Z (Class
A), 3 Shield (Standby and Alarm Polarity Shown) on main control board
Power-limited (Class 2) circuitry
Operation: Circuit can be wired Style Y (Class B) or Style Z (Class A)
Normal Operating Voltage: 25 VRMS @ 2 amps max. and maximum Load Impedance of 12.5Ω
(70.7 VRMS @ 700 mAmax. with maximum Load Impedance of 100Ω operation possible by plugging optional NFC-XRM-70V conver-
sion transformer into J12 of the main control board).
Output Power: 50 watts, standard; 100 watts with optional amplifier (100 watts total, maximum, allowed in standby for background
music)
Frequency Range: 800 - 2,800 Hz
Maximum total capacitance for each speaker circuit: 250 µF.
End-of-Line Resistor required for Style Y circuit: 15 KΩ, 1 watt (P/N: ELR-15K)
Command Input Circuits (alarm polarities shown)
• CMD1 - TB4 Terminals 3(+) & 4(-) are input terminals and Terminals 1(-) and 2(+) are output terminals which provide feed
through of the NAC circuits to NAC devices downstream; provides internal trouble relay rated at 3.0 amps maximum
• CMD2 - TB5 Terminals 3(+) & 4(-) are input terminals and Terminals 1(-) and 2(+) are output terminals which provide feed
through of the NAC circuits to NAC devices downstream
• CMD3 - TB6 Terminals 1(+) & 2(-) are input terminals for contact closure only
• CMD4 - TB6 Terminals 3(+) & 4(-) are input terminals for contact closure only
• CMD5 - TB7 Terminals 1(+) & 2(-) are input terminals for contact closure only
• CMD6 - TB7 Terminals 3(+) & 4(-) are input terminals for contact closure only
• CMD7 - TB8 Terminals 1(+) & 2(-) are input terminals for contact closure only
• CMD8 - TB8 Terminals 3(+) & 4(-) are input terminals for contact closure only
Power-limited (Class 2) and supervised circuitry
Normal Operating Voltage Range: 10.5 VDC - 29 VDC; Maximum Voltage: 29 VDC
NAC Reverse Polarity Current (requires End-of-Line Resistor from NAC): 1.6 mAmaximum.
Contact Closure Operation Current (requires 4.7K, ½ watt End-of-Line Resistor P/N 27072 only when messages have been assigned to
the command input): 6.6 mA maximum
Maximum Wiring Impedance CMD1 - CMD8 (Contact Closure Operation): 200Ω
Maximum Input Impedance:
• CMD1 & CMD2 (Reverse Polarity Operation): 20KΩ
• CMD1 - CMD8 (Contact Closure Operation): 4.75KΩ
Night Ring Input - TB16, Terminals 1 (+) & 2 (-)
Contact closure input
Isolated, nonsupervised
Operation current: 3.8 mA, maximum
Maximum wiring impedance: 30K Ω
Minimum isolation withstand voltage: 1500 VRMS
External Operator Interface Power Output - TB24, Terminals 1 (PWR, +) & 2 (GND, -)
Non-resettable power for external operator interface components
Power-limited (Class 2) circuitry, Supervised
Nominal operating voltage: 24 VDC
Maximum output current: 0.80 amps
Current limit: fuseless, electronic, power-limited circuitry
External Data Bus (EIA-485) - TB12, Terminals 2 (B), 3 (A), 4 (BRTN), 5 (ARTN), & 1 (SHLD)
Data connections for external operator interface components
Redundant transceiver circuitry for Class A operability
Power-limited (Class 2) circuitry, supervised
Maximum wiring impedance: 13.2 Ω
FACP Data Bus (EIA-485) - TB13, Terminals 1 (B IN), 2 (A IN), 3 (B OUT), & 4 (A OUT)
Dedicated connection to FACP serial bus
Output terminals: pass-through to other system components
Isolated, supervised
Minimum isolation withstand voltage: 1500 VRMS
Maximum wiring impedance: 40 Ω(ANN-BUS)/26 Ω(ACS BUS)

Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018 15
Input/Output Circuit Specifications Product Description
External Audio Riser TB22, Terminals 1 (OUT+), 2 (OUT-), 4 (IN+), 5 (IN-), & 3 (SHLD)
Style Y (Class B) or Style Z (Class A) audio connections to external operator interface components
Power-limited (Class 2) circuitry, supervised
Audio signal level: 3.85 VRMS, maximum
Frequency range: 800 - 2,800 Hz
Frequency range (NFC-50/125DA): 800 Hz - 2.8 KHz
Current Availability
The following figures illustrate the maximum current allowed for each output circuit in the panel and the total output current available
from the power supply. Refer to Section 6, “Power Supply Calculations” for additional current draw by option cards that must be consid-
ered when determining total standby and alarm currents.
NOTE: Zero impedance to ground will cause a ground fault.
TB20
TB21
TB19
TB24
TB23
TB17
Primary 50W
Speaker Circuit 50W max = 3.3
amps from supply
Secondary 50W
Speaker Circuit-
OptionalAmplifier
Installed
NAC Circuit 2.0 amps max.
Aux. Power 0.5 amp max.
Speaker Volume
Control Override 0.25 amp max.
ExternalOperator
Interface Power 0.8 amp max.
Alarm
7.5 amps
max.
Figure 1.1 Current Availability - 100 Watt System
TB20
TB21
TB24
TB17
50W max = 3.3
amps from supply
Primary 50W
Speaker Circuit
Secondary 50W
Speaker Circuit-
OptionalAmplifier
Installed
Aux. Power
ExternalOperator
Interface Power
combined 10W
max = 0.66 amps
from supply
0.5 amp max.
0.8 amp max.
Standby
2.0 amps max.
(includes
background music).

16 Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
Product Description Input/Output Circuit Specifications
1.2.2 Display Board
External Audio Input - TB5, Terminals 1(-), 2 (+)
Input Impedance: 8.5KΩ, nominal @ 1 KHz
Input Voltage: 700 mVRMS maximum
Input Current: 0.1 mA, maximum @ 700 mV
Background Music Input Voltage (Non-Canadian applications): 225mVRMS,maximum
1.2.3 NFC-CE6 Circuit Expander Module
Power-limited (Class 2) circuitry
Up to six (6) circuits on the NFC-CE6 can be wired as Style Y (Class B) or Style Z (Class A).
Normal Operating Voltage for Speaker Circuits: 25 VRMS @ 2 amps max. and maximum Load Impedance of 12.5Ω
(70.0 VRMS @ 700 mA max. with maximum Load Impedance of 100Ω operation possible for the primary circuit by plugging
optional NFC-XRM-70V conversion transformer into J12 of the main control board. The same operation is possible for the optional
50W amplifier by selecting the NFC-BDA-70V model.)
Speaker circuit wiring is supervised during standby, background music, and alarm.
Output Power: 50 watts total; Frequency Range: 800 - 2,800 Hz
Maximum total capacitance: 250 µF. (Note that the total capacitance for the speaker outputs must not exceed the maximum of 250 µF).
End-of-Line Resistor required for Style Y (Class B) speaker circuit: 15 KΩ, 1 watt (P/N: ELR-15K)
TB13 on the main control board: ACS/ANN (EIA-485) electrically isolated link to FACP provides programmed speaker control
TB20
TB19
TB17
TB23
TB24
TB20
TB17
TB24
Primary 50W
Speaker Circuit 10W max. = 0.66
amps from supply
NAC Circuit 2.0 amps max.
Aux. Power 0.5 amp max.
Speaker Volume
Control Override 0.25 amp max.
ExternalOperator
Interface Power 0.8 amp max.
Standby
2.0 amps max.
(includes
background
music).
Alarm
7.5 amps
max.
Figure 1.2 Current Availability - 50 Watt System
Primary 50W
Speaker Circuit 10W max. = 0.66
amps from supply
Aux. Power 0.5 amp max.
ExternalOperator
Interface Power 0.8 amp max.
NOTE: Some laptops/personal computers only provide an audio output for headphones. It may be necessary to adjust the headphone
output level for proper recording of voice messages.

Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018 17
Controls and Indicators Product Description
1.3 Controls and Indicators
1.3.1 Push-Button Controls
• All Call
• MNS Control
• System Control
• Speaker Select 1-24
• Message Select 1-8
• Diagnostic Select
• Trouble Silence
• Console Lamp Test
1.3.2 LED Indicators (visible with door closed)
• Fire System Active (green)
• MNS Control (green)
• System Control (green)
• System in Use (green)
• Speaker Zone 1-24 Active (green)
FIRE SYSTEM
ACTIVE
SYSTEM
CONTROL
ALL
CALL
1
2
3
4
5
6
7
8
9
10
11
12
13
18
19
20
21
22
23
24
16
17
14
15
ecckyd.wmf
Figure 1.3 NFC-50/100 Keypad
MNS
CONTROL
green green
yellow yellow
red
green
green
yellow
Note: Console
assignments are
shown here as an
example only.
SPEAKER
ZONE 1
SPEAKER
ZONE 2
SPEAKER
ZONE 3
SPEAKER
ZONE 4
SPEAKER
ZONE 5
SPEAKER
ZONE 6
SPEAKER
ZONE 7
SPEAKER
ZONE 8
SPEAKER
ZONE 9
SPEAKER
ZONE 10
SPEAKER
ZONE 11
SPEAKER
ZONE 12
SPEAKER
ZONE 13
SPEAKER
ZONE 14
SPEAKER
ZONE 15
SPEAKER
ZONE 16
SPEAKER
ZONE 17
SPEAKER
ZONE 18
SPEAKER
ZONE 19
SPEAKER
ZONE 20
SPEAKER
ZONE 21
SPEAKER
ZONE 22
SPEAKER
ZONE 23
SPEAKER
ZONE 24
MESSAGE 1
MESSAGE 2
MESSAGE 3
MESSAGE 4
MESSAGE 5
MESSAGE 6
MESSAGE 7
MESSAGE 8
OK TO PAGE
MICROPHONE
TROUBLE
DIST. AMP 1
DIST. AMP 2
DIST. AMP 3
DIST. AMP 4
DIST. AMP 5
DIST. AMP 6
DIST. AMP 7
DIST. AMP 8
DIAGNOSTIC
REMOTE AMPS TROUBLE SILENCE
AC POWER
GROUND FAULT
CHARGER FAULT
BATTERY FAULT
DATA BUS FAULT
NAC FAULT
NAC ACTIVE
SYSTEM TROUBLE
AUDIO RISER FAULT
LOC 1
LOC 2
RPU 1
RPU 2
RPU 3
RM 1
RM 2
RM 3
CONSOLE LAMP TEST
MAIN CONSOLE

18 Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
Product Description Components
• Speaker Zone 1-24 Fault (yellow)
• OK to Page (green)
• Microphone Trouble (yellow)
• Message 1-8 Active (red)
• Message 1-8 Fault (yellow)
• Remote Amplifier 1-8 Fault (yellow)
• LOC/RPU/RM 1-8 Fault (yellow)
• LOC/RPU/RM 1-8 Active (green)
• Main Console Fault (yellow)
• AC Power (green)
• Ground Fault (yellow)
• Charger Fault (yellow)
• Battery Fault (yellow)
• Data Bus Fault (yellow)
• NAC Fault (yellow)
• NAC Active (green)
• System Trouble (yellow)
• Audio Riser Fault (yellow)
1.3.3 LED Indicators (visible with door and dress panel open)
• MCB Trouble (yellow)
– Integral 50W amplifier electronics fault
• Option Card Trouble (yellow)
– NFC-CE6 card missing
– NFC-BDA-25/70V card missing
– NFC-BDA-25/70V electronics fault
• Amplifier Over Current Fault (yellow)
– Missing or incorrect EOL resistor
– Short circuit on volume control module
1.4 Components
Main Control Board
The NFC-50/100 main control board contains the system's CPU, power supply, battery charger, other primary components and wiring
interface components. One 50W amplifier is integrated into the main control board.
Display Board
The display board contains the user interface along with tone generators, digital message recorder/generator, integral microphone input,
and preamplifier.

Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018 19
Components Product Description
Cabinet
The cabinet is black with an attractive grey front overlay. A clear window allows viewing of the display board, status LEDs and location
of microphone. The backbox measures 16.65" x 19.0" x 5.2" D (42.29cm x 48.26cm x 13.23cm) and provides space for two 12AH or
two 18AH batteries.
Batteries
The cabinet provides space for up to 18 Amp Hour batteries (charged by integral Power Supply/Battery Charger) with all options
installed.
Dress Panel
The Dress Panel is supplied standard with the system. It mounts to the cabinet with two supplied screws. The Dress Panel protects the
user from high voltages and circuit boards from accidental damage.
Trim Ring
An optional TR-CE-B trim ring is available for semi-flush mounting of the audio panel.
Figure 1.4 Cabinet
nfcfront.wmf
Figure 1.5 Dress Panel
ecc_dp.wmf

20 Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
Product Description Optional Equipment
1.5 Optional Equipment
NFC-BDA-25/70V Audio Amplifier Modules
An optional second audio amplifier can be plugged into connectors J10 & J11 located in the upper right of the main control board in the
NFC-50/100. This amplifier also provides 50 watts of power at 25 VRMS or 70 VRMS, depending on the model, and can therefore be used
to expand system power to 100 watts (providing dual 50 watt speaker circuits) or it can be used as a backup amplifier. The output is
power-limited (Class 2) and speaker circuit connections to it are provided on the main control board and optional speaker circuit
expander module. The circuit can be wired for Style Y (Class B) or Style Z (Class A) operation.
LEDs are provided to indicate Amplifier Supervision (green indicates amplifier is functional) and CircuitTrouble (yellow indicates field
wiring fault or amplifier fault). The LEDs are only visible with the panel door open.
NFC-CE6 Circuit Expander Module
This optional module plugs into connector P1 in the upper middle of the main control board. The NFC-CE6 adds three primary speaker
circuits to the NFC-50/100. The NFC-CE6 adds three secondary circuits to the system when the NFC-BDA-25/70VAudio Amplifier
Module is also installed.
NFC-XRM-70V Transformer 70.7 VRMS
This optional module plugs into connector J12 of the main control board and provides conversion for the integral audio amplifier from
25 VRMS to 70.7 VRMS at full rated 50 watts output power.
NFC-FFT Fire Fighter Telephone
The NFC-FFT has a telephone handset and user interface that allows an operator to communicate with remotely located telephone hand-
sets in a building. It is housed in its own cabinet with key lock. It requires an external operator interface power connection (24 volts DC)
from the NFC-50/100 main console or it may be powered from an external 24 VDC power supply such as HP300ULX. The NFC-FFT
provides supervision, annunciation, and control for the local handset and for up to 24 remote telephone handsets. It provides indications
of phone activation and corresponding trouble conditions. Refer to the NFC-FFT Fire Fighter Telephone manual. Not for use in UL2572
Mass Notification or Canadian applications.
NFC-50DA Distributed (Remote) Audio
The NFC-50DA is a 50-watt audio amplifier (audio booster) with its own cabinet and key lock. It requires an external data bus connec-
tion and an external audio riser connection from the NFC-50/100 main console. The unit comes standard with 4 speaker circuits. An
option card, NFC-CE4, provides 4 more speaker circuits for a total of 8. Speaker circuits are activated/de-activated manually or automat-
ically by the NFC-50/100 main console. The unit is capable of either 25 VRMS or 70.7 VRMS operation. Refer to the NFC-50/125DA Dis-
tributed Audio manual. Not for use in Canadian applications.
NFC-125DA Distributed (Remote) Audio
The NFC-125DA is a 125-watt audio amplifier (audio booster) with its own cabinet and key lock. It requires an external data bus con-
nection and an external audio riser connection from the NFC-50/100 main console. The unit comes standard with four (4) speaker cir-
cuits. An option card, NFC-CE4, provides 4 more speaker circuits for a total of eight (8). Speaker circuits are activated/de-activated
manually or automatically by the NFC-50/100 main console. The unit is capable of 25 VRMS operation. Refer to the NFC-50/125DA
Distributed Audio manual. Not for use in Canadian applications.
NFC-50/100DA Distributed (Remote) Audio
The NFC-50/100DA is a 50/100-watt audio amplifier (audio booster) with its own cabinet and key lock. It requires an external data bus
connection and an external audio riser connection from the NFC-50/100 main console. The NFC-50/100DAis capable of producing up
to 100 watts of audio power. The amplifier functions as 50 watts with 50 watts as backup, 100 watts with no backup or 100 watts with 50
watts backup using NFC-BDA-BU. The unit comes standard with 8 speaker circuits. Speaker circuits are activated/de-activated manu-
ally or automatically by the NFC-50/100 main console. The unit is capable of either 25 VRMS or 70.7 VRMS operation. Refer to the NFC
Distributed Audio manual. Not for use in Canadian applications.
NFC-RM Remote Microphone
The NFC-RM has a hand held microphone and is housed in its own cabinet with keyed lock. It requires an external data bus connection,
an external audio riser connection, and an external operator interface power connection (24 volts DC) from the NFC-50/100 main con-
sole. ALL CALL paging can be broadcast over the speaker circuits by depressing the microphone's push-to-talk switch. Not for use in
UL2572 Mass Notification or Canadian applications.
NFC-RPU Remote Page Unit
The NFC-RPU has a hand held microphone and 8 message buttons. It is housed in its own cabinet with a keyed lock or thumb lock
(requires AHJ approval). It also has a 9th button that will activate a monitor module mounted inside the cabinet. This may be used for
HVAC shutdown applications when the monitor module is connected to the FACP SLC polling loop. The remote page unit requires an
external data bus connection, an external audio riser connection, and an external operator interface power connection (24 volts DC) from
the NFC-50/100 main console. ALL CALL paging can be broadcast over the speaker circuits by depressing the microphone's push-to-
NOTE: Any combination of up to eight audio boosters comprised of NFC-50DA, NFC-125DA, and NFC-50/100DA can be used in the
system. Their external data bus addresses must be unique and must be sequential. Addresses are set via dipswitches on each unit's PC
board. Refer to Section 2.14 on page 48.
This manual suits for next models
4
Table of contents
Other Honeywell Emergency Phone manuals