JADE™ ECONOMIZER MODULE
63-2700—05 2
SPECIFICATIONS
W7220A Economizer Module
The module is designed for use with any Honeywell 2 to 10
Vdc or Honeywell Sylkbus communicating actuator. The
module includes terminals for a CO2sensor, Mixed Air sensor,
and an Outdoor Dry Bulb sensor. Enthalpy and other options
are available with Sylk Bus sensors.
User Interface: Provides status for normal operation, setup
parameters, checkout tests, and alarms and error
conditions with a 2-line 16 character LCD display and a four
button keypad.
Electrical
Rated Voltage: 20 to 30 Vac RMS; 50/60 Hz
Transformer: 100 VA maximum system input
Nominal Power Consumption (at 24 Vac, 60 Hz): 11.5 VA
without sensors and actuator
Relay Digital Output Rating at 30 Vac (maximum power
from Class 2 input only): 1.5A run;
3.5A inrush @ 0.45PF (200,000 cycles) or
7.5A inrush @ 0.45PF (100,000 cycles)
External Sensors Power Output: 21 Vdc +/- 5% @ 48mA
IMPORTANT
All inputs and outputs must be Class 2 wiring.
Inputs
SENSORS:
NOTE: A Mixed air (MA) analog sensor is required on all
W7220 units; either an Outdoor Air (OA) sensor
for dry bulb change over or an OA Sylkbus sensor
for outdoor enthalpy change over is required in
addition to the MA sensor. An additional Return
Air (RA) Sylkbus sensor can be added to the
system for differential enthalpy or dry bulb
changeover. For differential dry bulb changeover
a 20k ohm sensor is required in the OA and a
Sylkbus sensor in the RA. Dip switch on RA
Sylkbus sensor must be set in the RA position.
Dry Bulb Temperature and Mixed Air, C7250A:
2-wire (18 to 22 AWG);
Temperature range -40 to 150 °F (-40 to 65 °C).
Temperature and Humidity, C7400S1000 (optional):
Sylk Bus; 2-wire (18 to 22 AWG)
Temperature: range -40 to 150 °F (-40 to 65 °C)
Humidity: range 0 to 100% RH with 5% accuracy.
NOTE: Up to three (3) SYLK Bus sensors may be
connected to the JADE™ Economizer module.
For outdoor air (OA), return air (RA) and
discharge (supply) air (DA).
DCV (CO2) Sensor (C7232):
2-10 Vdc control signal; minimum impedance >50k ohm.
4 Binary inputs:
1-wire 24 Vac + common GND (see page 5 for wiring
details). 24 Vac power supply: 20 to 30 Vac 50/60Hz;
100 VA Class 2 transformer.
Outputs
Actuator signal: 2-10 Vdc; minimum actuator impedance is
2k ohm; Sylkbus two-wire output for Honeywell Sylkbus
communicating actuators.
Exhaust fan, Y1, Y2 and AUX1 O:
All Relay Outputs (at 30 Vac):
Running: 1.5A maximum
Inrush: 7.5A maximum
Environmental
Operating Temperature: -40 to 150 °F (-40 to 65 °C).
Exception of display operation down to -4 °F with full
recovery at -4 °F from exposure to -40 °F
Storage Temperature: -40 to 150 °F (-40 to 65 °C)
Shipping Temperature: -40 to 150 °F (-40 to 65 °C)
Relative Humidity: 5% to 95% RH non-condensing
Dimensions (See Fig. 1 on page 2):
Height: 4.98 inches (126.4 mm)
Width: 6.3 inches (160 mm)
Depth: 1.34 inches (34 mm)
Weight: 0.58 lb. (0.265 kg)
Approvals: UL listed (XAPX) for USA and Canada.
Fig. 1. Dimensions in inches (mm) showing mounting
holes.
Accessories
— 50048926-001 2-pin edge connector for sensors (20
pieces per bag)
— 50048926-002 6-pin edge connector for field wiring (20
pieces per bag)
— C7250A 20k sensor for MA or OA (dry bulb changeover)
— C7400S Sylkbus sensor for enthalpy control in OA and/
or RA and RA for differential dry bulb changeover
— W7220 PCMOD interface tool for JADE controller and
Personal Computer. Go to www.customer.honey-
well.com/economizertools for the software
— 50053060-001 Duct mounting kit for sensors
4-63/64
(126)
6-19/64 (160)
MOUNTING HOLE (X2)
M32273A
3-5/32 (80)