manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Industrial Equipment
  8. •
  9. Honeywell RRD User manual

Honeywell RRD User manual

RETROFIT ROUND DAMPER (RRD)
369-1960
INSTALLATION
Before Installing this Product
1. Read all instructions before installing this product. Fail-
ure to follow instructions can damage the product or
cause a hazardous condition.
2. Check the ratings given in the instructions and on the
product to verify that the product is suitable for your
application.
3. Installer must be a trained and experienced service tech-
nician.
4. Install the product in an area that is easily accessible for
checkout and service.
5. After completing installation, use these instructions to
check out product operation.
Installing the Retrofit Round Damper
Select a location for the damper in the ductwork. It is
suggested that the RRD damper be at least 6 feet from the
register for quiet operation.
1.
Peel off the back of the cut-out template. Carefully align
the template with the centerline of the duct. Apply tem-
plate to the section of round ductwork where the damper
is to be installed. Ensure that the template is parallel to
the ductwork. It is suggested that the damper be installed
with the motor under a horizontal duct to reduce twist to
the duct. It may also be necessary to support the duct.
2. Drill a starter hole in the cut-out area of the template.
3. Cut out the area between the holes.
4. Slide the damper into the duct and secure it with the four
supplied self-drilling mounting screws. Be careful to
avoid over-tightening the screws as the duct may be
pulled out of round. See Fig. 3.
Fig. 3. Inserting RRD damper into duct.
WIRING
Wiring the Motor Actuator
Connect the motor to the zone control panel 18 or 20 gauge
wire. The motor terminals are labeled M1 for common, M6 for
closed, and M4 for open. Connect the motor terminals to
corresponding terminals on zone control panel for each zone.
See Fig. 4–6 for hookups.
Multiple RRD dampers can be wired to one zone when wired in
parallel. See Fig. 5 for wiring multiple dampers together in a
daisy chain manner or Fig. 6 using wire nuts. See Table 1 for
the maximum number of dampers that can be connected to
each zone control panel. Note that this is the total number of
dampers connected to all the zones of a zone control panel;
the maximum dampers per zone is 14. If more than 14
dampers are on one zone, a Slave Damper Control Relay
(SDCR) must be used.
When more than the maximum number of dampers allowed
per panel are necessary, a SDCR must be used. The SDCR is
an isolation relay that is powered by a separate transformer so
that it relieves the panel of this additional load. When a SDCR
is used, the dampers of that zone may either be all connected
to the SDCR, or some dampers may be wired to the SDCR and
the remainder to that zone’s damper terminals.
Fig. 4. RRD wired to zone control panel.
Fig. 5. Wiring multiple RRD dampers in daisy chain
fashion.
M23404
Table 1. Maximum number of dampers per zone.
One 40 VA
Transformer Two 40 VA Transformers
(or One 75 VA)
Emm-3 12 N/A
Emm-3u 12 N/A
Tz-4 11 25 (max 14 per zone)
W8835 12 26 (max 14 per zone)
SDCR 15 28
RYWGCM6M4M1
RYWG
ZONE
1, 2, 3, ETC.
M1
M6
M4
M23405
ZONE
THERMOSTAT
RYWGCM6M4M1
RYWG
ZONE
1, 2, 3, ETC.
M1
M6
M4
M1
M6
M4
M23407
ZONE
THERMOSTAT
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9
customer.honeywell.com
RETROFIT ROUND DAMPER (RRD)
® U.S. Registered Trademark
© 2006 Honeywell International Inc.
69-1960 M.S. 06-06
Fig. 6. Wiring multiple RRD dampers using wire nuts.
ADJUSTMENTS
Manual Blade Adjustment
To verify correct range of motion, depress the manual blade
adjustment button. While this is pressed, the gears are
disengaged, allowing the blade to be manually opened or
closed by turning the damper blade shaft. See Fig. 1.
Position Indicator
The position indicator points toward the position of the damper
blade to identify if the blade is open, closed, or at an
intermediate position. A slot at the end of the damper blade
shaft also indicates blade position.
Range stops
The RRD damper motor can be adjusted to prevent complete
closure of the blade. This is useful in zone systems where it is
not possible to install a bypass damper.
To set the range stop to prevent complete closure:
1. Locate the range stop adjustment screw on the top of
the motor to the right blade shaft. This is at the extreme
counter-clockwise end of travel.
2. Using a small Phillips head screwdriver, loosen the set
screw.
3. Move the end-stop block to the new position
4. Secure the set screw.
5. Verify the new range of motion while depressing the
manual blade release button.
CHECKOUT
CAUTION
Possible Equipment Damage
Do not manually open or close the damper unless the
manual blade release button is depressed
To check out the RRD damper using 24 VAC transformer:
1. Connect 24 VAC common to the M1 (common) terminal
on the actuator.
2. Connect 24 VAC hot to the M6 terminal to close the
damper.
3. Observe the blade move clockwise and stop in the
closed position.
4. Remove the 24 VAC hot wire from the M6 terminal.
5. Connect the 24 VAC hot wire to the M4 terminal.
6. Observe the blade move counter-clockwise and stop in
the open position.
7. This verifies correct operation.
To check out the RRD damper when connected to a zone
control panel. (This assumes that the damper has been wired
correctly as shown in Fig. 4.)
1. Begin with all zone thermostats set so that they are not
calling for heat, cool, or fan.
2. To test the damper on zone 1, set the thermostat on
zone 2 to the fan “On” mode so that it calls for fan.
3. This will make the damper on zone 1 close
4. Observe damper one closing on its position indicator.
The damper will take 90 seconds to close.
5. Set zone 2 thermostat to the fan “Auto” mode so that it
is no longer calling for fan. The zone 1 damper will now
return to the open position. This completes the test of
the zone 1 damper.
6. To test the damper on zone 2, set that thermostat on
zone 1 to the fan “On” mode so that it calls for fan.
7. Observe the damper on zone 2 close.
8.
Also observe that zone 3 or others, if connected, also
close when the zone 1 thermostat is in the fan “On” mode.
9. When complete, set the zone 1 thermostat to the fan
“Auto” mode. All zones will now return to the open
position.
10. This verifies correct damper wiring and operation.
TROUBLESHOOTING
RYWGCM6M4M1
RYWG
ZONE
1, 2, 3, ETC.
M1
M6
M4
M1
M6
M4
M23410
ZONE
THERMOSTAT WIRE NUT
Damper operates backwards Verify correct damper wiring as shown in Fig. 4–6.
Damper does not operate 1. Verify damper wiring using checkout methods listed in this document.
2. Verify that the duct is round and not making the blade stick. Depress the
manual blade release button and manually turn the blade shaft to verify
smooth opening and closing operation.

Other Honeywell Industrial Equipment manuals

Honeywell Q3400A User manual

Honeywell

Honeywell Q3400A User manual

Honeywell Enraf 1010 CB Owner's manual

Honeywell

Honeywell Enraf 1010 CB Owner's manual

Honeywell Gent Vigilon Plus User manual

Honeywell

Honeywell Gent Vigilon Plus User manual

Honeywell PATROL 1b User manual

Honeywell

Honeywell PATROL 1b User manual

Honeywell MILLER 81004170 Operator's manual

Honeywell

Honeywell MILLER 81004170 Operator's manual

Honeywell TA3840 User manual

Honeywell

Honeywell TA3840 User manual

Honeywell Modutrol IV 41 Series User manual

Honeywell

Honeywell Modutrol IV 41 Series User manual

Honeywell NOTIFIER NBG-12WL User manual

Honeywell

Honeywell NOTIFIER NBG-12WL User manual

Honeywell NOTIFIER NBG-12WLA User manual

Honeywell

Honeywell NOTIFIER NBG-12WLA User manual

Honeywell Farenhyt Series Technical manual

Honeywell

Honeywell Farenhyt Series Technical manual

Honeywell GENT COMPACT-MAINS-DAU Training manual

Honeywell

Honeywell GENT COMPACT-MAINS-DAU Training manual

Honeywell F-BO-AFE70 Series Guide

Honeywell

Honeywell F-BO-AFE70 Series Guide

Honeywell Industrial HERMetic Sampler GTX Chem Operation manual

Honeywell

Honeywell Industrial HERMetic Sampler GTX Chem Operation manual

Honeywell BA300 Series Installation instructions

Honeywell

Honeywell BA300 Series Installation instructions

Honeywell VR9105V User manual

Honeywell

Honeywell VR9105V User manual

Honeywell Q3300 User manual

Honeywell

Honeywell Q3300 User manual

Honeywell JADE W7220 User manual

Honeywell

Honeywell JADE W7220 User manual

Honeywell MS-9200UDLS User manual

Honeywell

Honeywell MS-9200UDLS User manual

Honeywell R8991 User manual

Honeywell

Honeywell R8991 User manual

Honeywell HS-700 Operating and installation instructions

Honeywell

Honeywell HS-700 Operating and installation instructions

Honeywell HON 512 Operating instructions

Honeywell

Honeywell HON 512 Operating instructions

Honeywell COMBISAFE User manual

Honeywell

Honeywell COMBISAFE User manual

Honeywell HERMetic Operation manual

Honeywell

Honeywell HERMetic Operation manual

Honeywell MICRO SWITCH GLL Series User manual

Honeywell

Honeywell MICRO SWITCH GLL Series User manual

Popular Industrial Equipment manuals by other brands

PREVOST PPS Technical documentation

PREVOST

PREVOST PPS Technical documentation

ABB HT608934 Operation manual

ABB

ABB HT608934 Operation manual

Zimmer PowerStop PHE16X10LSAK-A Installation and operating instructions

Zimmer

Zimmer PowerStop PHE16X10LSAK-A Installation and operating instructions

ABB HT569949 Operation manual

ABB

ABB HT569949 Operation manual

Dynaset HEU 320-40E manual

Dynaset

Dynaset HEU 320-40E manual

ZWAE ONIII Assembly manual

ZWAE

ZWAE ONIII Assembly manual

Axminster Trade AT50LP Ultimate Edge Original instructions

Axminster Trade

Axminster Trade AT50LP Ultimate Edge Original instructions

Makita M3602 instruction manual

Makita

Makita M3602 instruction manual

ABB HT608609 Operation manual

ABB

ABB HT608609 Operation manual

ABB Relion RER615 manual

ABB

ABB Relion RER615 manual

Siemens SIMATIC ET 200SP HA Equipment manual

Siemens

Siemens SIMATIC ET 200SP HA Equipment manual

flamco Logotherm LogoComfort 500 Installation and servicing instruction

flamco

flamco Logotherm LogoComfort 500 Installation and servicing instruction

Vestil VST-4-Y Use and maintenance instructions

Vestil

Vestil VST-4-Y Use and maintenance instructions

Graco Therm-O-Flow 20 Instructions - parts

Graco

Graco Therm-O-Flow 20 Instructions - parts

JST CMK-R Operation manual

JST

JST CMK-R Operation manual

ALENCON SPOT BOX v2 user manual

ALENCON

ALENCON SPOT BOX v2 user manual

Eaton NZM4-XU Series Instruction leaflet

Eaton

Eaton NZM4-XU Series Instruction leaflet

Master MB Bucker 500 Instructions for use and maintenance

Master

Master MB Bucker 500 Instructions for use and maintenance

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.