manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Measuring Instrument
  8. •
  9. Honeywell Touchpoint Plus User manual

Honeywell Touchpoint Plus User manual

Other manuals for Touchpoint Plus

9

Other Honeywell Measuring Instrument manuals

Honeywell Sensepoint XCD RTD User manual

Honeywell

Honeywell Sensepoint XCD RTD User manual

Honeywell 854 ATG Series User manual

Honeywell

Honeywell 854 ATG Series User manual

Honeywell AD1200-CT User manual

Honeywell

Honeywell AD1200-CT User manual

Honeywell BendixKing KN 62A User manual

Honeywell

Honeywell BendixKing KN 62A User manual

Honeywell QX User manual

Honeywell

Honeywell QX User manual

Honeywell BW RigRat User manual

Honeywell

Honeywell BW RigRat User manual

Honeywell Limitless WPMM Series User manual

Honeywell

Honeywell Limitless WPMM Series User manual

Honeywell GENT S4-34 Series Instruction manual

Honeywell

Honeywell GENT S4-34 Series Instruction manual

Honeywell LeaderLine DPR 100 C User manual

Honeywell

Honeywell LeaderLine DPR 100 C User manual

Honeywell DR Graphic User manual

Honeywell

Honeywell DR Graphic User manual

Honeywell Minitrend QX User manual

Honeywell

Honeywell Minitrend QX User manual

Honeywell FlexLine SmartServo 954 User manual

Honeywell

Honeywell FlexLine SmartServo 954 User manual

Honeywell KA 54 User manual

Honeywell

Honeywell KA 54 User manual

Honeywell Enraf FlexLine RMA805 Instruction Manual

Honeywell

Honeywell Enraf FlexLine RMA805 Instruction Manual

Honeywell FS24X Plus User manual

Honeywell

Honeywell FS24X Plus User manual

Honeywell W8710A User manual

Honeywell

Honeywell W8710A User manual

Honeywell OELD User manual

Honeywell

Honeywell OELD User manual

Honeywell Q209E Modutrol IV User manual

Honeywell

Honeywell Q209E Modutrol IV User manual

Honeywell SmartLine SLG 700 User manual

Honeywell

Honeywell SmartLine SLG 700 User manual

Honeywell Q4000 User manual

Honeywell

Honeywell Q4000 User manual

Honeywell TS34C User manual

Honeywell

Honeywell TS34C User manual

Honeywell ACM 150 Owner's manual

Honeywell

Honeywell ACM 150 Owner's manual

Honeywell RAE Systems NeutronRAE II User manual

Honeywell

Honeywell RAE Systems NeutronRAE II User manual

Honeywell HomMed Genesis Touch User manual

Honeywell

Honeywell HomMed Genesis Touch User manual

Popular Measuring Instrument manuals by other brands

Suaoki D40 user manual

Suaoki

Suaoki D40 user manual

Elster BK-G1.6 operating instructions

Elster

Elster BK-G1.6 operating instructions

Endress+Hauser Deltabar FMD71 technical information

Endress+Hauser

Endress+Hauser Deltabar FMD71 technical information

Duratool D03128 manual

Duratool

Duratool D03128 manual

Vega VEGAPULS 65 Quick setup guide

Vega

Vega VEGAPULS 65 Quick setup guide

Tonghui TH2618B Operation manual

Tonghui

Tonghui TH2618B Operation manual

Tenmars TM-801 user manual

Tenmars

Tenmars TM-801 user manual

MSR 145 user manual

MSR

MSR 145 user manual

TPS WP-82 manual

TPS

TPS WP-82 manual

PCB Piezotronics 003C30 Installation and operating manual

PCB Piezotronics

PCB Piezotronics 003C30 Installation and operating manual

Tenma 72-10465 manual

Tenma

Tenma 72-10465 manual

Endress+Hauser Proline Promag 50 Brief operating instructions

Endress+Hauser

Endress+Hauser Proline Promag 50 Brief operating instructions

Siemens SITRANS F Coriolis FCT030 Function manual

Siemens

Siemens SITRANS F Coriolis FCT030 Function manual

KLINGER CMF V Series instruction manual

KLINGER

KLINGER CMF V Series instruction manual

Keysight M8290A Getting started guide

Keysight

Keysight M8290A Getting started guide

Acterna MS1400 Operation manual

Acterna

Acterna MS1400 Operation manual

R&S ZPH manual

R&S

R&S ZPH manual

Datacolor ColorReader DC10-2 user guide

Datacolor

Datacolor ColorReader DC10-2 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

1 Information
Please read this entire guide before installing the Touchpoint
Plus, as it contains information that is essential for your safety
and for the correct operation of the Touchpoint Plus.
1.1 Safety
Incorrect setup, maintenance, operation or modification of the
Touchpoint Plus gas detection system or its installation may
constitute a serious hazard to the health and safety of
personnel and their environment. It is therefore imperative that
the contents of this chapter are thoroughly understood by
everyone who has access to the gas and fire detection system
or its associated equipment.
1.2 Conditions of Use
This Touchpoint Plus equipment should only be operated
under the following circumstances:
By properly trained personnel.
Under approved conditions.
With due authorisation.
Using approved maintenance and servicing procedures.
1.3 Packaging list
Please check that your package was undamaged, and that you
have received the following:
Touchpoint Plus
Allen Key
Quick start guide (This document)
Please go to www.honeywellanalytics.com to download the
Technical Handbook, which contains full install instructions.
2 General Introduction
The Touchpoint Plus is an entry level (or upgrade) touch-
screen digital controller for light industrial and commercial gas
detection installations.
It has eight inputs, with a further eight inputs available through
an expansion box.
It can handle a wide range of milliamp, millivolt and catalytic
sensors and analogue inputs, and it can control various outputs
such as audible and visible signals and solenoid valves.
The cabinets are constructed from high–impact plastic, are
rated IP65, and have fully-sealed, easy opening access. They
are supplied with a wall mount bracket or can be directly
mounted to any solid vertical surface or rack. Cable entry is via
entry glands on the lower side.
Figure 1 shows the basic layout of the Touchpoint Plus
Controller:
Figure 1. Basic System Layout
3 Installation
3.1 To Mount the Unit Directly to the Wall
Figure 2. Wall Mounting Points
3.1.1 Fixings Required
Screw x 4; corrosion resistant, sized according to the fixing
surface:
Screw Head dia. < 14 mm (12.1 mm recommended)
Screw Body dia. < 7.5 mm (6.15 mm recommended)
Screw Length > 76.2 mm (3 in) (If using concrete anchor,
> 55 mm + anchor depth)
Flat Washer x 4; corrosion resistant, 19.05 mm max. OD, to fit
the screws above.
3.2 To Mount the Unit Using the Optional
Wall Bracket
Figure 3. Wall Mounting Options
Please refer to the wall mount bracket instructions (part
number: TPPLOWMB).
4 Wiring and Connections
4.1 Power Connection
The Touchpoint Plus systems are factory set to operate at a
switchable voltage of 110/220 VAC, on a single phase, 50 to
60 Hz supply. They can also be wired to DC 18 — 32 V.
Every Unit has a typical peak power consumption of less than
105W, and must be directly connected to supplies via a Main
Isolator Switch that leaves protective earth (ground)
permanently connected.
The circuit should incorporate a Residual Current Device or
Residual Current Circuit Breaker (RCD or RCCB).
Touchpoint Plus systems are not certified for connection to
domestic power supplies.
4.2 Expansion Power Module
TPPL has the option to add an expansion unit that has
the same power equipment and modules as the base
unit except that it has no Motherboard or GUI. See
Figure 5 for wiring details.
4.3 AC Power Supply
To confirm or alter the pre-set operating voltage, open the
system front cover, locate the SMPS RS–150–24 transformer
and, if required, change the voltage selector inserting a
screwdriver at the point shown by the Voltage Selector label
below:
Figure 4. Switched Mode Power Supply (SMPS) Connections
Note: Mains Earth (Ground) must only be connected to the
Protective Earth (Ground) rail, and not to the SMPS.
Regional power cable wires are coloured in accordance with
the following code:
Wire Europe Canada USA Asia
Protective Earth
(Ground) Green + Yellow Green Green Green
Isolated Earth
(Ground) — Green Green + Yellow —
Neutral Blue White White Black
Live Brown Red or Black Blue, Red, or
Black Red, Yellow, or
Blue
Table 1. Regional Power Cable Colours
Before making any electrical connections or changes ensure:
The mains supply isolator switch and backup battery
switch are in the Off position.
The system is set up to operate at the correct voltage.
Refer to the User Manual for further information on system
electrical specifications and power requirements.
Note 1: Input voltage of less than 24 VDC will fail to charge the
backup battery, and the battery will discharge over time.
Note 2: Remote sensors may need their own power supplies if
they exceed 15W power consumption.
Figure 5. Mains Power Supplies
4.4 DC Power Supply
It is possible to power the Touchpoint Plus controller directly
from a DC 24V supply without using AC supplies at all.
However, batteries alone will not suffice as they must not drop
below 22 volts.
Note: The system must still be connected to Protective Earth
(Ground) when using an external DC supply.
Figure 6. DC 24 V Input Terminals
4.5 Field Device Cables
Field Device cabling (sensors, lights, solenoids, etc.) should be
appropriate to the zone classification, and in accordance with
the device manufacturer’s recommendations. Refer to local and
national regulations where appropriate, and to the device user
manual.
All sensor field cables must be screened and earthed
(grounded) in order to:
Ensure correct operation of the system
Avoid spurious signals
Meet European Standards for RFI and EMC.
Ensure that the maximum loop resistance is not exceeded, as
specified by the device manufacturer.
Take account of voltage drops due to line resistance to ensure
that the correct voltage level is present at the field device, as
specified by the device manufacturer.
The I/O modules will accept wire sizes to a maximum of 2.5
mm².
4.6 Main Module Connections
The Main Module controls the Touchpoint Plus and its ancillary
components.
Terminal Label Channel Remarks
1 +DC
Power
+18 – 32 V
2 –DC -V Return
3 — Earth / Ground
4 NC
System State
Relay 1
Fig. 9
5 COM Fig. 9
6 NO Fig. 9
7 NC
System State
Relay 2
Fig. 9
8 COM Fig. 9
9 NO Fig. 9
10 NC
System State
Relay 3
Fig. 9
11 COM Fig. 9
12 NO Fig. 9
13 +24 VDC
Visual Output
Fig. 4
14 VIS Fig. 4
15 Unused —
16 A1
External Alarms
Fig. 4
17 A2 Fig. 4
18 F Fig. 4
19 +24 VDC
External Alarm
Power
Fig. 4
20 +24 VDC Fig. 4
21 +24 VDC Fig. 4
22 3.3 V
Remote
COM/Reset/Inhibit
Fig. 10
23 R1 Fig. 10
24 R2 Fig. 10
25 CAN_H
CAN
Expansion Unit
Connection
26 CAN_L Expansion Unit
Connection
Table 2. Main Module Connections
Touchpoint Plus
Quick Start Guide
English
Basic Unit Expansion Unit
Isolator Switch
4.7 mA Input Module Connections
This is an optional module for providing up to eight mA loop
inputs. (Ch.4.13)
Terminal Label Input Field Device
1 +Ve
mA input 1
+ 24 VDC
2 –Ve 0 VDC
3 Sig 4 – 20 mA signal
4 +Ve
mA input 2
+ 24 VDC
5 –Ve 0 VDC
6 Sig 4 – 20 mA signal
7 +Ve
mA input 3
+ 24 VDC
8 –Ve 0 VDC
9 Sig 4 – 20 mA signal
10 +Ve
mA input 4
+ 24 VDC
11 –Ve 0 VDC
12 Sig 4 – 20 mA signal
13 +Ve
mA input 5
+ 24 VDC
14 –Ve 0 VDC
15 Sig 4 – 20 mA signal
16 +Ve
mA input 6
+ 24 VDC
17 –Ve 0 VDC
18 Sig 4 – 20 mA signal
19 +Ve
mA input 7
+ 24 VDC
20 –Ve 0 VDC
21 Sig 4 – 20 mA signal
22 +Ve
mA input 8
+ 24 VDC
23 –Ve 0 VDC
24 Sig 4 – 20 mA signal
Table 3. mA Input Module Connections
4.8 mV Input Module Connections
This is an optional module for mV CAT sensor inputs. (Ch.4.13)
Terminal Label Input Field Device
1 S
mV input 1
Sensitive (+)
2 01 Signal
3 NS Sensitive (–)
4 S
mV input 2
Sensitive (+)
5 01 Signal
6 NS Sensitive (–)
7 S
mV input 3
Sensitive (+)
8 01 Signal
9 NS Sensitive (–)
10 S
mV input 4
Sensitive (+)
11 01 Signal
12 NS Sensitive (–)
13 S
mV input 5
Sensitive (+)
14 01 Signal
15 NS Sensitive (–)
16 S
mV input 6
Sensitive (+)
17 01 Signal
18 NS Sensitive (–)
19 S
mV input 7
Sensitive (+)
20 01 Signal
21 NS Sensitive (–)
22 S
mV input 8
Sensitive (+)
23 01 Signal
24 NS Sensitive (–)
Table 4. mV Input Module Connections
4.9 Dual Input Module
This is an optional module for providing 2 or 4 x mA Loop + 2
or 4 x mV CAT inputs.
Terminal Label Input Field Device
1, 7, 4, 10 +Ve
mA Inputs 1 – 4
+ 24 VDC
2, 5, 8, 11 –Ve 0 VDC
3, 6, 9, 12 Sig 4 – 20 mA signal
13, 16, 19, 22 S
mV Inputs 1 – 4
Sensitive (+)
14, 17, 20, 23 01 Signal
15, 18, 21, 24 NS Sensitive (–)
4.10 Modbus RTU Option
This is an option that uses Modbus RTU (RS-485) control
protocols. Full details are given in the Technical Handbook.
4.11 Relay Output Module Connections
This is an optional module providing 12 relay outputs.
(Ch.4.13)
Terminal Label Output
1 NC
Relay 12 COM
3 NO
4 NC
Relay 25 COM
6 NO
7 NC
Relay 38 COM
9 NO
10 NC
Relay 411 COM
12 NO
13 NC
Relay 514 COM
15 NO
16 NC
Relay 6
17 COM
18 NO
19 NC
Relay 720 COM
21 NO
22 NC
Relay 823 COM
24 NO
25 NC
Relay 926 COM
27 NO
28 NC
Relay 1029 COM
30 NO
31 NC
Relay 1132 COM
33 NO
34 NC
Relay 1235 COM
36 NO
Table 5.
Table 6. Relay Output Module Connections
4.12 mA Output Module
This is an optional module for providing isolation mA loop
output (Ch.4.13).
Terminal Label Output
1 I+
mA Out 1
2 I–
3 I+
mA Out 2
4 I–
5 I+
mA Out 3
6 I–
7 I+
mA Out 4
8 I–
Table 7. mA Output Module Connections
4.13 Field Device Circuit Diagrams
Figure 7. Dedicated Alarm Circuit Figure 8. Three Wire Devices
Figure 9. Two Wire Loop Devices Figure 10. Two Wire Barrier Devices
Figure 11. Catalytic Devices Figure 12. Relay Devices
Figure 13. Remote Switches Figure 14. mA Output Devices
4.14 Backup Battery Option
The optional backup battery is shipped in sleep mode. You
must read the manual before connecting it to the system.
Figure 15. Backup Battery Connection
5 Technical Specifications
General Specifications
Capacity Up to 8 inputs Base Unit, + 8 inputs with Expansion Unit
Type of Inputs 2 or 3 wires, mA, mV
Size (Wall Units only) 426 mm x 300 mm x 156 mm
Weight 9 Kg (20 lbs) Base Unit, 8.5 Kg (18.7 lb) Expansion Unit
User Interface
Display 7 inch Colour LCD Touch Screen GUI
Visual Indicators 3 LED Master Indicators and 16 LED inputs, Green for
Normal, Yellow for Fault/ Inhibit, and Red for Alarm
Audible Alarm 70 dB @ 1 metre (40 ins)
Button One alarm mute and reset membrane button
Languages Selectable English, Chinese (Simplified), Dutch, French,
German, Italian, Portuguese, Russian, Spanish
Power Supply
Power AC AC 110/220 V, 50 — 60 Hz
(Manual Voltage Selection via SMPS)
Power DC DC 18 — 32 V (24 VDC Nominal). DC 24 – 32 V advised
Power Consumption 105 W max (including field devices), 210 W max with
Expansion Unit
Environmental
Operating Temperature –10 to +55 °C (+14 to +131 °F) continuous operation
Storage Temperature Instrument –25 to +60 °C (–13 to +140 °F)
Humidity Range 5 – 95 %RH non-condensing
Ingress Protection IP65 (wall mounted), NEMA 4X indoors only
I/O Capacities
mV Input Pellistor type Catalytic gas sensors (HA models).
2, 4, or 8 channels with Base Unit or 10, 12, or 16
channels with Expansion Unit
4 – 20 mA Input 2 or 3 wire, SOURCE. 2, 4, or 8 channel module
4 – 20 mA Output 4 or 8 repeated 0 – 22 mA outputs, 12 or 16 with
expansion unit. (4 – 20 mA = 0 – 100 %FSD)
Relay Output Configurable time delay On/Off option. 1.7 A @ 250 VAC,
1.7 A @ 30 VDC, 12 relays per module
Certifications
Electrical Safety Compliant with CE, EN 50270:2015, UL/
IEC/EN 61010-1, UL 508
Performance
ATEX, EN 60079-29-1 (pending)
EN 50104 (pending), EN 45544 (pending)
SIL 2 (pending)
CSA 22.2 no.152
CCCF, China – GB16808-2008 (pending)
Marine MED (pending)
Hazardous Approval ISA 12.12.01–2013 (Class 1, Div 2, Groups A,B,C,D & T4)
CSA C22.2 No. 213–M1987
Others
Backup Batteries 22.2 V Lithium Ion, 2600 mAh.
Circa 30 mins Buffer time when fully charged.
Data Logging Configuration backups and event / TWA logging onto SD
Card. Can be transferred to PC or Printer (.bin and .csv)
Communication Modbus RTU & TCP, Web Monitoring
6 Default Password
The default access password for all levels is TPPL, but it is the
User’s responsibility to immediately change the passwords as
to avoid unauthorized access. Full instructions are contained in
the Technical Handbook, and Honeywell will not accept any
liability caused by failing to follow these instructions.
Find out more:
www.honeywellanalytics.com
Please Note:
While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for
errors or omissions. Data may change, as well as legislation and you are strongly advised to obtain copies of the
most recently issued regulations, standards and guidelines. This publication is not intended to form the basis of a
contract.
Part No. 3011M5000_EN
H_MAN0985_HAA160009
Iss.2.0_02/2016
© 2016 Honeywell Analytics