Honeywell ESSER User manual

Manual de Instalación
Pulsador Manual compacto IQ8
Installation Instruction
IQ8Electronic module / Manual Call Point
(Ref. / Part No. 804955 / 804971)
798936 Cambios técnicos reservados!
05.2007 GB Technical changes reserved!
Novar GmbH a Honeywell Company
Dieselstraße 2, D-41469 Neuss
Internet: www.esser-systems.de
E-Mail: [email protected]
Cuando se usa un Pulsador IQ8 como pulsador de Alarma, se
debe usar una carcasa roja con una etiqueta de identificación con
el símbolo correcto como es mostrado en Fig. 3 y 4.
Cuando se usan diferentes carcasas o diferentes símbolos, el
equipo está clasificado como equipo de activación y no como
Pulsador de Alarma
Observe la secuencia correcta en el cableado de lazo analógico!
Terminales 1-4 ULIN (Entrada) ÖULOUT (Salida).
Use cable de comunicaciones claramente identificado
I-Y (St) Y n x 2 x 0.8 mm o cable para alarma de incendio!
La conexión de la malla del cable debe realizarse al Terminal de
tierra para evitar interferencias.
Use junta de paso para cableado para evitar el acceso de
humedad.
Se debe tener en cuenta durante el mantenimiento o labores de
reparación la activación de sistemas de aviso como por ejemplo
activación a central receptora.
Información adicional y actualizada
Las especificaciones se refieren al la fecha de creación del
documento y pueden ser modificadas o variadas sobre la
normativa aplicada o la información facilitada.
Para obtener la información actualizada para mantenimiento o
configuración de los sistemas, contacte con su proveedor para
que se la facilite o en
www.esser-systems.de.
Siguiendo normas de instalación de VdS no es posible configurar
Pulsadores y Detectores en la misma zona de Detección (max. 10
MCP por zona de detector.
La conexión de una zona externa a este Pulsador IQ8 no está
regulado por la normativa Vds.
GB
When the MCP is used as a manual call point it must be installed
in a red housing with an identification label showing the
standardize-conformal symbol as shown in Fig. 3/4. When
housings with different colours and identification labels are used
the unit is classed as a manual activation device and not as a
manual call point.
Observe the correct wiring sequence for the analog loop!
Terminals 1-4 ULIN (Input) ÖULOUT (Output).
Use designated communication cable I-Y (St) Y n x 2 x 0.8 mm or
fire alarm cable!
Connection of the cable shield to the ground terminal protects the
signal cables against interference.
The alarm activation and triggering of notifying systems e.g.
manned centre link (Master box) must be observed during any
Service of the MCP.
Install inlying cable with a dripping bend to protect the device from
dampness.
Additional and updated Informations
The product specification relate to the date of issue and may differ
due to modifications and/or amended Standards and Regulations
from the given informations.
For updated informations to commissioning and maintenance of
Fire alarm detectors refer to www.esser-systems.de.
Pursuant to the VdS guidelines MCPs and automatic fire
detectors must not be operated in a common detector zone
(max. 10 MCP per detector zone).
Connection of an external detector zone (D-Line) to this IQ8 MCP
is not in accordance to the VdS guidelines.
By using the mounting frame (Part No. 704967) the white covering
must be fitted.
Importante!
Se declina toda responsabilidad sobre daños derivados y garantía
por no seguir estas instrucciones de instalación. Estas
instrucciones deben ser tenidas en cuenta cuidadosamente antes
de proceder a la puesta en marcha del módulo electrónico IQ8 /
Pulsador Manual de Alarma IQ8.
Información de seguridad
•NUNCA conecte el pulsador directamente a 220V ac
•Instale el pulsador dentro el rango de temperatura
especificado.
•Solo técnicos cualificados que estén familiarizados con los
riesgos específicos y las normativas correspondientes deben
llevar a cabo las operaciones de reparación y mantenimiento
del Pulsador.
•El pulsador no debe ser alterado ni modificado.
General
El pulsador electrónico IQ8 (Ref. 804955) y respectivamente el pulsador
manual (Ref. 804971) con carcasa roja está identificado con un símbolo
de una “casa ardiendo” para activación manual de sistemas de alarma u
otros sistemas en espacios secos no sujetos a riesgos de explosión. El
pulsador también está disponible en otras versiones para otras
aplicaciones, por ejemplo en carcasas de diferentes colores y con
elección de diferentes colores o etiqueta de identificación (ver tabla -
página 2). El modo de operación se indica mediante el parpadeo del led
verde LED 1 (H); (ver Fig. 4).
Funccionamiento Revise ésta información!
Activar Alarma: Presione el cristal hacia adentro hasta que aparezca la
lengüeta amarilla (G) en la zona superior de la ventana y
el LED Rojo (F) parpadee (Fig. 4).
Suba la cubierta de llave (A) e inserte la llave.
Rearme Pulsador con Cristal
Abra la caja y retire el cristal. Gire la llave (C) en sentido
horario hasta el tope derecho (M) (Fig. 5). Abra la
cubierta y reemplace el cristal, gire la llave en sentido
contrahorario hasta el tope izquierdo (N) para subir la
lámina (Fig. 6).
Pulsador con lámina rearmable
Gire la llave (C) en sentido horario hasta el tope derecho
(M) (Fig. 5). Coloque la lámina (K) correctamente y gire
la llave en sentido contrahorario hasta el tope izquierdo
(N) para subir la lámina (Fig. 6).
Prueba: Gire la llave (C) en sentido horario hasta el tope derecho
(M) hasta que la lámina caiga y se indique la activación
(F/G) (Fig. 4). Para rearmar el equipo gire la llave en
sentido contrahorario hasta el tope izquierdo (N), para
subir la lámina.
Instalación
Montaje
empotrado: El pulsador puede instalarse sobre caja de mecanismo
estándar (Ø 55 – 60mm)
Montaje en
Superficie: El pulsador se instala sobre caja sde superficie (opcional) o
con marco de montaje universal (opcional). Instale el
Pulsador de un modo seguro, en una pared apropiada
sobre una superficie lisa, con los tornillos y tacos
adecuados. (Fig. 7/8).
Apertura: Inserte la llave por sus dos patillas en los orificios
inferiores de la cubierta (abajo). Presione hacia arriba
para liberar la tapa (Fig. 2). Tire desde abajo hacia fuera
hasta retirar la tapa.
Cierre: Gire la llave en sentido contrahorario hasta su tope
izquierdo (Fig. 6). Coloque la lengüeta superior de la
cubierta sobre las ranuras del módulo del pulsador y
presione hasta encajar la cubierta en su posición.
Símbolo: Abra la carcasa como se ha indicado y quite la lámina
transparente de plástico (D/E) presionando hacia afuera,
coloque el pictograma adecuado en el frontal, coloque de
nuevo la lámina transparente sobre el nuevo pictograma
y presione hasta su posición (Fig. 3).
Etiqueta: Para indicar equipo fuera de uso (K).
Lámina de
plástico o
cristal:
Gire la llave en sentido horario hasta el tope derecho
(Fig. 5). Inserte la lámina o cristal en su posición (J/L) en
el hueco frontal deslice la lámina hacia arriba girando la
llave en sentido contrahorario. (Fig. 6).
Terminales: Los terminales 1-8 pueden extraerse para facilitar la
instalación (Fig. 10).
La pantalla del cable debe interconectarse en regleta
separada. La caja de superficie tiene un terminal
apropiado para conectar la pantalla (opcional) (Fig. 7).
Cubierta
Abatible:
Ref. 704965
(opcional)
Para proteger de activaciones no intencionadas y para
aumentar el grado de protección de IP 43 a IP 55.
La cubierta abatible (O) se inserta en los orificios
laterales (P) de la carcasa y puede precintarse en caso
necesario (B) (Fig. 2/9).
Cableado Típico (Fig. 10)
Los Pulsadores se conectan al lazo analógico del Sistema de Detección
de Incendios 8000 o IQ8Control. Los Pulsadores deben configurarse
juntos en sus propias zonas de detección. Conecte los cables de la zona
de detector a los terminales 1-4.
Pulsador con aislador de zona y Línea Externa (Ref. No. 804905)
Los aisladores de zona sirven para asegurar el funcionamiento del
sistema en caso de que se produzca una avería en el lazo, por ejemplo
en caso de un cortocircuito. Cuando esto sucede, el aislador abre y
desconecta la sección del lazo entre los aisladores. Aperturas de lazo
no afectan al funcionamiento correcto del lazo. Es posible conectar una
línea externa de detección (D-line) con Pulsadores convencionales
(Resistencia en Alarma interior para cada Pulsador de 1 KOhm) por
ejemplo Ref. No. 804900 o 804901 a este modelo de Pulsador IQ8.
Cuando se produce una alarma se muestra de modo automático la
dirección y la etiqueta programada del Pulsador IQ8 a la que el
pulsador convencional está conectado. La longitud total de cable de la
zona externa no debe exceder de 500m. Inserte en el último pulsador
de la línea externa una resistencia RFL de 10 KOhm (Fig. 10). Si no se
conecta nada en la línea externa D-line se debe conectar una
resistencia de 10 KOhm directamente en los terminales 7/8 (Fig.10).
Características Técnicas
Alimentación : 8 V cc a 42 V cc
Consumo reposo @ 19 V DC : 45 µA aprox.
Consumo alarma : 9 mA aprox. pulsante
Número Pulsadores : max. 127 por lazo
Indicación alarma : LED rojo / lámina amarilla
Indicador funcionamiento : LED verde
Terminales : 2,5 mm² máx. (AWG 26-14)
Temperatura trabajo : -20 °C a +70 °C
Temperatura almacenamiento : -30 °C a +75 °C
Grado de protección : IP 43 (en carcasa)
: IP 55 (con cubierta abatible)
Caja : Plástico PC/ASA
Color : Rojo (similar RAL 3020)
Peso : 110 g aprox.
Dimensiones (a x h x f) : 88 x 88 x 21 (mm)
Diemnansiones con caja sup. : 88 x 88 x 57 (mm)
Especificación : EN 54-11, Typ A
Certificado VdS : G 205132
GB
Important!
Any damage caused by failure to observe the installation instructions voids
the product guarantee. Furthermore, no liability can be accepted for any
consequential damage arising from such failure. These instructions must
be studied carefully before installing and configuring the IQ8Electronic
module / Manual Call Point (MCP).
Safety information
•NEVER connect the MCP directly to a 230V AC mains power supply.
•Only operate in the specified ambient temperature range.
•Only qualified technicians who are fully familiar with all the associated
hazards and the applicable legislation and regulations may perform
maintenance and repair work on the call point.
•The call point may not be changed or modified in any way.
General
The IQ8Electronic module (Part No. 804955) respectively the IQ8Manual
Call Point (Part No. 804971) in the red housing identified with a “burning
house” symbol is designated for use as a call point for manually triggering
fire alarms or other hazard alarms in dry workplaces not subject to
explosion hazards. The call point is also available in other versions for
other applications, for example in housings with different colours and with
a choice of different identification labels (refer to table - page 2). The
operation mode is displayed via the flashing green LED (H); (Fig. 4).
Operation Observe Info!
Trigger alarm: Press screen centre inwards until the yellow tab indicator
(G) is visible in the upper area and the red LED (F) is
flashing (Fig. 4).
Push up the keyhole cover (A) to insert the key.
Reset: Detector with glass screen
Open housing and remove the broken glass. Turn key
(C) clockwise until the right (L) stop position
(Fig. 5). Replace glass screen and turn key (M) anti-
clockwise until the left stop position to lift screen upwards
(Fig. 6).
Detector with plastic operating panel
Turn key (C) clockwise until the right (L) stop position
(Fig. 5). Align the plastic operating panel (K) and turn key
(M) anti-clockwise until the left stop position to lift screen
upwards (Fig. 6).
Test mode: Turn key (C) clockwise (L) until the screen moves
downwards and the activation (F/G) is indicated (Fig. 4).
To reset the detector after a test simply turn key (M) to
the left stop position to lift screen upwards.
Installation
Flush mounting The Manual Call Point is installed on a conventional
standard housing (Ø 55 – 60mm).
Surface
mounting The Manual Call Point is installed on a back box for
surface mounting (option) or with an universal installation
frame for wall mounting (option). The call point securely
on a suitable wall with a smooth surface, e.g. with 2
screws (length ≥40mm) and dowels (S6) (Figs. 7/8).
Opening: Insert the key with the both tenons in the opening at the
bottom of the housing (Fig. 2) to release the cover lock.
Lift up the bottom edge of the cover a little to release it
and then remove it.
Closing: Turn key lock anti-clockwise until the left stop position
(Fig. 6). Position the upper edge of the cover in the
groove at the top of the base and then press the cover
down until it locks into position.
Symbolism: Open the housing and remove the transparent plastic
cover (D/E) by prising it out. Insert the appropriate
identification label from the front. Align the cover and
snap it back into place (Fig. 3).
Paper inlay: To indicate that the detector is out of order (K)
Plastic
operating panel
or
glass screen:
Turn key lock clockwise until the right stop position
(Fig. 5). Insert screen aligned (J/L) in the front recess
und move screen upwards by turning the key anti-
clockwise until the left stop position (Fig. 6).
Terminals: The screw terminals 1-8 can be removed to simplify the
installation (Fig. 10).
The cable shield of the connection cable must be
interconnected by using a single terminal block. The
back box (option) provides an integrated screw terminal
for the shield connection (Fig. 7).
Hinged cover:
Part No. 704965
(Option)
To protect the detector for unintended activation and to
increase the protection rating from IP 43 up to IP 55.
The hinged cover (O) is fixed by the sideway dents (P) of
the housing and may be sealed (B) if required (Fig. 2/9).
Typical wiring (Fig. 10)
The MCPs are connected to the analog loop of the System 8000 or
IQ8Control fire alarm control panel. Manual call points must be configured
together in their own detector zones. Connect the detector zone
connection cable to terminals 1-4.
Call point with zone isolator and ext. D Line
The zone isolators ensure that the system continues to function even if a
segment of the loop circuit fails due to a short circuit. When a short circuit
occurs the zone isolators before and after the short circuit open,
disconnecting the section of the loop between the isolators. Simple wire
breaks do not affect the functionality of the loop circuit. An external
detector zone (D-line) with up to 10 standard manual call points (internal
Alarm resistor for each detector 1KOhm) may be connected to a single IQ8
Manual Call Point. When an alarm is triggered the address and the
programmed additional text of the IQ8 Manual Call Point to which the
standard zone is connected are displayed automatically. The total cable
length of the external call point zone should not exceed 500 meters!
Terminate the last call point of the external D-line with a 10 KOhm End-of-
line resistor (Fig. 10).
If no external D-line is connected the 10KOhm terminating resistor must be
installed directly to terminals 7/8 (Fig. 10).
Specification
Power supply : 8 V DC to 42 V DC
Quiescent current @ 19 V DC : approx. 45 µA @ 19 V DC
Alarm current : approx. 9 mA, pulsed
No. of call points : max. 127 MCP per loop
Alarm indicator : red LED / yellow tab
Operation indicator : green LED
Connection terminals : max. 2.5mm² (AWG 26-14)
Application temperature : -20 °C to +70 °C
Storage temperature : -30 °C to +75 °C
Protection rating : IP 43 (in housing)
: IP 55 (with hinged cover)
Housing : PC/ASA plastic
Colour : red (similar RAL 3020)
Weight : approx. 110 g
Housing dimensions (w x h x d) : 88 x 88 x 21 (mm)
Dimensions with back box : 88 x 88 x 57 (mm)
Call point specification : EN 54-11, type A
VdS approval : G 205132
GB
Opción Ref. Options Part No.
Carcasa Azul similar RAL 5015 704951 Housing for MCP, blue similar to RAL 5015 704951
Cristal de repuesto (10 Uds.) 704960 Replacement glass screen (10 pieces) 704960
Etiqueta transparente para impresión de otros iconos (10 Uds.) 704961 Label, transparent with whit printing, differing from standard icons (10 pieces) 704961
Lámina deplástico rearmable (L) (10 Uds.) 704964 Plastic operating panel (L) resettable, white (10 pieces) 704964
Cubierta transparente abatible (O) para protección de activaciones no intencionadas y aumento de
grado de protección IP 43 a IP 55 704965 Hinged cover (O) to protect the detector for unintended activation and to increase
the protection rating from IP 43 up to IP 55 704965
Llave de repuesto (10 Uds.) 704966 Replacement key (10 pieces) 704966
Marco de monataje para pulsador compacto rojo + blanco (132 x 132 x 8 mm) 704967 Frame for small Manual Call Points incl. cover red + white (132 x 132 x 8 mm) 704967
Caja de montaje en superficie rojo similar RAL 3020 704980 Back box for surface mounting, red similar to RAL 3020 704980
Caja de montaje en superficie azul similar RAL 5015 704981 Back box for surface mounting, blue similar to RAL 5015 704981
instalación / Mounting
88
88
A
15
21
C
B
D
E
Fig.1: Dimensiones
Fig. 1: Dimensions Figura 2: Apertura de la tapa / carcasa
Fig. 2: Open the housing / seal Figura 3: Etiqueta de identificación
Fig. 3: Identification label
FG H
J
Glasscheibe
Glass screen
Oben
Top
KOut of
Order Außer
Betrieb
Papiereinleger
Paper inlay Oben
Top
L
Kunststoffbedienfeld (Art.-Nr. 704964)
Plastic operating panel (Part No.704964)
Oben
Top
M
N
Figura 4: Indicacidores LED y cubiertas de Plástico rearmable, cristal y papel
fuera de uso
Fig. 4: Mechanical alarm indicator and LED,
Glass screen, paper inlay and plastic operating panel
Figura 5: Posición de llave para prueba / extraer cristal
Fig. 5: Key lock position for test mode and removing screen Figura. 6: Posición de llave para rearme / insertar cristal
Fig. 6: Key lock position for Reset / Replace screen
36
THIS WAY UP
50
88
88
44
18,5
132
132
O
P
Figura 7: Caja de montaje en superficie (Ref. 704980)
Fig. 7: Back box for surface mounting (Part No. 704980) Figura 8: Marco de montaje universal (Art.-Nr. 704967)
Fig. 8: Universalinstallation incl. cover (Part No. 704967) Figura 9: Cubierta abatible (Ref. 704965)
Fig. 9: Hinged cover (Part No. 704965)
Sistema 8000 / IQ8Control
-ULin 1
-ULout 2
+ULin 3
+ULout 4
5
6
-ext. D-Linie 7
+ext. D-Linie 8
-ULin 1
-ULout 2
+ULin 3
+ULout 4
5
6
-ext. D-Linie 7
+ext. D-Linie 8
10K
10K
10K
Analog-Ring-Modul
Analog Loop Module
A+
A-
B+
B-
-ULin 1
-ULout 2
+ULin 3
+ULout 4
5
6
-ext. D-Linie 7
+ext. D-Linie 8
Figura 10: Conexionado de lazo analógico
Fig. 10: Analog loop wiring
Cristal/Glass
Indicador de Papel /
Pa
p
er inla
y
Lámina rearmable Ref.704964
Plastic operating panel Part.Nº 704964
Arriba
Top
Arriba
Top
Arriba
Top

Other Honeywell Security System manuals

Honeywell VISTA-128FBPT User manual

Honeywell

Honeywell VISTA-128FBPT User manual

Honeywell Lynx Plus Series User manual

Honeywell

Honeywell Lynx Plus Series User manual

Honeywell INTELLIGUARD 9000 Manual

Honeywell

Honeywell INTELLIGUARD 9000 Manual

Honeywell Domonial User manual

Honeywell

Honeywell Domonial User manual

Honeywell GENT Xenex Product guide

Honeywell

Honeywell GENT Xenex Product guide

Honeywell LYNX Touch L5210 Series Operating instructions

Honeywell

Honeywell LYNX Touch L5210 Series Operating instructions

Honeywell HS3SSXX User manual

Honeywell

Honeywell HS3SSXX User manual

Honeywell FG8MS User manual

Honeywell

Honeywell FG8MS User manual

Honeywell Friedland FGGA04 Series User manual

Honeywell

Honeywell Friedland FGGA04 Series User manual

Honeywell LYNX Touch L7000 Series User manual

Honeywell

Honeywell LYNX Touch L7000 Series User manual

Honeywell Ademco Lynx Touch User manual

Honeywell

Honeywell Ademco Lynx Touch User manual

Honeywell ADEMCO 4110XM User manual

Honeywell

Honeywell ADEMCO 4110XM User manual

Honeywell GENT Nano panel-based Training manual

Honeywell

Honeywell GENT Nano panel-based Training manual

Honeywell Galaxy 3-48C Owner's manual

Honeywell

Honeywell Galaxy 3-48C Owner's manual

Honeywell Fire-Lite Alarms MS-9200UDLSC User manual

Honeywell

Honeywell Fire-Lite Alarms MS-9200UDLSC User manual

Honeywell SD500-PSDA User manual

Honeywell

Honeywell SD500-PSDA User manual

Honeywell TCPA1BS User manual

Honeywell

Honeywell TCPA1BS User manual

Honeywell ADEMCO VISTA SERIES Operating instructions

Honeywell

Honeywell ADEMCO VISTA SERIES Operating instructions

Honeywell LYNX Touch Security System User manual

Honeywell

Honeywell LYNX Touch Security System User manual

Honeywell ADEMCO VISTA-15PSIA Assembly instructions

Honeywell

Honeywell ADEMCO VISTA-15PSIA Assembly instructions

Honeywell Frieland FGGA06 Series User manual

Honeywell

Honeywell Frieland FGGA06 Series User manual

Honeywell Domonial User manual

Honeywell

Honeywell Domonial User manual

Honeywell ADEMCO LYNXR Series User manual

Honeywell

Honeywell ADEMCO LYNXR Series User manual

Honeywell Ademco Vista-12D Assembly instructions

Honeywell

Honeywell Ademco Vista-12D Assembly instructions

Popular Security System manuals by other brands

CrimeStopper CG-1000 installation guide

CrimeStopper

CrimeStopper CG-1000 installation guide

nest Nest Secure user guide

nest

nest Nest Secure user guide

Bosch ICP-CP508 user guide

Bosch

Bosch ICP-CP508 user guide

Honeywld MyGuardian XC-109 Getting started

Honeywld

Honeywld MyGuardian XC-109 Getting started

E2S D1xC2 Series Instructions/service manual

E2S

E2S D1xC2 Series Instructions/service manual

Zipato ZIPABOX Quick installation guide

Zipato

Zipato ZIPABOX Quick installation guide

NAPCO Continental Access SUPER TWO CICP1300IOCOMBO Installation and service manual

NAPCO

NAPCO Continental Access SUPER TWO CICP1300IOCOMBO Installation and service manual

WICOMM RW232M Installation and reference guide

WICOMM

WICOMM RW232M Installation and reference guide

Night Owl Tiger-4500 instruction manual

Night Owl

Night Owl Tiger-4500 instruction manual

Eaton Crouse-hinds series Safety manual

Eaton

Eaton Crouse-hinds series Safety manual

Philips VSS7374/D4T user manual

Philips

Philips VSS7374/D4T user manual

Transistor Lynx Tactum manual

Transistor

Transistor Lynx Tactum manual

American Dynamics MegaPower 3200 installation guide

American Dynamics

American Dynamics MegaPower 3200 installation guide

Time2 Clan Noah user guide

Time2

Time2 Clan Noah user guide

Zorachka Homam manual

Zorachka

Zorachka Homam manual

ProCurve J8462A quick start guide

ProCurve

ProCurve J8462A quick start guide

smartvue S8 user guide

smartvue

smartvue S8 user guide

Honeywell Home VISTA-21iP user guide

Honeywell Home

Honeywell Home VISTA-21iP user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.